Part Number: 2413F
CAT6+ Horizontal, 4pr, F/UTP, LS-PVC Jkt, CMP
Product Description
CAT6+ (350MHz), 4-Pair, F/UTP-foil shielded, Plenum-CMP, Premise Horizontal cable, 23 AWG solid bare copper conductors, FEP/PO insulation, patented
X-spline, overall Beldfoil® shield, Flamarrest® jacket
Technical Specifications
Product Overview
Environmental Space: Plenum
Suitable Applications: Networking Horizontal Cable, HDBaseT, 1000Base-T (Gigabit Ethernet), 100Base-T (Fast Ethernet), 10Base-T (Ethernet), 100BaseVG, ANYLAN, 155ATM, 622ATM,
ANSI.X3.263 FDDI TP-PMD, NTSC/PAL Component or Composite Video, AES/EBU, Digital Video, RS-422, Noisy Environments, 250 MHz Category 6
Physical Characteristics (Overall)
Conductor
AWG Stranding Material No. of Pairs
23 Solid BC - Bare Copper 4
Conductor Count: 8
Total Number of Pairs: 4
Conductor Size: 23 AWG
Insulation
Material
FEP - Fluorinated Ethylene Propylene
Bonded-Pair: N/A
Color Chart
Number Color
1White/Blue Stripe & Blue
2White/Orange Stripe & Orange
3White/Green Stripe & Green
4White/Brown Stripe & Brown
Outer Shield Material
Type Material Material Trade Name Coverage [%] Drainwire Material Drainwire AWG Drainwire Construction n x D
Tape Aluminum/Polyester Beldfoil® 100 % TC - Tinned Copper 24 Solid
Outer Jacket Material
Material Material Trade Name Nominal Diameter Ripcord Separator Material
LS PVC - Low Smoke Polyvinyl Chloride Flamarrest® 0.310 in No Polyester Tape
Construction and Dimensions
Cabling
Filler
Patented Central X-Spline
Electrical Characteristics
Conductor DCR
Max. Conductor DCR Max. DCR Unbalance
93.8 Ohm/km 5 %
Capacitance
Max. Capacitance Unbalance Nom.Mutual Capacitance
330 pF/100m 14 pF/ft
Delay
Frequency [MHz] Max. Delay Max. Delay Skew Nominal Velocity of Propagation (VP) [%]
100 MHz 537.6 ns/100m 45 ns/100m 72 %
High Freq
Frequency
[MHz]
Max. Insertion
Loss (Attenuation)
Min.
NEXT
[dB]
Min.
PSNEXT
[dB]
Min.
ACR
[dB]
Min.
PSACR
[dB]
Min. ACRF
(ELFEXT) [dB]
Min. PSACRF
(PSELFEXT) [dB]
Min. RL
(Return
Loss) [dB]
Max./Min. Input
Impedance
(unFitted)
Max./Min.
Fitted
Impedance
Min.
TCL
[dB]
Min.
