Bulletin I27402 rev. B 07/03 IRKD600.. SERIES SUPER MAGN-A-pakTM Power Modules STANDARD DIODES 600 A Features High current capability 3000 V RMS isolating voltage with non-toxic substrate High surge capability High voltage ratings up to 2000V Industrial standard package UL E78996 approved Typical Applications Rectifying bridge for large motor drives Rectifying bridge for large UPS Major Ratings and Characteristics Parameters IF(AV) A 100 C 942 A @ TC 100 C @ 50Hz 19.0 KA @ 60Hz 20.1 KA @ 50Hz 1805 KA2s @ 60Hz 1683 KA2s 18050 KA2s IF(RMS) 2 I t Units 600 @ TC IFSM IRKD600.. I2t VRRM range 800 to 2000 V TSTG range - 40 to 150 C TJ range - 40 to 150 C www.irf.com 1 IRKD600.. Series Bulletin I27402 rev. B 07/03 ELECTRICAL SPECIFICATIONS Voltage Ratings Voltage Type number Code IRKD600.. VRRM , maximum repetitive VRSM , maximum non- peak reverse voltage V repetitive peak rev. voltage V 08 800 900 12 1200 1300 16 1600 1700 20 2000 2100 IRRM max. @ TJ max. mA 50 Forward Conduction Parameter I F(AV) IRKD600.. Units Conditions Maximum average forward current 600 A @ Case temperature 100 C 180 conduction, half sine wave I F(RMS) Maximum RMS forward current 942 A IFSM Maximum peak, one-cycle forward, 19.0 KA t = 10ms No voltage non-repetitive surge current 20.1 t = 8.3ms reapplied 16.2 t = 10ms 100% VRRM 17.2 t = 8.3ms reapplied Sinusoidal half wave, t = 10ms No voltage Initial TJ = TJ max. t = 8.3ms reapplied It 2 Maximum I t for fusing 2 1805 KA s 2 1683 I2t Maximum I2t for fusing 180 conduction, half sine wave @ TC = 100C 1319 t = 10ms 100% VRRM 1230 t = 8.3ms reapplied 18050 VF(TO)1 Low level value of threshold voltage 0.70 VF(TO)2 High level value of threshold voltage 0.77 rf1 Low level value of forward slope resistance 0.28 rf2 High level value of forward slope resistance 0.25 V FM Maximum forward voltage drop 1.45 KA2s t = 0.1 to 10ms, no voltage reapplied V (16.7% x x IF(AV) < I < x IF(AV)), TJ = TJ max. (I > x IF(AV)), TJ = TJ max. m (16.7% x x IF(AV) < I < x IF(AV)), TJ = TJ max. (I > x IF(AV)), TJ = TJ max. V Ipk = 1800A, TJ = 25C, tp = 10ms sine pulse Blocking Parameter VINS RMS isolation voltage IRRM Maximum peak reverse and off-state IRKD600.. Units Conditions 3000 V 50 mA t=1s TJ = TJ max., rated VRRM applied leakage current 2 www.irf.com IRKD600.. Series Bulletin I27402 rev. B 07/03 Thermal and Mechanical Specifications Parameter IRKD600.. TJ Max. junction operating temperature range - 40 to 150 Tstg Max. storage temperature range - 40 to 150 RthJC Max. thermal resistance, junction to Units Conditions C 0.065 K/W 0.02 K/W 6-8 Nm Per junction, DC operation case RthC-hs Max. thermal resistance, case to heatsink T Mounting torque 10%SMAP to heatsink busbar to SMAP wt 12 - 15 Approximate weight 1500 Case style A mounting compound is recommended and the torque should be rechecked after a period of 3 hours to allow for the spread of the compound g SUPER MAGN-A-pak See outline table RthJC Conduction (The following table shows the increment of thermal resistance RthJC when devices operate at different conduction angles than DC) Conduction angle Sinusoidal conduction Rectangular conduction 180 0.009 0.006 120 0.011 0.011 90 0.014 0.015 60 0.021 0.022 30 0.037 0.038 Units Conditions K/W TJ = TJ max. Ordering Information Table 1 Device Code 1 - ~ IRK D 600 1 2 3 - 20 4 Module type 2 - Circuit configuration D = 2 diodes in series 3 - Current rating 4 - Voltage code: Code