(c) Siemens AG 2018 3WL1 Air Circuit Breakers SENTRON Configuration Manual Edition 04/2018 siemens.com/lowvoltage (c) Siemens AG 2018 (c) Siemens AG 2018 3WL1 Air Circuit Breakers 2 8 14 21 27 36 38 52 54 55 56 56 57 58 Introduction 3WL1 air circuit breakers/ non-automatic air circuit breakers up to 6300 A (AC), IEC General data - Design - Function - Configuration - Technical specifications Configuration aids - Characteristic curves - Dimensional drawings - Circuit diagrams - More information 3WL1 non-automatic air circuit breakers up to 4000 A (DC) General data - Technical specifications Configuration aids - Characteristic curves - Dimensional drawings - Circuit diagrams - More information (c) Siemens AG 2018 All dimensions in mm. For further technical product information: Siemens Industry Online Support: www.siemens.com/lowvoltage/productsupport Entry type: Application example Certificate Characteristic Download FAQ Manual Product note Software archive Technical data Siemens * 04/2018 (c) Siemens AG 2018 3WL1 Air Circuit Breakers Introduction Overview Size I Size III Size II 3WL air circuit breakers 3WL1 air circuit breakers/non-automatic air circuit breakers 3WL1 non-automatic air circuit up to 6300 A (AC), IEC breakers up to 4000 A (DC) Size Rated current In A Number of poles Rated operational voltage Ue V AC V DC Rated ultimate short-circuit breaking capacity at 500 V AC kA Endurance Operating cycles I, II, III I II 630, 800, 1000, 1250, 1600, 2000, 2500, 3200, 4000, 5000, 6300 2000 1000, 2000, 4000 3-pole, 4-pole 4-pole 3-pole, 4-pole ... 690/1000/1150 -- -... 1000 Size I Size II Size II Size III 55/66/85 66/80/100 130 100/150 (3-pole), 20 30/25/20 130 (4-pole) (at 1000 V DC) (at 300/600/1000 V DC) Up to 20000 15000 10000 10000 Mounting position 30 30 H D 30 30 NSE0_00061a NSE0_00062a IP55 IP41 Dimensions 3-/4-pole W 30 30 30 30 NSE0_00061a Degree of protection With cover Without cover (with door sealing frame) 15000 NSE0_00062a IP55 IP41 W mm 320/410 460/590 460/590 704/914 410 460/590 Fixed H mm D mm 434 291 434 291 434 291 434 291 434 291 434 291 Withdrawable H mm D mm 465.5 471 465.5 471 465.5 471 465.5 471 --- 465.5 471 ETU15B1) ETU25B ETU27B ETU45B ETU76B Overload protection Short-time delayed short-circuit protection -- Instantaneous short-circuit protection Neutral conductor protection -- -- Ground-fault protection -- -- Zone Selective Interlocking -- -- -- LCD, 4-line -- -- -- -- LCD, graphic -- -- -- -- Communication -- -- -- Metering function Plus -- -- -- Selectable parameter sets -- -- -- -- Parameters freely programmable -- -- -- -- CubicleBUS -- -- -- Rating Plug NSE0_01111a NSE0_01108a Type NSE0_01106a NSE0_01107a NSE0_01109a NSS0_00535 Electronic Trip Units for 3WL circuit breakers Standard -- Not available Optional 1) ETU15B cannot be used with 3WL circuit breakers, size III. 2 Siemens * 04/2018 3WL air circuit breakers/non-automatic air circuit breakers according to UL 489 up to 5000 A, see Catalog LV 16. (c) Siemens AG 2018 3WL1 Air Circuit Breakers Introduction Breaking capacity Size I II Type 3WL11 3WL12 Breaking capacity N S N S H H III N 3WL13 N S H S H C C H H C 3-pole C C 4-pole Rated short-circuit breaking capacity Rated operational voltage Ue up to 415 V AC Icu Ics Icm kA kA kA 55 55 121 66 66 145 85 85 187 66 66 145 80 80 176 100 100 220 130 130 286 100 100 220 150 150 330 130 130 286 kA kA kA 55 55 121 66 66 145 85 85 187 66 66 145 80 80 176 100 100 220 130 130 286 100 100 220 150 150 330 130 130 286 kA kA kA 42 42 88 50 50 105 66 66 145 50 50 105 75 75 165 85 85 187 100 100 220 85 85 187 150 150 330 130 130 286 ---- ---- 509) 509) 1059) ---- ---- 50 50 105 ---- 50 50 105 704) 704) 1544) 704) 704) 1544) 55 42 29.5 24 66 50 35 29 75 66 46 44 66 55 39 32 80 66 46 44 100 85 651)/702) 501)/652) 100 100 70 65 100 100 80 65 100 100 80 65 100 100 80 65 55 42 -- 66 50 -- 75 66 509) 66 50 -- 80 75 -- 100 85 504) 130 100 -- 100 85 5010) 100 100 704) 100 100 704) Rated operational voltage Ue up to 500 V AC Icu Ics Icm Rated operational voltage Ue up to 690 V AC Icu Ics Icm Rated operational voltage Ue up to 1000 V/1150 V AC kA kA kA Icu Ics Icm Rated short-time withstand current Icw of the circuit breakers3) 0.5 s 1s 2s 3s kA kA kA kA Rated conditional short-circuit current Icc of the non-automatic air circuit breakers Up to 500 V AC Up to 690 V AC Up to 1000 V/1150 V AC kA kA kA Size I Type 3WL11 3WL12 Breaking capacity DC DC 20 20 20 20 35 30 25 20 -20 --- -355)/306)/257)/208) --- DC II DC Rated short-circuit breaking capacity Up to 220 V DC Up to 300 V DC Up to 600 V DC Up to 1000 V DC Icc Icc Icc Icc kA kA kA kA Rated short-time withstand current Icw 0.5 s 1s 2s 3s kA kA kA kA N Circuit breakers with ECO breaking capacity N Abbreviations* (functions) English long text Explanation L Long Time Delay Overload protection S Short Time Delay Short-circuit protection (short-time delayed) S Circuit breakers with standard breaking capacity S H Circuit breakers with high breaking capacity H C Circuit breakers with very high breaking capacity C DC Non-automatic air circuit breakers with DC breaking capacity I Instantaneous Short-circuit protection (instantaneous) These breaking capacities are indicated in the corresponding tables by the symbols shown on orange backgrounds. N Neutral Protection Neutral conductor protection G Ground Fault Ground-fault protection 1) Size II with In max 2500 A. 2) Size II with In max = 3200 A and In max = 4000 A. 3) At a rated voltage of 690 V, the Icw value of the circuit breaker cannot be greater than the Icu or Ics value at 690 V. * Designations according to IEC 60947-2, Annex K. 6) At Ue = 300 V DC 7) At Ue = 600 V DC 4) Rated operational voltage Ue = 1150 V. 8) At Ue = 1000 V DC 5) At Ue = 220 V DC 9) Values also apply to 690 V + 20% version with Z option "A16". 10) Rated operational voltage Ue = 1000 V. Siemens * 04/2018 3 C (c) Siemens AG 2018 3WL1 Air Circuit Breakers Introduction 3WL1 air circuit breakers: 3WL1 air circuit breakers offer highly flexible application and consistent communication capability. With the 3WL1 circuit breakers, just three sizes cover a performance range of 630 A to 6300 A. All models are characterized by the same design, the same operation and the same comprehensive accessories. 6 7 2 3 8 5 4 9 1 25 21 10 19 22 11 23 12 24 18 13 14 20 16 15 $ % & ( ) * + , . / 0 1 2 3 4 Guide frame Main circuit connection front, flange, horizontal, vertical Position signaling switch Grounding connection, leading Shutters COM15 PROFIBUS module or COM16 MODBUS module External CubicleBUS modules Closing coil, auxiliary release Auxiliary conductor plug-in system Auxiliary switch block Door sealing frame Interlocking set for mechanical ON/OFF Transparent panel, function insert EMERGENCY STOP pushbutton, key operated Motorized operating mechanism Siemens * 04/2018 4 5 6 7 8 9 : ; < = Operating cycles counter Breaker Status Sensor (BSS) Protective device with device holder, Electronic Trip Unit (ETU) Remote reset solenoid Breaker Data Adapter (BDA Plus) Four-line display Ground-fault protection module Rating plug Metering function module Air circuit breaker NSE0_01887d 17 (c) Siemens AG 2018 3WL1 Air Circuit Breakers Introduction Communication-capable circuit breakers (with ETU45B or ETU76B Electronic Trip Unit) 20 Ethernet 18 19 PROFIBUS PROFINET 4 6 5 3VA-line 1 14 15 16 17 8 10 11 1 NSE0_01105 12 3 12 Metering function Plus 1 3VA molded case circuit breakers 2 3VL molded case circuit breaker 13 Zone Selective Interlocking module 3 Electronic Trip Unit ETU / LCD ETU 14 Digital output module with relay contacts 4 COM800 breaker data server 15 Digital output module with relay contacts, configurable 5 COM100 breaker data server 16 Analog output module 6 COM20 Release 2 PROFIBUS module including Zone Selective Interlocking 17 Digital input module 7 BDA Plus with Ethernet interface 18 Powerconfig commissioning and service software V2.3 and higher 8 3WL air circuit breaker 19 PLC, e.g. SIMATIC S7 9 COM15 PROFIBUS module 20 E.g. SIMATIC powerrate 21 7KM PAC measuring devices 10 Breaker Status Sensor (BSS) 11 Electronic Trip Unit (ETU) 7 CubicleBUS 9 3VA-line 2 1 13 21 Siemens * 04/2018 5 (c) Siemens AG 2018 3WL1 Air Circuit Breakers Introduction 11 Ethernet MODBUS TCP 6 7 8 10 RS 485 with MODBUS RTU 3VA-line 3VA-line 9 5 3 1 1 2 4 I201_19162 1 1 3VA molded case circuit breakers 7 COM100 breaker data server 2 3WL air circuit breaker 8 7KM PAC4200 measuring device 3 COM16 MODBUS module 9 7KM PAC3100 measuring device 4 3VL molded case circuit breaker 10 7KM PAC3200 measuring device 5 COM21 MODBUS module 11 Powerconfig commissioning and service software V2.3 and higher 6 COM800 breaker data server Characteristics * Coordinated communication concept using the PROFIBUS DP or MODBUS, ranging from 16 A to 6300 A with 3VL molded case circuit breakers and 3WL air circuit breakers * The high level of modularity of circuit breakers and accessories allows easy retrofitting of all communication components * Significant additional benefits for the switchboard due to the possibility of linking up external input and output modules to the circuit breaker-internal CubicleBUS of the 3WL air circuit breaker * Innovative software products for parameterization, operation, monitoring, and diagnostics of circuit breakers, both locally or via PROFIBUS DP, MODBUS or Ethernet/Intranet/Internet * Complete integration of the circuit breakers into the Totally Integrated Power and Totally Integrated Automation solutions 6 Siemens * 04/2018 Communication: * For air circuit breakers with optional communication function (ETU45B or ETU76B Electronic Trip Units), see Catalog LV 10. * For accessories, see Catalog LV 10. * For more information, see also Catalog LV 10, chapters "Measuring Devices and Power Monitoring" and "Software". (c) Siemens AG 2018 3WL1 Air Circuit Breakers 3WL1 Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC), IEC Introduction Benefits * Measured values are the basis for efficient load management, for drawing up power demand profiles and for allocating energy to cost centers * Preventive maintenance reduces the risk of expensive plant downtimes * Metering function with a very wide range of measured values, such as current, voltage, energy, power, etc. * Can be used in 690 V networks Low space requirements The 3WL air circuit breakers require very little space. Size I devices (up to 2000 A) fit into a 400 mm wide switchboard panel. Size III devices (up to 6300 A) are the smallest of their kind and with their construction width of 704 mm fit into an 800 mm wide switchboard panel. Application