ELTCTL
[dB]
0.772 MHz 1.8 dB/100m 77.0 dB 77.0 dB 75.2 dB 76.2 dB 73.0 dB 70.0 dB 19.4 dB 100 +/- 15 100 ± 15 Ohm 40.0 dB 37.2 dB
1 MHz 2.0 dB/100m 75.3 dB 75.3 dB 73.3 dB 74.3 dB 70.8 dB 67.8 dB 20.0 dB 100 +/- 15 100 ± 15 Ohm 40.0 dB 35.0 dB
4 MHz 3.7 dB/100m 66.3 dB 66.3 dB 62.6 dB 63.6 dB 58.8 dB 55.8 dB 23.0 dB 100 +/- 15 100 ± 15 Ohm 40.0 dB 23.0 dB
8 MHz 5.2 dB/100m 61.8 dB 61.8 dB 56.6 dB 57.6 dB 52.7 dB 49.7 dB 24.5 dB 100 +/- 15 100 ± 15 Ohm 40.0 dB 16.9 dB
10 MHz 5.8 dB/100m 60.3 dB 60.3 dB 54.5 dB 55.5 dB 50.8 dB 47.8 dB 25.0 dB 100 +/- 15 100 ± 15 Ohm 40.0 dB 15.0 dB
16 MHz 7.4 dB/100m 57.2 dB 57.2 dB 49.9 dB 50.9 dB 46.7 dB 43.7 dB 25.0 dB 100 +/- 15 100 ± 15 Ohm 38.0 dB 10.9 dB
20 MHz 8.3 dB/100m 55.8 dB 55.8 dB 47.5 dB 48.5 dB 44.8 dB 41.8 dB 25.0 dB 100 +/- 15 100 ± 15 Ohm 37.0 dB 9.0 dB
25 MHz 9.3 dB/100m 54.3 dB 54.3 dB 45.1 dB 46.1 dB 42.8 dB 39.8 dB 24.3 dB 100 +/- 15 100 ± 15 Ohm 36.0 dB 7.0 dB
31.25 MHz 10.4 dB/100m 52.9 dB 52.9 dB 42.5 dB 43.5 dB 40.9 dB 37.9 dB 23.6 dB 100 +/- 15 100 ± 15 Ohm 35.1 dB 5.1 dB
62.5 MHz 15.0 dB/100m 48.4 dB 48.4 dB 33.4 dB 34.4 dB 34.9 dB 31.9 dB 21.5 dB 100 +/- 15 100 ± 15 Ohm 32.0 dB
100 MHz 19.3 dB/100m 45.3 dB 45.3 dB 26.0 dB 27.0 dB 30.8 dB 27.8 dB 20.1 dB 100 +/- 15 100 ± 15 Ohm 30.0 dB
155 MHz 24.6 dB/100m 42.4 dB 42.4 dB 17.9 dB 18.9 dB 27.0 dB 24.0 dB 19.5 dB 100 +/- 22 100 ± 15 Ohm 28.1 dB
200 MHz 28.3 dB/100m 40.8 dB 40.8 dB 12.5 dB 13.5 dB 24.8 dB 21.8 dB 18.7 dB 100 +/- 22 100 ± 15 Ohm 27.0 dB
250 MHz 32.1 dB/100m 39.3 dB 39.3 dB 7.2 dB 8.2 dB 22.8 dB 19.8 dB 18.0 dB 100 +/- 32 100 ± 15 Ohm 26.0 dB
300 MHz 35.6 dB/100m 38.1 dB 36.1 dB 2.5 dB 1.5 dB 21.3 dB 18.3 dB 17.5 dB 100 +/- 32 100 ± 15 Ohm 25.2 dB
350 MHz 38.9 dB/100m 37.1 dB 35.1 dB 19.9 dB 16.9 dB 17.0 dB 100 +/- 32 100 ± 15 Ohm 24.6 dB
400 MHz 42.0 dB/100m 36.3 dB 34.3 dB 18.8 dB 15.8 dB 16.6 dB 100 +/- 32 100 ± 15 Ohm 24.0 dB
450 MHz 45.0 dB/100m 35.5 dB 33.5 dB 17.7 dB 14.7 dB 16.2 dB 100 +/- 32 100 ± 15 Ohm 23.5 dB
500 MHz 47.9 dB/100m 34.8 dB 32.8 dB 16.8 dB 13.8 dB 15.9 dB 100 +/- 32 23.0 dB
550 MHz 50.6 dB/100m 34.2 dB 32.2 dB 16.0 dB 13.0 dB 15.6 dB 100 +/- 32 22.6 dB
Voltage
UL Voltage Rating
300 V RMS
Temperature Range
Installation Temp Range: 0°C To +50°C
UL Temp Rating: 75°C
Storage Temp Range: -20°C To +75°C
Operating Temp Range: -20°C To +75°C
Mechanical Characteristics
Bulk Cable Weight: 44 lbs/1000ft
Max Recommended Pulling
Tension: 25 lbs
Min Bend Radius During
Installation: 2.25 in
Min Bend Radius/Minor Axis: 1.0 in
Standards
NEC/(UL) Specification: CMP
CEC/C(UL) Specification: CMP
ISO/IEC Compliance: 11801 ed 2.2 (2011) Class E
CPR Euroclass: Eca
Data Category: Category 6
ANSI Compliance: S-116-732-2013 Category 6, ANSI/NEMA WC-66 Category 6
Telecommunications Standards: ANSI/TIA-568-C.2 Category 6
IEEE Specification: IEEE 802.3bt Type 1, Type 2, Type 3, Type 4
Third Party Performance
Verification: Category 6
Applicable Environmental and Other Programs
EU Directive 2000/53/EC (ELV): Yes
EU Directive 2002/96/EC
(WEEE): Yes
EU Directive 2003/11/EC (BFR): Yes
EU Directive 2003/96/EC (BFR): Yes
EU Directive 2011/65/EU
(ROHS II): Yes
EU Directive 2012/19/EU
(WEEE): Yes
EU Directive 2015/863/EU: Yes
