https://www.phoenixcontact.com/gb/products/2320238
26/03/2014Page2/9
Uninterruptible power supply-QUINT-UPS/ 24DC/ 24DC/20-2320238
Technical data
Ambient conditions
Max. permissible relative humidity (operation) ≤ 95 % (25°C, non-condensing)
Noise immunity EN 61000-6-2:2005
Input data
Nominal input voltage 24 V DC
Input voltage range 18 V DC ... 30 V DC
Current consumption 32.9 A (Maximum, mains operation)
10.5 mA (No load, mains operation)
6.9 A (Charging, mains operation)
Current consumption (maximum) 32.9 A (Maximum, mains operation)
Current consumption (idle) 10.5 mA (No load, mains operation)
Current consumption (charging process) 6.9 A (Charging, mains operation)
Buffer period 1 h (With battery module 38 AH)
Output data
Nominal output voltage 24 V DC
Output voltage range 18 V DC ... 30 V DC
Output current 20 A (-25 °C ... 50 °C)
Derating 60 °C ... 70 °C (2.5%/K)
Connection in parallel Yes, up to 2 modules with redundancy module
Connection in series No
General
Net weight 0.6 kg
Efficiency > 98 % (Mains operation, with charged power storage)
98 % (Battery operation)
Protection class III
MTBF (IEC 61709, SN 29500) > 500000 h (According to EN 29500)
Mounting position horizontal DIN rail NS 35, EN 60715
Assembly instructions Can be aligned: horizontal 5 mm, vertical 50 mm
Electromagnetic compatibility Conformance with EMC Directive 2004/108/EC
Low Voltage Directive Conformance with LV directive 2006/95/EC
Standard - Electrical safety EN 60950-1/VDE 0805 (SELV)
Standard – Electronic equipment for use in electrical power installations
and their assembly into electrical power installations EN 50178/VDE 0160 (PELV)
UL approvals UL/C-UL Recognized UL 60950
UL Listed UL 508
Connection data, input
Connection method Screw connection
Conductor cross section solid min. 0.2 mm²
Conductor cross section solid max. 6 mm²
Conductor cross section stranded min. 0.2 mm²