Modular design Components such as auxiliary releases, motorized operating mechanisms, Electronic Trip Units, current sensors, auxiliary circuit signaling switches, automatic reset devices, interlocks and engagement operating mechanisms can all be exchanged or retrofitted at a later stage, thus allowing the circuit breaker to be adapted to new, changing requirements. * As incoming-feeder, distribution, tie, and outgoing-feeder circuit breakers in electrical installations. * For switching and protecting motors, capacitors, generators, transformers, busbars and cables. When connected to an electronic I&C system, the air circuit breakers offer a wide range of options for monitoring network events. The main contact elements can all be replaced in order to increase the endurance of the circuit breaker. Air circuit breakers belong to the SENTRON product family of protection, switching, measuring and monitoring devices and can be used in applications between 16 A and 6300 A. Retrofittable modules for Electronic Trip Units Modularity is one of the main features of the new 3WL air circuit breakers. Special LCDs, ground-fault modules, rating plugs and communication modules for the Electronic Trip Units are available for fast and easy retrofitting and adaptation to changing requirements. The AC devices are available as circuit breakers and non-automatic air circuit breakers. DC devices are only available as non-automatic air circuit breakers. Standards Communication/metering functions The use of modern communication-capable circuit breakers opens up completely new possibilities in terms of start-up, parameterization, diagnostics, maintenance and operation. This allows many different ways of reducing costs and improving productivity in industrial plants, buildings and infrastructure projects to be achieved: * Fast and reliable parameterization * Timely information and response can prevent plant stoppages * Effective diagnostics management 3WL air circuit breakers comply with: * IEC 60947-2 * IEC 60947-2 Annex F / CISPR 11/22 Class B * Climate-proof according to IEC 60068-2-30. Versions with UL 489 also available, see Catalog LV 16. Conductor cross-sections for AC Size Type Permissible load for withdrawable versions at rear horizontal main circuit connections * Up to 55 C (Cu bare) * Up to 60 C (Cu bare)1) * Up to 70 C (Cu painted black)1) Main conductor minimum cross-sections * Copper bars, bare * Copper bars, painted black I Up to 3WL11 10 A 1000 A 1000 A 1000 II 3WL11 12 3WL11 16 3WL11 20 3WL12 08 3WL12 10 3WL12 12 3WL12 16 3WL12 20 1250 1250 1210 1600 1600 14902) 2000 1930 1780 800 800 800 1000 1000 1000 1250 1250 1250 1600 1600 1600 2000 2000 2000 Unit(s) 1 x mm2 60 x 10 2x 40 x 10 2x 50 x 10 3x 50 x 10 1x 50 x 10 1x 60 x 10 2x 40 x 10 2x 50 x 10 3x 50 x 10 Unit(s) 1 x mm2 60 x 10 2x 40 x 10 2x 50 x 10 3x 50 x 10 1x 50 x 10 1x 60 x 10 2x 40 x 10 2x 50 x 10 3x 50 x 10 Size II Type 3WL12 25 3WL12 32 3WL12 403) 3WL13 40 3WL13 50 3WL13 633) Permissible load for withdrawable versions at rear horizontal main circuit connections * Up to 55 C (Cu bare) * Up to 60 C (Cu bare)1) * Up to 70 C (Cu painted black)1) Main conductor minimum cross-sections * Copper bars, bare * Copper bars, painted black III 3200 3020 2870 39504) 3810 3600 4000 4000 4000 5000 5000 5000 5920 5810 5500 Unit(s) 2 x mm2 100 x 10 3x 100 x 10 4x 120 x 10 4x 100 x 10 6x 100 x 10 6x 120 x 10 Unit(s) 2 x mm2 100 x 10 3x 100 x 10 4x 100 x 105) 4x 100 x 10 6x 100 x 10 6x 120 x 10 A 2500 A 2500 A 2280 1) ETU76B with graphics display can be used up to max. 55 C. 2) At breaking capacity H: 1600 A up to 70 C 3) With rear vertical connections 4) Size II, 3-pole, in fixed-mounted version 5) Minimum main conductor cross-sections for 4-pole withdrawable circuit breakers: 4 x 120 mm x 10 mm Siemens * 04/2018 7 (c) Siemens AG 2018 3WL1 Air Circuit Breakers 3WL1 Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC), IEC General data Design Circuit breaker rated current n max (A) Breaking capacity cu at 500 V AC (kA) or cc at 300 V DC (kA) Size III 6300 5000 H 100 4000 C 150 (3p) 130 (4p) Dimensions Fixed-mounted, 3-/4-pole Withdrawable 3-/4-pole 704 / 914 704 / 914 Width 434 / 434 460 / 460 Height 291 / 291 385 / 385 Depth 460 / 590 460 / 590 Width 434 / 434 460 / 460 Height 291 / 291 385 / 385 Depth 320 / 410 320 / 410 Width 434 / 434 460 / 460 Height 291 / 291 385 / 385 Depth 4000 3200 Size II 2500 2000 1600 DC N S H 30 66 80 100 1250 1000 800 2000 Size I 1600 1250 1000 DC N S H 20 55 66 85 800 630 The dimension for the depth of the circuit breaker is from the circuit breaker rear to the inner surface of the closed switchgear door. Overview of 3WL circuit breakers/non-automatic air circuit breakers Versions * * * * Rated currents: 630 A to 6300 A 3 sizes for different rated current ranges (see diagram above) 3 and 4-pole versions Rated operational voltage up to 690 V AC and 1000 V DC. Special versions up to 1000 V AC and 1150 V AC available * 4 different breaking capacities from 55 kA to 150 kA for AC applications and one breaking capacity for DC applications The 3WL circuit breakers are supplied complete with operating mechanism (manual operating mechanism with mechanical closing), Electronic Trip Unit and auxiliary switches (2 NO contacts + 2 NC contacts in the standard version), and can be equipped with auxiliary releases. Installation methods Fixed-mounted or withdrawable versions Ambient temperatures 3WL circuit breakers are suitable for use in any climate in accordance with IEC 60068-2-30. They are intended for use in enclosed rooms in which no severe operating conditions (such as dust, caustic vapors, hazardous gases) prevail. When installed in dusty and damp areas, suitable enclosures must be provided. NSE0_00887q Coordinated dimensions The dimensions of 3WL circuit breakers only differ in terms of the width of the device which depends on the number of poles and the size. Due to the nature of the design, the dimensions of devices with a withdrawable version are determined by the dimensions of the guide frames, which are slightly larger. Non-automatic air circuit breakers One special version of circuit breaker is utilized as a non-automatic air circuit breaker. The non-automatic air circuit breakers are designed without an electronic trip system and do not perform any protection functions for the plant. One potential application is the use as a tie-breaker in systems with parallel infeeds. The versions and features can be selected according to those of the circuit breakers. Operating mechanisms The circuit breakers are available with various optional operating mechanisms: * Manual operating mechanism with mechanical closing (standard design) * Manual operating mechanism with mechanical and electrical closing * Motorized operating mechanism with mechanical and electrical closing The operating mechanisms with electrical closing are suitable for synchronization tasks. 8 Siemens * 04/2018 (c) Siemens AG 2018 3WL1 Air Circuit Breakers 3WL1 Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC), IEC General data Safety and reliability To protect the circuit breakers and system against unauthorized switching and to protect the maintenance and operator personnel, the system contains many locking devices. Others can be retrofitted. Front connection with single hole or double hole Horizontal connection NSE0_00979a NSE0_00969b NSE0_00967b NSE0_00968b Fixed-mounted circuit breakers Vertical connection Horizontal connection Front connection with single hole or double hole Vertical connection NSE0_00973b NSE0_00972b NSE0_00971b NSE0_00967b NSE0_00970b Withdrawable circuit breaker, withdrawable guide frame Flange connection Main circuit connections - connection types Main circuit connections All circuit breakers are equipped with horizontal main circuit connections on the rear for up to 5000 A as standard (horizontal connection to busbars). Exception: Circuit breakers of size II with max. rated current 4000 A. Circuit breakers with a max. rated current of 6300 A and circuit breakers of size II with a max. rated current of 4000 A are equipped with vertical main circuit connections (for upright busbars). Connection using screw connection method (SIGUT) (standard) NSE0_00976b NSE0_00975b The following options are available, with all combinations of top and bottom connections possible: * Accessible from the front, single hole (for vertically installed busbars) * Accessible from the front, double hole (holes according to DIN 43673) (for vertically installed busbars) * At the rear, vertical (for vertically installed busbars) * Connecting flange (for direct connection to guide frames up to 4000 A) Screwless connection method (tension spring) (optional) Connection options for auxiliary circuit connections Auxiliary circuit connections The type of connection for the auxiliary switches depends on the type of installation: * Withdrawable version: The internal auxiliary switches are connected to the male connector on the switch side. When fully inserted, the connector makes a connection with the sliding contact module (see the graphic "Guide frame" under "Design") in the guide frame. Various adapters can then be used to complete the wiring (see the graphic "Connection options for auxiliary circuit connections"). * Fixed-mounted version: In this case the auxiliary supply connectors are engaged directly onto the circuit breaker. The connectors are equipped with coding pins that prevent them being mistakenly interchanged Operator panel The operator panel is designed to protrude from a cutout in the door providing access to all control elements and displays with the control cabinet door closed. The operator panels for all circuit breakers (fixed-mounted/ withdrawable versions, 3-/4-pole) are identical. The operator panel ensures degree of protection IP41. Other safety features include: * Infeed from above or below, as required * Locking of the guide frame with the circuit breaker removed, as standard * Locking of the withdrawable circuit breaker against movement, as standard * High degree of protection with cover IP55 * Mechanical reclosing lockout after overload or short-circuit tripping as standard * The circuit breaker is always equipped with the required number of auxiliary supply connectors Standard version 3WL circuit breakers are equipped with the following features as standard: * Mechanical ON and OFF button * Manual operating mechanism with mechanical closing * Switching position indication * Ready-to-close indicator * Store status indicator * Auxiliary switch 2 NO + 2 NC * Rear horizontal