x 100 = VRRM (See Voltage Ratings Table) + 2 3 www.irf.com 3 IRKD600.. Series Bulletin I27402 rev. B 07/03 Outline Table 4 150 IRKD600.. Series R thJC (DC) = 0.065 K/W 140 130 Conduction Angle 120 110 100 30 60 90 120 90 180 80 0 100 200 300 400 500 600 700 Maximum Allowable Case Temperature (C) Maximum Allowable Case Temperature (C) All dimensions in millimeters (inches) 150 IRKD600.. Series R thJC (DC) = 0.065 K/W 140 130 120 Conduction Period 110 60 100 30 90 90 120 180 DC 80 0 200 400 600 800 1000 Average Forward Current (A) Average Forward Current (A) Fig. 1 - Current Ratings Characteristics Fig. 2 - Current Ratings Characteristics www.irf.com IRKD600.. Series 700 180 120 90 60 30 600 500 RMS Limit 400 300 Conduction Angle 200 IRKD600.. Series Per Junction TJ = 150C 100 0 0 100 200 300 400 500 1000 DC 180 120 90 60 30 900 800 700 600 500 RMS Limit 400 Conduction Period 300 IRKD600.. Series Per Junction T J= 150C 200 100 0 0 600 200 400 600 800 1000 Average Forward Current (A) Average Forward Current (A) Fig. 3 - Forward Power Loss Characteristics Fig. 4 - Forward Power Loss Characteristics 18000 Peak Half Sine Wave Forward Current (A) Peak Half Sine Wave Forward Current (A) Maximum Average Forward Power Loss (W) Maximum Average Forward Power Loss (W) Bulletin I27402 rev. B 07/03 At Any Rated Load Condition And With Rated V RRM Applied Following Surge. 16000 Initial TJ = 150C @ 60 Hz 0.0083 s 14000 @ 50 Hz 0.0100 s 12000 10000 8000 IRKD600.. Series Per Junction 6000 4000 1 10 100 20000 Maximum Non Repetitive Surge Current Versus Pulse Train Duration. Initial T J = 150C No Voltage Reapplied Rated VRRM Reapplied 18000 16000 14000 12000 10000 8000 IRKD600.. Series Per Junction 6000 4000 0.01 0.1 Number Of Equal Amplitude Half Cycle Current Pulses (N) Fig. 5 - Maximum Non-Repetitive Surge Current Fig. 6 - Maximum Non-Repetitive Surge Current 1000 A = W K/ S R th 2 0.0 K/ W -D el ta 0.2 5K /W 0.3 5K /W 0.5 K /W R IRKD600.. Series Per Junction TJ = 150C 200 W K/ 400 K/ W 0. 12 K/ W 0. 1 6K /W 4 180 (Sine) 600 0. 08 6 DC 800 0 0. 0 0. Maximum Total Forward Power Loss (W) 1 Pulse Train Duration (s) 0 0 200 400 600 800 Total RMS Output Current (A) 1000 0 25 50 75 100 125 150 Maximum Allowable Ambient Temperature (C) Fig. 7 - Forward Power Loss Characteristics www.irf.com 5 IRKD600.. Series Bulletin I27402 rev. B 07/03 /W -D el ta R 2 x IRKD600.. Series Single Phase Bridge Connected T J = 150C 1K 0.0 0.12 500 = /W K/ W 0.0 8K 1000 A 1500 K/ W 4K 0.0 5 S R th 2000 0. 0 W K/ 0. 03 180 (Sine) 180 (Rect) 2500 02 0. Maximum Total Power Loss (W) 3000 /W K/W 0.2 K /W 0 0 200 400 600 800 1000 1200 0 Total Output Current (A) 25 50 75 100 125 150 Maximum Allowable Ambient Temperature (C) Fig. 8 - Forward Power Loss Characteristics R th 4000 SA 0. 02 3000 1500 0.08 3 x IRKD600.. Series Three Phase Bridge Connected T J = 150C 500 /W R 2000 0.0 5 ta el 3K 2500 1000 K/ W -D 0 .0 W K/ 120 (Rect) 01 0. 3500 = Maximum Total Power Loss (W) 4500 K/W K/W 0.12 K /W 0.2 K /W 0 0 300 600 900 1200 1500 1800 0 25 50 75 100 125 150 Maximum Allowable Ambient Temperature (C) Total Output Current (A) Transient Thermal Impedance Z thJC (K/W) Fig. 9 - Forward Power Loss Characteristics 0.1 IRKD600.. Series Per Junction 0.01 Steady State Value: R thJC = 0.065 K/W (DC Operation) 0.001 0.001 0.01 0.1 1 10 100 Square Wave Pulse Duration (s) Fig. 10 - Thermal Impedance ZthJC Characteristic 6 www.irf.com