EU Directive Compliance: Yes
EU CE Mark: Yes
EU REACH SVHC Compliance
(yyyy-mm-dd): 2017-07-10
EU RoHS Compliance Date
(yyyy-mm-dd): 2004-01-01
CA Prop 65 (CJ for Wire &
Cable): Yes
MII Order #39 (China RoHS): Yes
Suitability
Suitability - Aerial: No
Suitability - Burial: No
Suitability - Hazardous
Locations: No
Suitability - Indoor: Yes
Suitability - Non-Halogenated: No
Suitability - Oil Resistance: No
Suitability - Outdoor: No
Suitability - Sunlight Resistance: No
Flammability, LS0H, Toxicity Testing
C(UL) Flammability: FT6
UL Flammability: NFPA 262 Plenum (UL 910)
CSA Flammability: FT6
ISO/IEC Flammability: IEC 60332-1-2
UL voltage rating: 300 V RMS
Plenum/Non-Plenum
Plenum (Y/N): Yes
Part Number
Non-Plenum Number: 2412F
Variants
Item # Color UPC Length
2413F 0101000 Black 612825131601 1,000 ft
2413F D151000 Blue 612825131526 1,000 ft
2413F D15A500 Blue 612825131519 500 ft
2413F 0081000 Gray 612825131571 1,000 ft
2413F 0051000 Green 612825131564 1,000 ft
2413F 0031000 Orange 612825131540 1,000 ft
2413F 0021000 Red 612825131533 1,000 ft
2413F 0091000 White 612825131595 1,000 ft
2413F 009A500 White 612825131588 500 ft
2413F 0041000 Yellow 612825131557 1,000 ft
Patent: https://www.belden.com/resources/patents
Product Notes
Notes: Values above 300 MHz are for Engineering Information Only. Shield is Bonded to Jacket Inner Wall for Electrical Stability. Print Includes Descending Footage Markings from
Max. Put-Up Length to 0.
History
Update and Revision: Revision Number: 0.356 Revision Date: 07-11-2019
© 2019 Belden, Inc
All Rights Reserved.
Although Belden makes every reasonable effort to ensure their accuracy at the time of this publication, information and specifications described here in are subject to error or omission and to change without
notice, and the listing of such information and specifications does not ensure product availability.
Belden provides the information and specifications herein on an "ASIS" basis, with no representations or warranties, whether express, statutory or implied. In no event will Belden be liable for any damages
(including consequential, indirect, incidental, special, punitive, or exemplary damages) whatsoever, even if Belden has been advised of the possibility of such damages, whether in an action under contract,
negligence or any other theory, arising out of or in connection with the use, or inability to use, the information or specifications described herein.
All sales of Belden products are subject to Belden's standard terms and conditions of sale.
Belden believes this product to be in compliance with all applicable environmental programs as listed in the data sheet. The information provided is correct to the best of Belden's knowledge, information and belief
at the date of its publication. This information is designed only as a general guide for the safe handling, storage, and any other operation of the product itself or the one that it becomes a part of. The Product
Disclosure is not to be considered a warranty or quality specification. Regulatory information is for guidance purposes only. Product users are responsible for determining the applicability of legislation and
regulations based on their individual usage of the product.