main circuit connections for fixed-mounted and withdrawable versions up to 5000 A, and rear vertical main circuit connections for 6300 A applications and size II with 4000 A * For 4-pole circuit breakers, the fourth pole (N) is installed on the left and is 100% loadable with the rated current * Contact erosion indicator for the main contacts * Auxiliary circuit plug-in system with SIGUT screw terminals Delivery inclusive of all auxiliary supply connectors as per internal equipment including coding device for the prevention of incorrect installation of auxiliary supply connectors for fixed-mounted circuit breakers * Mechanical "tripped" indicator for electronic trip system * Mechanical reclosing lockout after tripping operation * Operator panel cannot be taken off with the circuit breaker in the ON position Additional features of the withdrawable version: * Main contacts: Laminated receptacles in the guide frame, blade contacts on the withdrawable circuit breaker * Position indicator in the operator panel of the withdrawable circuit breaker * Captive manual crank handle for moving the withdrawable circuit breaker * Guide frame with guide rails for easy moving of the withdrawable circuit breaker * The withdrawable circuit breaker can be locked to prevent it being pushed out of position * The withdrawable circuit breaker cannot be moved when it is in the ON position * Coding of the rated current between the guide frame and the withdrawable circuit breaker Standards 3WL circuit breakers comply with: * IEC 60947-2 * Climate-proof according to IEC 60068-2-30. Versions acc. to UL 489 also available, see Catalog LV 16. For further standards, see www.siemens.com/lowvoltage/product-support or www.siemens.com/lowvoltage/configurators. Siemens * 04/2018 9 (c) Siemens AG 2018 3WL1 Air Circuit Breakers 3WL1 Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC), IEC General data Withdrawable short-circuit, grounding, and bridging units Undervoltage releases Portable positively-driven grounding and short-circuit devices are used for the disconnected system sections to verify isolation from the supply at the workplace. The undervoltage release causes the circuit breaker to be opened if the operational voltage falls below a certain value or is not applied. The circuit breaker cannot be closed manually or by means of an electrical ON command if the undervoltage release is not connected to the operational voltage. The undervoltage release has no delay as standard. A delay can be set by the customer in the range between td < 80 ms and td < 200 ms. Withdrawable grounding units allow simple and comfortable grounding. They are simply inserted into the guide frames in place of the corresponding withdrawable circuit breakers. This ensures that these devices are always first connected with the grounding electrode and then with the components to be grounded. The grounding contacts are fitted to the side of the breaker enclosure and establish the connection when inserted into the guide frame. Short-time current of the grounding contact kA 15 (500 ms) Rated operational voltage V 1000 (690 for size I) DIN VDE 0683 Standards All withdrawable contacts are short-circuited and grounded on delivery. Electrically skilled persons can easily convert them to withdrawable bridging units by following the enclosed instructions. In addition, the withdrawable unit can be adapted to various rated currents of one size. Withdrawable short-circuit and grounding unit The withdrawable short-circuit and grounding unit consists of a breaker enclosure with blade contacts which are connected with the short-circuiting link. Depending on the version, the short-circuiting links are arranged at the top or bottom. The grounding and short-circuit connections are established when the device is inserted. It must be ensured that the side to be short-circuited and grounded is not live. For this reason it is recommended that the withdrawable unit is only cranked in when the door is closed. Withdrawable bridging unit In addition, an undervoltage release with a delay in the range from 0.2 to 3.2 s is available. Closing coil The closing coil is used to close the circuit breaker electrically by means of a local electrical "ON" command or by remote means. Motorized operating mechanism The operating mechanism is used to charge the spring energy store automatically. The operating mechanism is activated if the spring energy store has been discharged and the control voltage is available. It is switched off automatically after charging. This does not affect manual operation of the spring energy store. Indicators, signals and control elements Motor cutout switch Selector switch for switching off the motorized operating mechanism (automatic charging). Operating cycles counter The motorized operating mechanism can be supplied with a 5-digit operating cycles counter. The display is incremented by "1" as soon as the spring energy store is fully charged. Resetting of the manual tripped signal When the circuit breaker has tripped, this is indicated by the protruding red mechanical tripped indicator on the ETU. When the mechanical tripped indicator is activated, the tripping solenoid and tripped signal are reset. If this manual display is to be reset remotely, the reset button can be equipped with a reset solenoid. The withdrawable bridging unit consists of a breaker enclosure in which all disconnection components and the operating mechanism have been replaced with simple connections between the upper and lower contacts. This option allows the circuit breaker to be reset both manually and electrically. Auxiliary releases When the ETU is tripped, reclosing of the circuit breaker is prevented until the trip unit is either electrically or manually reset. If the "Automatic resetting of reclosing lockout" option is used, the pre-tensioned circuit breaker is ready to close immediately after tripping. Resetting the manual "tripped" indicator is not included in this option. Up to two auxiliary releases can be installed at the same time. The following are available for selection: 1 shunt release or 1 undervoltage release or 2 shunt releases or 1 shunt release + 1 undervoltage release Automatic resetting of reclosing lockout Tripped signaling switch One signaling contact is used for each auxiliary release to determine the positions of the auxiliary releases. If the circuit breaker has tripped due to an overload, shortcircuit, ground fault or extended protection function, the tripped signaling switch can indicate this. This signaling switch is available as an option. If the circuit breaker is used for communication, this option is supplied as standard. Shunt releases Ready-to-close signaling switch When the operational voltage is connected to the shunt release, the circuit breaker is opened immediately. The shunt release is available in the versions 5% OP for overexcitation and 100% OP for permanent excitation. This means that it is also possible to block the circuit breaker against being jogged into closing. The 3WL circuit breakers are equipped with an optical ready-toclose indicator as standard. In addition, the ready-to-close status can be transmitted by means of a signaling switch as an option. If the switch is used for communication, this signaling switch is supplied as standard. Signaling switches for auxiliary releases An energy storage device for shunt releases allows the circuit breaker to be opened even if the control voltage is no longer available. 10 Siemens * 04/2018 (c) Siemens AG 2018 3WL1 Air Circuit Breakers 3WL1 Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC), IEC General data Circuit breakers 28 1 2 3 4 1 2 27 26 3 4 25 5 24 6 23 7 22 21 8 20 9 10 19 11 18 17 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 12 13 16 14 NSE0_00965b 15 23 24 25 26 27 28 Arc chute Carrying handle Labeling plates Motor cutout switch (option) or "Electrical ON" (option) Type plate for circuit breaker Spring charge indicator "Mechanical ON" button Rated current indication Positioning pictogram Operating cycles counter (option) Hand-operated lever Crank handle Withdrawable unit drive shaft Equipment plate Grounding connection Position indicator Table for ground-fault protection Safety lock for crank handle (option) Mechanical unlocking of crank handle (option) Electronic trip unit Rating plug "Mechanical OFF" button or "EMERGENCY-STOP" mushroom pushbutton (option) Ready-to-close indicator Contact position indicator "Tripped" indicator (reset button) "Secure OFF" locking device (option) Operator panel Male connector for auxiliary connections Guide frames 1 2 18 3 17 4 1 2 3 4 5 6 7 8 9 10 11 5 6 16 7 15 14 8 13 12 13 14 15 16 17 18 Arc chute cover (option) Blow-out openings Opening for crane hook Shutter (option) Locking device (shutter) (option) Type plate for guide frame Isolating contacts Ground terminal O14 mm Locking device for racking rail Locking device against movement when cabinet door is open (option) Door interlock for guide frame (option) Racking rail Factory-set rated current coding Sliding contact for breaker grounding (option) Equipment-dependent coding (option) Shutter actuator (option) Position indicator switch (option) Sliding contact module for auxiliary conductors (number depends on equipment) 12 9 11 10 NSE0_00966b Siemens * 04/2018 11 (c) Siemens AG 2018 3WL1 Air Circuit Breakers 3WL1 Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC), IEC General data Locking devices Sealing devices Locking device in OFF position Sealing cap for "Electrical ON" button This function prevents closing of the circuit breaker and complies with the requirements for main control switches according to EN 60204 (VDE 0113) - supply disconnecting device. This lockout only affects this circuit breaker. The "Electrical ON" button is equipped with a sealing cap as standard. If the circuit breaker is replaced, closing is no longer prevented unless the new circuit breaker is also protected against unauthorized closing. The locking set contains covering caps which can be sealed. To activate the locking device, the circuit breaker must be opened. The locking device is disabled when the circuit breaker is closed. The lock is only activated when the key is removed. The safety key can be removed only in the "OFF" position. Sealing cap for "Mechanical ON" and "OFF" button Sealing device for Electronic Trip Units The transparent cover can be sealed. The parameter setting sections are covered to prevent unauthorized access. Openings allow access to the query and test button. Locking mechanisms Locking device for "Electrical ON" (see graphic "Circuit breakers") Locking mechanism against movement for withdrawable circuit breakers when the control cabinet door is open This prevents unauthorized electrical closing from the operator panel. Mechanical closing and remote closing remain possible. The lock is only activated when the key is removed. The crank handle is blocked when the control cabinet door is open and cannot be removed. The withdrawable circuit breaker cannot be moved. The lock only affects the inserted crank handle. Locking device for "Mechanical ON" (see graphic "Circuit breakers") This prevents unauthorized mechanical closing. The mechanical ON button can only be activated if the key is inserted (key operation). Closing with the "Electrical ON" button and remote closing remain possible. The lock is only activated when the key is removed. "Safe OFF" circuit breaker-independent locking device against unauthorized closing This special breaker-independent function for withdrawable circuit breakers prevents closing and fulfills the requirements for main control switches to EN 60204 (VDE 0113) - supply disconnecting device. Unauthorized closing remains impossible even after the circuit breaker has been replaced. To activate the lock, the circuit breaker must be opened. The locking device is disabled when the circuit breaker is closed. The lock is only activated when the key is removed. The safety key can be removed only in the "OFF" position. Locking device for crank handle Prevents removal of the crank. The circuit breaker is protected against movement. The lock is only activated when the key is removed. Locking device for "Mechanical OFF" Prevents unauthorized mechanical opening from the operator panel. The "Mechanical OFF button" can only be activated if the key is inserted (key operation). Remote opening remains possible. The lock is only activated when the key is removed. Locking device for hand-operated lever The hand-operated lever can be locked with a padlock. The spring energy store cannot be charged manually. Locking device against resetting the "tripped" indicator A lockable cover prevents manual resetting of the "tripped" indicator after tripping due to overcurrent. This locking device is supplied together with the transparent cover option for Electronic Trip Units. 12 Siemens * 04/2018 Locking of the control cabinet door The control cabinet door cannot be opened if * the fixed-mounted circuit breaker is closed (the blocking signal is transmitted via the Bowden cable) or * the withdrawable circuit breaker is in the connected position Blocking mechanism using "Mechanical ON" and "OFF" button The "Mechanical ON" and "OFF" buttons are covered with a cap which only allows actuation with a tool. These cover caps are part of the interlocking set. Optional equipment for guide frames Shutters The sealing strips of the shutter seal the laminated contacts of the guide frame when the withdrawable circuit breaker is removed and therefore implement touch protection. The sealing strips can be manually opened using the strip levers. The position of the sealing strips can be locked in various positions using padlocks for securing against tampering. (c) Siemens AG 2018 3WL1 Air Circuit Breakers 3WL1 Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC), IEC General data Rated current coding unit between circuit breaker and guide frame Equipment-dependent coding Withdrawable circuit breakers and guide frames are equipped with a rated current coding unit as standard. This ensures that only circuit breakers whose blade contacts are suited to the laminated contacts of the guide frame can be inserted into a guide frame (see diagram below). Withdrawable circuit breakers and guide frames can be retrofitted with an equipment-dependent coding unit. This allows different designs of circuit breakers and guide frames to be uniquely assigned. If the circuit breaker and guide frame have been assigned different codes, the circuit breaker cannot be inserted. NSE0_01031b 36 different coding options can be selected. Position signaling switches for guide frame The guide frame can be equipped with position signaling switches. These can be used to determine the position of the circuit breaker in the guide frame. 1 Two versions are available: * Option 1 Connected position 1 CO contact, Test position 1 CO contact, Disconnected position 1 CO contact * Option 2 Connected position 3 CO contacts, Test position 2 CO contacts, Disconnected position 1 CO contact 1 Guide frame, interior left-hand side; interior right-hand side similar 2 Coding pin on racking rail in guide frame 3 3 Racking rail NSE0_01032b 2 4 4 Withdrawable circuit breaker right-hand side; left-hand side similar 5 5 Coding pin on guide frame Rated current coding unit between circuit breaker and guide frame Positions of the withdrawable circuit breaker in the guide frame Representation Maintenance position 2 Position indicator CONNECT Main circuit Auxiliary circuit Cabinet door Shutter Disconnected Disconnected Open Closed Disconnected Disconnected Closed Closed Disconnected Connected Closed Closed Connected Connected Closed Open 1 TEST 4 DISCON NSE0_01033a NSE0_01037 1 Auxiliary circuit 2 Main circuit 4 Shutter Disconnected position CONNECT 3 TEST NSE0_01034a DISCON NSE0_01038 3 Control cabinet door Test position CONNECT TEST DISCON NSE0_01035a NSE0_01039 Connected position CONNECT TEST NSE0_01036a DISCON NSE0_01040 Phase barriers The plant engineering company can manufacture phase barriers made of insulating material for the arcing fault barriers. The rear panel of the fixed-mounted circuit breakers or guide frames are equipped with guide grooves. Door sealing frame and cover 3WL circuit breakers have degree of protection IP20 as standard. However, if the switchboard is to be equipped with a higher degree of protection, a door sealing frame with IP41 and a cover with IP55 are available. Arc chute cover The arc chute cover is available as optional equipment for the guide frame. It protects switchboard components which are located directly above the circuit breaker. Siemens * 04/2018 13 (c) Siemens AG 2018 3WL1 Air Circuit Breakers 3WL1 Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC), IEC General data NSE0_00880b NSE0_00881b NSE0_00882b Function R R s d s d J J s d J ETU15B g N S E 0 _ 0 0 9 5 2 b N S E 0 _ 0 0 9 5 1 b NSE0_00950c ETU25B ETU27B Functions of the Electronic Trip Units Basic protection functions Overload protection L Short-time delayed short-circuit protection S -- Instantaneous short-circuit protection I Neutral conductor protection N -- -- Ground-fault protection G -- -- Neutral conductor protection (can be switched on/off) -- -- N-conductor protection adjustable -- -- -- Short-time delay short-circuit protection (can be switched on/off) -- -- -- Additional functions Instantaneous short-circuit protection (can be switched on/off) -- -- -- Thermal memory can be switched on/off -- -- -- Load monitoring -- -- -- Short-time delay short-circuit protection switchable to I2t -- -- -- Instantaneous short-circuit protection adjustable -- -- Overload protection switchable to I4t -- -- -- Overload protection can be switched on/off -- -- -- Selectable parameter sets -- -- -- Parameterization through rotary coding switches (10 steps) Parameterization through communication (absolute values) -- -- -- Parameterization through user interface of ETU (absolute values) -- -- -- Parameterization and display Parameterization of the extended protection functions -- -- -- LCD alphanumerical -- -- -- LCD graphical -- -- -- -- -- -- CubicleBUS -- -- -- Communication through PROFIBUS DP -- -- -- Communication through MODBUS -- -- -- -- -- -- Metering function Metering function Plus Communication Communication via Ethernet Standard -- Not available Optional Note Detailed information about the functions of the Electronic Trip Units is given in the following. 14 Siemens * 04/2018 s d g (c) Siemens AG 2018 3WL1 Air Circuit Breakers 3WL1 Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC), IEC General data ETU76B Rating Plug NSE0_00886c NSE0_00883b 12 = IR IR tR tR Ig tg Isd t sd Ii NSE0 00953a Ig tg Isd t sd Ii NSE0 00953a ETU45B ETU76B -- -- -- -- -- -- -- Siemens * 04/2018 15 (c) Siemens AG 2018 3WL1 Air Circuit Breakers 3WL1 Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC), IEC General data Electronic Trip Units (ETU) The Electronic Trip Unit is controlled by a microprocessor and operates independently of an auxiliary voltage. It enables systems to be adapted to the different protection requirements of distribution systems, motors, transformers and generators. Tripped indicator/ Reset button LCD alphanumeric with 15 inclination and rotatable through 180 Communication capability The international standardized PROFIBUS DP or MODBUS can be used to transmit data such as current values, switching states, causes of tripping etc. to central computers. Data acquisition and energy management are possible in conjunction with the Plus metering function. An internal circuit breaker data bus allows switchboard panel communication between the circuit breaker and typical secondary devices in the circuit breaker section: * Control of analog displays * Facility to test the communication build-up with circuit breakers * Display of tripping state and tripping reasons * Input module for reading in further switchboard panel signals and for transmission of these signals to the PROFIBUS DP or MODBUS * Various output modules for displaying measured values Slide switch for selectable overload characteristic Rating plug Ground-fault protection module (retrofittable) Example of configuration for ETU45B This means that it is not only possible to monitor the device remotely, but also to transmit current values from the entire system and perform switching operations remotely. I2t and I4t characteristic curves for overload protection The best protection for the whole switchboard is achieved by setting the tripping characteristic curve to an optimum value. In order to achieve optimal discrimination for upstream fuses or medium-voltage protection systems, the inclination of the characteristic curve can be selected for the overload range. The overload protection L (long time protection) for the ETU45B and ETU76B Electronic Trip Units allows the curve to be switched between the I2t and I4t characteristics. The I4t characteristic improves discrimination for downstream circuit breakers and fuses. Electronic Trip Units ETU High emphasis has also been placed on modularity during the development of the Electronic Trip Units. These are some of the modules which can be easily retrofitted at any time: * Ground-fault protection module * Communication * Metering function * Display * Rating plug This allows quick adaptation to new local power supply conditions. In addition, innovative functions have been included in the ETUs. Rating plug The rating plug is an exchangeable module which allows the user to reduce the rated device current so as to adapt it optimally to the plant; e.g. if a new plant section is put into operation. The rating plug must be selected to correspond to the rated current of the plant. 16 Siemens * 04/2018 Metering function Plus Selectable parameters In the case of quick changes of power supply conditions, e.g. for switchover from transformer to generator operation or if a section of the supply is disconnected when the shift changes, 3WL circuit breakers allow the relevant protection parameters to be quickly adapted to the new conditions. The ETU76B contains two independent tripping characteristics (parameter sets). The switchover is completed within 200 ms and is performed with the help of an external signal. (c) Siemens AG 2018 3WL1 Air Circuit Breakers 3WL1 Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC), IEC General data ETU15B Electronic Trip Unit Application: Option: safety lock prevents pressing of reset button after overcurrent release Mechanical RESET for reclosing lockout and mechanical tripped indicator Indicator: overcurrent release activated Indicator: fault in overcurrent release Indicator: overload alarm Rotary switch for setting value, overload release Simple building and system protection without time-selective coordination up to 4000 A. Not to be used for size III. Properties: * Adjustable overload protection with I2t characteristic with non-adjustable delay time tR = 10 seconds at 6 x IR * Instantaneous short-circuit protection adjustable in the range 2 ... 8 x In * Overload display * Protection function is set by means of the rotary coding switch For technical details, see the table "Function overview of the electronic trip system" under "Technical specifications". Rotary switch for setting value, instantaneous short-circuit release NSE0_00954b Sealing ring Test socket ETU25B Electronic Trip Unit Application: Option: safety lock prevents pressing of reset button after overcurrent release Mechanical RESET for reclosing lockout and mechanical tripped indicator Indicator: overcurrent release activated Indicator: overload alarm ETU25B Indicator: fault in overcurrent release Rating Plug Rated current module Rotary switch for setting value, overload release Indicator: cause of release Rotary switch for setting value, instantaneous short-circuit release Short-circuit protection fixed setting Rotary switch for delay, short-circuit release NSE0_00955b Query pushbutton Test pushbutton Sealing ring Clear pushbutton Test socket Classical building, motor and system protection with time-selective coordination for up to 6300 A Properties: * Adjustable overload protection with I2t-characteristic delay time tR = 10 seconds at 6 x IR * Short-time delayable short-circuit protection adjustable in the range 1.25 ... 12 x In and * Instantaneous short-circuit protection non-adjustable at 20 x In, max. 50 kA * Can be adapted at any time to the required plant currents through exchangable rating plug, thus ensuring overload protection in the range from 100 A to 6300 A * Overload display * Indicates the cause of tripping by means of an LED * Test facility for the trip unit * Protection function is set by means of the rotary coding switch For technical details, see the table "Function overview of the electronic trip system" under "Technical specifications". Siemens * 04/2018 17 (c) Siemens AG 2018 3WL1 Air Circuit Breakers 3WL1 Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC), IEC General data ETU27B Electronic Trip Unit Application: Option: safety lock prevents pressing of reset button after overcurrent release Mechanical RESET for reclosing lockout and mechanical tripped indicator Classical building, motor and system protection with time-selective coordination for up to 6300 A NSE0_00956c Properties: Indicator: overcurrent release activated ETU27B Indicator: overload alarm N-conductor protection on/off OFF ON Rating Plug Indicator: fault in overcurrent release Rated current module N Rotary switch for setting value, overload release Indicator: cause of release Rotary switch for setting value, instantaneous short-circuit release The same as ETU25B but also * Connectable neutral conductor protection * Permanently integrated ground-fault protection. Calculation of the ground-fault current through vectorial summation current formation For technical details, see the table "Function overview of the electronic trip system" under "Technical specifications". Rotary switch for delay, short-circuit release Short-circuit protection fixed setting Rotary switch for setting value, ground-fault protection Sealing ring OFF Rotary switch for delay, ground-fault protection Query pushbutton Test pushbutton Clear pushbutton Test socket ETU45B Electronic Trip Unit Mechanical RESET for reclosing lockout and mechanical tripped indicator Scroll down Option: safety lock prevents pressing of reset button after overcurrent release Option: alphanumeric display Indicators: Overcurrent release activated Overload alarm Scroll up Indicator: fault in overcurrent release COMMUNICATION EXPANDED ETU45B OFF ON Rated current module Rating Plug = Rotary switch for setting value, overload release 1 1 1 1 1 Rotary switch for setting value, short-circuit protection Selector for ground-fault protection Rotary switch for setting value, ground-fault protection Rotary switch for setting value, ground-fault alarm Rotary switch for delay, overload release 12 Rotary switch for setting value, instantaneous short-circuit release Thermal memory on/off N-conductor protection on/off Setting value N-conductor overload Transfer of overload characteristic 2 t / 4t Rotary switch for delay, short-circuit release Indicator: cause of release Sealing ring Option: ground-fault module SI g Indicator: ground-fault alarm Indicator: ground-fault tripped Rotary switch for delay, ground-fault protection tg / 2 t g Clear pushbutton Test socket Test pushbutton Query pushbutton NSE0_00957c Application: Low-cost highly versatile device for intelligent buildings and all types of industrial applications - "CubicleBUS integrated" Properties: The same as ETU25B but also * Adjustable time-lag class for overload protection * Selectable characteristic for overload and short-time delayed short-circuit range (current discrimination) for more accurate discrimination adaptation to upstream fuses and protective devices * Thermal memory as restart protection for tripped motor outgoing units * Connectable and adjustable neutral conductor protection * Modular ground-fault protection module with alarm and tripping functions which can be adjusted separately * Communication interface, Plus metering function, optional connection of external modules or for retrofitting * Storage of events and causes of tripping for specific fault analysis * Extended protection functions possible with metering function * Optional high-contrast display with viewing angle adjustment option * The protection functions can be set by means of a rotary coding switch or slide switch For technical details, see the table "Function overview of the electronic trip system" under "Technical specifications". 18 Siemens * 04/2018 (c) Siemens AG 2018 3WL1 Air Circuit Breakers 3WL1 Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC), IEC General data ETU76B Electronic Trip Unit Application: Mechanical RESET for reclosing lockout and mechanical tripped indicator Option: safety lock prevents pressing of reset button after overcurrent release ETU76B The multi-talent with graphical display for system analysis - "CubicleBUS integrated" Properties: Indicators: Overcurrent release activated Overload alarm COMMUNICATION EXPANDED Graphical display Indicator: fault in overcurrent release Indicator: cause of release Rating Plug Control keys for setting the release parameters Rated current module Indicators: Ground-fault alarm Ground-fault tripped Option: ground-fault module Fields for noting setting values Fields for noting setting values Test pushbutton Clear pushbutton Query pushbutton Test socket The same as ETU45B but also including * Two protection parameter sets which can be stored separately in the trip unit (switchover is performed by means of external signal) * With overload protection which can be deactivated for use in modern drive engineering applications * Adjustable delay of delayed short-circuit protection up to 4000 ms * Neutral conductor protection adjustable up to IN = 200% In * Setting of protection functions by means of Breaker Data Adapter (BDA Plus) or via communications interface * Graphical display of all parameters and events/curve trends * Graphics display with high contrast, backlit display, and sleep mode For technical details, see the table "Function overview of the electronic trip system" under "Technical specifications". NSE0_00960b Ground-fault protection Selector for ground-fault detection Indicators: Ground-fault tripped Rotary switch for setting value, ground-fault protection Rotary switch for setting value ground-fault alarm Ground-fault alarm Rotary switch for setting value, groundfault protection delay tg/ 2 tg NSE0_00962 GFM AT 45B ground-fault module Field for noting transfer ground-fault detection Fields for noting setting values Indicators: Ground-fault releases "G" sense fault currents that flow to ground and that can cause a fire in the plant. Multiple circuit breakers connected in series can have their delay times adjusted so as to provide graduated discrimination. When setting the parameters for the Electronic Trip Unit it is possible to choose between "alarm" and "trip" in the event that the set current value is exceeded. The reason for tripping is indicated by means of an LED when the query button is activated. The ETU45B and ETU76B Electronic Trip Unit versions can be retrofitted with a ground-fault protection module. This groundfault protection function is integrated in ETU27B Electronic Trip Units. Ground-fault alarm Ground-fault tripped NSE0_00964a Fields for noting setting values GFM AT 55B-76B ground-fault module Siemens * 04/2018 19 (c) Siemens AG 2018 3WL1 Air Circuit Breakers 3WL1 Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC), IEC General data Measurement method Setting Vectorial summation current formation (measurement method 1) How the module is set depends on the measurement method used (see above): The three phase currents and the N-conductor current are measured directly. Measurement method 1: in position . The Electronic Trip Unit determines the ground-fault current by means of vectorial summation current formation for the three phase currents and the N-conductor current. Measurement method 2: in position Direct measurement of the ground-fault current (measurement method 2) Ground-fault protection with I 2t characteristic curve A standard current transformer with the following data is used for measurement of the ground-fault current: 1200 A/1 A, Class 1 (the internal load of the 3WL circuit breaker is 0.11 ). The current transformer can be installed directly in the grounded neutral point of a transformer. With the exception of the ETU27B Electronic Trip Unit, all versions of the ground-fault modules are supplied with an I2t characteristic curve which can be activated. T5 L1 L2 L3 N PE NSE0_00946a 3-pole circuit breakers, current transformers in the N-conductor L1 L2 L3 N T6 PE T6: 1200 A/1 A NSE0_00947 3-pole circuit breakers, current transformers in the grounded neutral point of the transformer L1 L2 L3 N T6 PE T6: 1200 A/1 A NSE0_00948 4-pole circuit breakers, current transformers in the grounded neutral point of the transformer 20 Siemens * 04/2018 . This setting can be implemented for the Electronic Trip Unit version ETU76B with Menu/Comm. Selection criteria for 3WL circuit breakers Basic criteria for selecting circuit breakers are: * Max. short-circuit current at place of installation of circuit breaker Ik max . This value determines the short-circuit breaking capacity or short-circuit current carrying capacity of the circuit breaker. * It is compared with the value Icu, Ics, Icw of the circuit breaker and essentially determines the size of the circuit breaker. See Figure "Overview of 3WL circuit breakers/non-automatic air circuit breakers". * Rated current In that is to flow through the branch circuit. This value must not be higher than the maximum rated current for the circuit breaker. The rated current for the 3WL circuit breaker is set with the rating plug. See Figure "Overview of 3WL circuit breakers/ non-automatic air circuit breakers" under "Design". * Ambient temperature for the circuit breaker. This is usually the control cabinet's internal temperature. * Design of the circuit breaker * Minimum short-circuit current which flows through the switching device. The trip unit must still detect this value as a short-circuit and must respond by tripping. Protection functions of the circuit breaker. These are defined by selection of the corresponding Electronic Trip Unit; see table "Functions of the Electronic Trip Units" under "Functions". (c) Siemens AG 2018 3WL1 Air Circuit Breakers 3WL1 Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC), IEC General data 3WL circuit breakers for DC applications This version of the 3WL non-automatic air circuit breaker is suitable for direct current applications. The external protective device DIGmat S100 provides adjustable overload and shortcircuit protection for the 3WL non-automatic air circuit breaker. This is based on the measuring chain of a shunt resistor and the DIGmat S100 tripping unit. Shunt resistors are available for 1000 A, 2000 A and 4000 A (special ranges on request). They are in accordance with DIN 43703 and have a class accuracy of 0.5. A measuring-circuit voltage of 60 mV DC is picked off for the rated current In. The measuring-circuit voltage is a linear image of the primary current. DIGmat S100 The DIGmat S100 trip unit monitors the image of the primary current thus supplied and compares it with the tripping characteristic curve set on the device. The parameter settings on the DIGmat S100 apply also for DC feedbacks. Reversing duty is thus possible. * Short-circuit protection: Setting range Ii = 1.25 x IR to max. 4 x In Tripping occurs in less than 50 ms if the set value is exceeded. In IR tR Ii The tripping characteristic curve is determined and described by the following variables: * Overload protection: Setting range IR = 0.4 ... 1.0 In The characteristic curve has a I2t characteristic. The tripping time tR is selectable between 2 and 10 s, with tR defined for 6 x IR. = = = = Rated current of the circuit breaker Current setting value of the adjustable overload release Assigned tripping time of the overload trip Instantaneous tripping current of the adjustable short-circuit release The components are available only from the company mat - Maschinen- und Anlagentechnik: mat - Maschinen- und Anlagentechnik Dr. Becker GmbH Rudolf-Diesel-Strae 22 22941 Bargteheide Tel.: +49 (4532) 20-2101 Fax: +49 (4532) 20-2121 Email: info@m-a-t.de Internet: www.m-a-t.de Configuration * The bending radii of the Bowden cable must be > 500 mm * The total bending angle across the length of the Bowden cable must not exceed 640 * If the circuit breakers to be interlocked are arranged vertically, the interlock mechanisms must be aligned * Circuit breakers to be interlocked must be arranged so that Bowden cables can be optimally installed in compliance with the conditions mentioned in the above points * The installed Bowden cable must be fixed (with cable ties or the like) before the interlock is adjusted * Select the width of switchboard cubicle to allow enough freedom of movement for adjusting the interlock! * Openings and cutout sections in system elements must be designed in such a way that the direction of the Bowden cables is not changed and that the wires are not obstructed when they are routed Mutual mechanical circuit breaker interlocks The module for mutual mechanical interlocking can be used for two or three 3WL circuit breakers and can be adapted easily to the corresponding versions. The fixed-mounted and withdrawable circuit breaker versions are fully compatible and can therefore be used in a mixed configuration in an installation. This also applies to 3WN6 circuit breakers. The circuit breakers can be mounted adjacent to each other or one above the other, whereby the distance of the circuit breakers is determined solely by the length of the Bowden cable (lengths: 2 m/3 m/4.5 m). Interlock signals are looped through using the Bowden cables. Interlocking is only effective in the connected position in the case of withdrawable circuit breakers. The mechanical endurance of the Bowden cables is 10000 operating cycles. To ensure that the interlock functions properly, the following minimum switchboard requirements must be fulfilled: * Bowden cables must be laid so that they are as straight as possible Mutual mechanical interlocking of circuit breakers - examples Mutual interlocking of two circuit breakers S1 S2 Interlocking of three circuit breakers S3 S1 S2 NSE0_01041 NSE0_01042 Mutual interlocking of three circuit breakers S1 S1 S2 NSE0_01043 S2 S3 Interlocking of three circuit breakers, two of them mutual S1 S3 S2 S3 NSE0_01044 NSE0_01045 Siemens * 04/2018 21 (c) Siemens AG 2018 3WL1 Air Circuit Breakers 3WL1 Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC), IEC General data Communication-capable circuit breakers 20 Ethernet 18 19 PROFIBUS PROFINET 6 5 3VA-line 1 14 15 16 17 CubicleBUS 9 3VA-line 2 1 13 21 8 10 11 1 12 3 NSE0_01105 4 12 Metering function Plus 1 3VA molded case circuit breakers 2 3VL molded case circuit breaker 13 Zone Selective Interlocking module 3 Electronic Trip Unit ETU / LCD ETU 14 Digital output module with relay contacts 4 COM800 breaker data server 15 Digital output module with relay contacts, configurable 5 COM100 breaker data server 16 Analog output module 6 COM20 Release 2 PROFIBUS module including Zone Selective Interlocking 17 Digital input module 7 BDA Plus with Ethernet interface 18 Powerconfig commissioning and service software V2.3 and higher 8 3WL air circuit breaker 19 PLC, e.g. SIMATIC S7 9 COM15 PROFIBUS module 20 E.g. SIMATIC powerrate 21 7KM PAC measuring devices 10 Breaker Status Sensor (BSS) 11 Electronic Trip Unit (ETU) Communication with PROFIBUS DP 22 Siemens * 04/2018 7 (c) Siemens AG 2018 3WL1 Air Circuit Breakers 3WL1 Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC), IEC General data 11 Ethernet MODBUS TCP 6 7 8 10 RS 485 with MODBUS RTU 3VA-line 3VA-line 9 5 3 1 1 2 4 I201_19162 1 1 3VA molded case circuit breakers 7 COM100 breaker data server 2 3WL air circuit breaker 8 7KM PAC4200 measuring device 3 COM16 MODBUS module 9 7KM PAC3100 measuring device 4 3VL molded case circuit breaker 10 7KM PAC3200 measuring device 5 COM21 MODBUS module 11 Powerconfig commissioning and service software V2.3 and higher 6 COM800 breaker data server Communication with MODBUS RTU The requirements for power distribution in terms of communication capability, data transparency, flexibility and integration are constantly increasing. An integrated and modular communication architecture was designed for the 3WL circuit breaker to ensure that it can satisfy these requirements. The core component of this architecture is the CubicleBUS, which links together all of the intelligent components within the 3WL circuit breaker and enables the easy and safe connection of other additional external components to the circuit breaker. The CubicleBUS is already incorporated and connected in all complete circuit breakers with ETU45B and ETU76B trip units. The high modularity of the system allows retrofitting of communication functions (e.g. metering function) at any time. Similarly, a non-communication-capable 3WL circuit breaker can be upgraded (e.g. changeover from ETU25B to ETU45B with CubicleBUS) easily on site in the plant. All modules connected to the CubicleBUS can directly access the existing source data of the circuit breaker, which guarantees the quickest possible access to information and response to events. Furthermore, additional external modules (including digital inputs and outputs, analog outputs) can be connected to the CubicleBUS to provide cost-effective solutions for the automation of additional devices in the switchboard. Siemens * 04/2018 23 (c) Siemens AG 2018 3WL1 Air Circuit Breakers 3WL1 Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC), IEC General data Communication-capable 3WL circuit breakers Function Electronic Trip Unit Breaker PROFIBUS Metering Analog version Status communi- function output module ETU45B ETU76B Sensor cation port Plus Digital Digital ZSI Breaker output input module Data module module Adapter Plus Functions of the communication-capable 3WL circuit breakers Indication of measured values in trip unit (current only) Indication of measured values in the trip unit (U, I, P, S, Q, p.f., etc.) Indication of measured values (current only), parameters, diagnostic values etc. on display -- Indication of measured values (U, I, P, S, Q, p.f., etc.), parameters, diagnostic values, etc. in trip unit -- Output of measured values (current only) to rotary coil instruments in control cabinet door Output of measured values (U, I, P, S, Q, p.f., etc.) to rotary coil instruments in control cabinet door Output of digital signals (e.g. reason for tripping, alarms, status) through contacts Automatic changeover between parameter sets A and B -- Read-in of digital signals and forwarding to PROFIBUS/MODBUS Transmission of breaker information on HTML basis locally to a PC Transmission of breaker information on HTML basis through Ethernet Short-time discrimination for S tripping and G protection Local display of harmonics analysis and waveform memory -- Local storage of harmonics analysis and waveform memory and transmission through PROFIBUS Read-out of protection parameters through PROFIBUS Read-out and adjustment of protection parameters through PROFIBUS -- Required Not necessary for this function, optionally combinable Function can optionally be adopted by several trip units. -- Function can optionally be adopted by one of these modules. 24 Siemens * 04/2018 Function not available (c) Siemens AG 2018 3WL1 Air Circuit Breakers 3WL1 Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC), IEC General data Data that can be transmitted over the PROFIBUS DP/MODBUS or the Breaker Data Adapter All 3WL circuit breakers with ETU45B, ETU76B (CubicleBUS integrated) Transmittable circuit breaker data BSS Order code (Article No. of circuit breaker + "-Z") BDAPLUS BSS F01 + "BDAPLUS"Article No. Article No. COM15/COM16 F02/F12 Possible applications Transmission of circuit breaker data to PROFIBUS DP or MODBUS and integration into higher-level visualization systems possible e.g. in PCS7, Power Management Systems, WinCC (including add-ons like the text message radio server) -- Transmission of circuit breaker data and software (i.e. HTML pages with data) to a local output device, or remotely through Ethernet/Intranet/Internet (without the possibility of integration into higher-level visualization systems) e.g. for monitoring, diagnostics, maintenance and parameterization of individual circuit breakers -- Utilization of the functionality of all CubicleBUS modules e.g. configuration of the configurable digital output module, status check of the digital input modules, diagnostics --1) Operating states On/Off status message, spring energy store, tripped, readiness Breaker position (connected, test and disconnected position, removed) for withdrawable circuit breakers, PROFIBUS/MODBUS write protection on/off, free user input, tripped signal --1) --1) Control commands Switch circuit breaker on/off, switch free user output on/off Reset tripped signal Delete event and history memory Reset min./max. measured values, reset maintenance information --1) --1) History Read-out of event log, read-out of trip log --1) Maintenance information Number of tripping operations L, S/I and in total, contact wear Number of operating cycles under load and in total, number of operating hours --1) Event signals Tripped signals with details of the tripping current Alarm signals (e.g. overload) with incoming/outgoing information All of the named event signals with time stamp --1) --1) Parameterization of the protection functions Read-out of the protection function parameters Settings for the protection function parameters can be changed by means of communication Parameter set switchover possible (set A to set B and back) 2) 2) 2) 2) Measured values Phase currents, each with min./max. value Temperature in the circuit breaker with min./max. value Temperature in the control cabinet with min./max. value All of the named measured values with time stamp --1) --1) --1) Transmittable circuit breaker data without integrated metering function Device identification Communication address, Article No. Circuit breaker in delivery state, circuit breaker parameters (size, number of poles, rating plug etc.), identification numbers, trip unit type, free text for plant code and comments Metering function Plus Order code F01+ ... or F02+ ... F05 Additional transmittable circuit breaker data with integrated metering function Additional event signals Threshold value alarms (e.g. over/underfrequency, over/undervoltage) Parameterization of the extended protection functions and setpoints (threshold values) Read-out of the parameters of the extended protection functions Settings for the extended protection function parameters can be changed Read-out and adjustment of threshold values Additional measured values Voltages, power, energy, p.f., frequency, each with min./max. value Harmonics analysis Recording of currents and voltages for configurable events in the waveform memory 1) Data only available in conjunction with the COM15 module (BUS connection not required). 2) Only possible with ETU76B. Available -- Not available Siemens * 04/2018 25 (c) Siemens AG 2018 3WL1 Air Circuit Breakers 3WL1 Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC), IEC General data CubicleBUS modules Digital output module with rotary coding switch 6 items of binary information concerning the state of the circuit breaker (reasons for tripping and alarms) can be output via this module to external signaling devices (e.g. LED, horn) or used for the selective shutdown of other system components (e.g. frequency converters). Digital output modules are available in versions with and without a rotary coding switch. On modules with a rotary coding switch it is possible to choose between two signaling blocks each with 6 defined assignments and to set an additional response delay. All the digital output modules are available as a version with relay outputs (CO contacts, up to 12 A). Up to two modules of this type can be connected to one 3WL circuit breaker. Analog output module Digital input module With the digital input module, up to 6 additional binary signals (24 V DC) in the circuit breaker environment can be connected to the system. It is thus possible for example to send messages concerning the state of a switch disconnector or a control cabinet door to the PROFIBUS DP/MODBUS. With the digital input module on the CubicleBUS it is also possible for the two different protection parameter sets held in the ETU76B Electronic Trip Unit trip unit to be switched over automatically in a few milliseconds. It is thus possible, for example, to automatically change the parameters of a tie-breaker should the transformer infeed fail. Digital output module with rotary coding switch One module each of this type can be used for holding the six items of digital information and for automatically switching over the parameters. Digital output module, configurable The configurable output module is available for higher-performance solutions. With this module, random events on the CubicleBUS can be switched directly to one of six available outputs or three of these outputs can be assigned with up to six events. In other words, up to six events can be placed on one physical output with "OR" operation. Either BDA Plus or powerconfig is used for configuring. A relay variant is also available here the same as for the output modules with rotary coding switch. Only one module of this type is possible per 3WL circuit breaker. Digital input module ZSI module (short-time discrimination control) The use of ZSI modules is recommended when Siemens circuit breakers are arranged in several staggered levels but full discrimination with the smallest possible delay is to be assured nevertheless. Digital output module, configurable Analog output module The analog output module can be used to output the following measured values to analog indicators in the control cabinet door: * IL1, IL2, IL3, IN or * UL12, UL23, UL31, UL1N or * PL1, PL2, PL3, Stot or * p.f.1, p.f.2, p.f.3, I % or * favg, ULLavg, Ptot, p.f. avg Four 4-20 mA/0-10 V interfaces are available for this. The measured values to be output are selected with a rotary coding switch. By using the analog output module it is possible to do without additional converters and their conventional installation/ wiring in the main conducting path. Up to two modules of this type can be connected to one 3WL circuit breaker. 26 Siemens * 04/2018 The circuit breakers are interconnected by these modules. In case of a short-circuit, each affected circuit breaker interrogates the circuit breakers directly downstream whether the shortcircuit has also occurred in the next, lower level. The short-circuit is exactly localized as a result, and only the next upstream circuit breaker in the energy flow direction is switched off. ZSI module (short-time discrimination control) (c) Siemens AG 2018 3WL1 Air Circuit Breakers 3WL1 Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC), IEC General data Technical specifications Size Type Number of poles Rated current In at 40 C, at 50/60 Hz Main conductor N-conductor (only on 4-pole versions) Rated operational voltage Ue at 50/60 Hz (1000 V version, see Catalog LV 10 "Options") Rated insulation voltage Ui Rated impulse withstand voltage Uimp * Main conducting paths * Auxiliary circuits * Control circuits9) Isolating function acc. to EN 60947-2 Utilization category Permissible ambient temperature * During operation (in operation with LCD max. 55 C)1) * Storage Permissible load for * Up to 55 C (Cu bare) withdrawable versions * Up to 60 C (Cu bare)2) at rear horizontal main circuit * Up to 70 C connections (Cu painted black)2) Rated rotor operational voltage Uer Power loss at In With 3-phase symmetrical load * Fixed-mounted circuit breakers * Withdrawable circuit breakers Switching times * Make time * Opening time * Electrical make time (through closing coil)4) * Electrical opening time (through shunt release) I II ... 3WL11 10 3WL11 12 3WL11 16 3WL11 20 3WL12 08 3WL12 10 3WL12 12 3WL12 16 3-pole, 4-pole A ... 1000 A ... 1000 V AC ... 690/1000 V AC 1000 1250 1250 ... 690/1000 1000 1600 1600 ... 690/1000 1000 2000 2000 ... 690/1000 1000 800 800 ... 690/1000 1000 1000 1000 ... 690/1000 1000 1250 1250 ... 690/1000 1000 1600 1600 ... 690/1000 1000 kV 12 kV 4 kV 2.5 Yes B 12 4 2.5 Yes 12 4 2.5 Yes 12 4 2.5 Yes 12 4 2.5 Yes 12 4 2.5 Yes 12 4 2.5 Yes 12 4 2.5 Yes C C A A A -25/+70 -40/+70 1250 1250 1210 -25/+70 -40/+70 1600 1600 14903) -25/+70 -40/+70 2000 1930 1780 -25/+70 -40/+70 800 800 800 -25/+70 -40/+70 1000 1000 1000 -25/+70 -40/+70 1250 1250 1250 -25/+70 -40/+70 1600 1600 1600 V 2000 2000 2000 2000 2000 2000 2000 2000 W 100 W 195 105 205 150 350 240 440 40 85 45 95 80 165 85 175 ms 35 ms 38 35 38 35 38 35 38 35 34 35 34 35 34 35 34 ms 80 ms 73 80 73 80 73 80 73 100 73 100 73 100 73 100 73 73 73 73 73 73 73 73 73 50 50 50 50 50 50 50 50 10 000 20 000 10 000 --20 000 10 000 20 000 10 000 --20 000 10 000 20 000 10 000 --20 000 10 000 15 000 7500 --15 000 10 000 15 000 7500 --15 000 10 000 15 000 7500 --15 000 10 000 15 000 7500 --15 000 10 000 15 000 7500 --15 000 10 000 15 000 7 500 1000 -15 000 10 000 15 000 7 500 1000 -15 000 10 000 15 000 7 500 1000 -15 000 10 000 15 000 7500 1000 -15 000 10 000 15 000 7500 1000 500 15 000 10 000 15 000 7500 1000 500 15 000 10 000 15 000 7500 1000 500 15 000 10 000 15 000 7500 1000 500 15 000 10 000 15 000 7 500 1000 -10 000 10 000 15 000 7 500 1000 -10 000 10 000 15 000 7 500 1000 -10 000 10 000 15 000 7500 1000 -10 000 10 000 15 000 7500 1000 500 15 000 10 000 15 000 7500 1000 500 15 000 10 000 15 000 7500 1000 500 15 000 10 000 15 000 7500 1000 500 15 000 ----- ----- ----- ----- 5 000 10 000 5 000 10 000 5 000 10 000 5 000 10 000 5 000 10 000 5 000 10 000 5 000 10 000 5 000 10 000 608) --80 608) --80 608) --80 60 20 -80 608) 20 20 80 608) 20 20 80 608) 20 20 80 608) 20 20 80 ms * Electrical opening time (instantaneous undervoltage release) * Opening time due to ETU, instantaneous short-circuit ms release Service life: Breaking capacity N and S, 3-/4-pole * Mechanical (without maintenance) Operating cycles Operating cycles * Mechanical (with maintenance)5) * Electrical (without maintenance) Operating cycles * 1000 V version, electrical (without maintenance) Oper. cycles * 1150 V version, electrical (without maintenance) Oper. cycles Operating cycles * Electrical (with maintenance)5) Service life: Breaking capacity H, 3-pole * Mechanical (without maintenance) Operating cycles Operating cycles * Mechanical (with maintenance)5) * Electrical (without maintenance) Operating cycles * 1000 V version, electrical (without maintenance) Oper. cycles * 1150 V version, electrical (without maintenance) Oper. cycles Operating cycles * Electrical (with maintenance)5)6) Service life: Breaking capacity H, 4-pole * Mechanical (without maintenance) Operating cycles Operating cycles * Mechanical (with maintenance)5) * Electrical (without maintenance) Operating cycles * 1000 V version, electrical (without maintenance) Oper. cycles * 1150 V version, electrical (without maintenance) Oper. cycles Operating cycles * Electrical (with maintenance)5)6) Service life: Breaking capacity C * Mechanical (without maintenance) Operating cycles Operating cycles * Mechanical (with maintenance)5) * Electrical (without maintenance) Operating cycles Operating cycles * Electrical (with maintenance)5) Switching frequency7) * 690 V version 1/h * 1000 V version 1/h * 1150 V version 1/h Minimum interval between tripping operation by ms Electronic Trip Unit and next making operation of the circuit breaker (only with automatic mechanical resetting of the lockout device). Minimum interval between On-Off or Off-On switching operations. 1) 2) 3) 4) -25/+70 -40/+70 1000 1000 1000 Use of trip units from -20 C ETU76B with graphics display can be used up to max. 55 C. At breaking capacity H: 1600 A to 70 C. Make time through closing coil for synchronization purposes (short-time excited) 50 ms. 5) Maintenance means: Replace main contact elements and arc chutes (see Operating Manual). 6) 7) 8) 9) Replacement of the main contact elements of circuit breakers size I with breaking capacity H is only possible at the factory. Minimum interval time between 2 tripping operations. 3-pole switching with breaking capacity N and S: 45/h. Motorized operating mechanisms Uimp = 1.2 kV Siemens * 04/2018 27 (c) Siemens AG 2018 3WL1 Air Circuit Breakers 3WL1 Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC), IEC General data I II ... 3WL11 10 3WL11 12 3WL11 16 3WL11 20 3WL12 08 3WL12 10 3WL12 12 3WL12 16 30 30 30 30 Dhmax. = 1 mm Size Type Mounting position and/or NSE0_00062a NSE0_00061a Degree of protection Main conductor minimum cross-sections Auxiliary conductors (Cu) Max. number Auxiliary conductors x cross-section (solid/stranded) Unit(s) * Copper bars, mm2 bare Unit(s) * Copper bars, mm2 painted black Standard connection = strain-relief clamp * Without end sleeve 2 x 0.5 mm2 (AWG 20) ... 2 x 1.5 mm2 (AWG 16); 1 x 2.5 mm2 (AWG 14) * With end sleeve acc. to 1 x 0.5 mm2 (AWG 20) ... 1 x 1.5 mm2 (AWG 16) DIN 46228 Part 2 2 x 0.5 mm2 (AWG 20) ... 2 x 1.5 mm2 (AWG 16) * With twin end sleeve Optional connection = tension spring * Without end sleeve 2 x 0.5 mm2 (AWG 20) ... 2 x 2.5 mm2 (AWG 14) * With end sleeve acc. to 2 x 0.5 mm2 (AWG 20) ... 2 x 1.5 mm2 (AWG 16) DIN 46228 Part 2 Position signaling switches Tension spring terminals Weights 3-pole * Fixed-mounted circuit breakers * Withdrawable circuit breakers * Guide frames 4-pole * Fixed-mounted circuit breakers * Withdrawable circuit breakers * Guide frames Dimensions 3-/4-pole H W 56 56 56 kg 45 45 45 45 60 60 60 60 kg 25 kg 50 25 50 25 50 25 50 31 67 31 67 31 67 31 67 kg 54 54 54 54 72 72 72 72 kg 30 30 30 30 37 37 37 37 320/410 460/590 Fixed-mounted H mm D mm 434 291 434 291 Withdrawable H mm D mm 465.5 471 465.5 471 D Siemens * 04/2018 2x 50 x 10 2x 50 x 10 1 x 0.5 mm2 (AWG 20) ... 1 x 2.5 mm2 (AWG 14) 43 43 43 56 kg 43 W mm NSS0_00535 28 NSE0_00927 IP20 without cabinet door, IP41 with door sealing frame, IP55 with cover 1x 2x 2x 3x 1x 1x 2x 60 x 10 40 x 10 50 x 10 50 x 10 50 x 10 60 x 10 40 x 10 1x 2x 2x 3x 1x 1x 2x 60 x 10 40 x 10 50 x 10 50 x 10 50 x 10 60 x 10 40 x 10 (c) Siemens AG 2018 3WL1 Air Circuit Breakers 3WL1 Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC), IEC General data Size II Type 3WL12 20 3WL12 25 3WL12 32 3WL12 40 3WL13 40 3WL13 50 3WL13 63 3-pole, 4-pole Number of poles Rated current In at 40 C, at 50/60 Hz Main conductor N-conductor (only on 4-pole versions) III A 2000 A 2000 2500 2500 3200 3200 4000 4000 4000 4000 5000 5000 6300 6300 Rated operational voltage Ue at 50/60 Hz (1000 V version, see Catalog LV 10 "Options") V AC ... 690/1000 ... 690/1000 ... 690/1000 ... 690 ... 690/1000 ... 690/1000 ... 690/1000 Rated insulation voltage Ui V AC 1000 1000 1000 1000 1000 1000 1000 kV 12 kV 4 kV 2.5 12 4 2.5 12 4 2.5 12 4 2.5 12 4 2.5 12 4 2.5 12 4 2.5 Yes Yes Yes Yes Yes Yes -25/+70 -40/+70 -25/+70 -40/+70 -25/+70 -40/+70 -25/+70 -40/+70 -25/+70 -40/+70 -25/+70 -40/+70 A 2000 A 2000 A 2000 2500 2500 2280 3200 3020 2870 39503) 3810 3600 4000 4000 4000 5000 5000 5000 5920 5810 5500 V 2000 2000 2000 2000 2000 2000 2000 W 180 W 320 270 520 410 710 750 925 520 810 630 1050 900 1600 Rated impulse withstand voltage Uimp * Main conducting paths * Auxiliary circuits * Control circuits10) Isolating function acc. to EN 60947-2 Yes Utilization category B Permissible ambient temperature * During operation (in operation with LCD max. 55 C)1) * Storage Permissible load for with- * Up to 55 C (Cu bare) * Up to 60 C (Cu bare)4) drawable versions2) * Up to 70 C (Cu painted black)4) Rated rotor operational voltage Uer Power loss at In With 3-phase symmetrical load * Fixed-mounted circuit breakers * Withdrawable circuit breakers C -25/+70 C -40/+70 Switching times * Make time * Opening time ms ms 35 34 35 34 35 34 35 34 35 34 35 34 35 34 * Electrical make time (through closing coil)5) * Electrical opening time (through shunt release) ms 100 ms 73 100 73 100 73 100 73 100 73 100 73 100 73 * Electrical opening time (instantaneous undervoltage release) * Opening time due to ETU, instantaneous short-circuit release ms ms 73 50 73 50 73 50 73 50 73 50 73 50 73 50 Service life: Breaking capacity N, S and H11) * Mechanical (without maintenance) * Mechanical (with maintenance)6) * Electrical (without maintenance) up to 690 V * 1000 V version, electrical (without maintenance) * 1150 V version, electrical7) (without maintenance) * Electrical (with maintenance)6) Operating cycles 10000 Operating cycles 15000 Operating cycles 7500 Operating cycles 1000 Operating cycles 500 Operating cycles 15000 10000 15000 7500 1000 500 15000 10000 15000 4000 1000 500 15000 10000 15000 2000 1000 500 15000 5000 10000 2000 1000 500 10000 5000 10000 2000 1000 500 10000 5000 10000 2000 1000 500 10000 Service life: Breaking capacity C * Mechanical (without maintenance) * Mechanical (with maintenance)6) * Electrical (without maintenance) up to 690 V * Electrical (without maintenance) up to 1150 V * Electrical (with maintenance) up to 690 V6) Operating cycles 5000 Operating cycles 10000 Operating cycles 5000 Operating cycles -Operating cycles 10000 5000 10000 5000 -10000 5000 10000 4000 -8000 ------ 5000 10000 1000 500 -- 5000 10000 1000 500 -- 5000 10000 1000 500 -- 1/h 609) 1/h 20 1/h 20 609) 20 20 609) 20 20 609) 20 20 60 20 20 60 20 20 60 20 20 ms 80 80 80 80 80 80 80 Switching frequency8) * 690 V version * 1000 V version * 1150 V version7) Minimum interval between tripping operation by Electronic Trip Unit and next making operation of the circuit breaker (only with automatic mechanical resetting of the lockout device). Minimum interval between On-Off or Off-On switching operations. 1) Use of trip units from -20 C 2) 6) 4000 A, size II in fixed-mounted version, 3-pole. Maintenance means: Replace main contact elements and arc chutes (see Operating Manual). 3) Derating factors for fixed mounting of 3WL12 40. 4) 7) ETU76B with graphics display can be used up to max. 55 C. Size II with order code "A15" and size III: data for very high breaking capacity. 5) 8) Make time through closing coil for synchronization purposes (short-time excited) 50 ms. Minimum interval time between 2 tripping operations. 9) 3-pole switching with breaking capacity N and S: 45/h. 10) Motorized operating mechanisms Uimp = 1.2 kV 11) 1000 V and 1150 V versions only in the case of H breaking capacity Siemens * 04/2018 29 (c) Siemens AG 2018 3WL1 Air Circuit Breakers 3WL1 Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC), IEC General data II Type 3WL12 20 3WL12 25 3WL12 32 3WL12 40 3WL13 40 3WL13 50 3WL13 63 III Mounting position Dhmax. = 1 mm Size 30 30 30 30 and/or NSE0_00927 NSE0_00062a NSE0_00061a IP20 without cabinet door, IP41 with door sealing frame, IP55 with cover Degree of protection Main conductor minimum cross-sections * Copper bars, bare Unit(s) 3 x mm2 50 x 10 2x 100 x 10 3x 100 x 10 4x 120 x 10 4x 100 x 10 6x 100 x 10 6x 120 x 10 * Copper bars, painted black Unit(s) 3 x mm2 50 x 10 2x 100 x 10 3x 100 x 10 4x 4x 100 x 101) 100 x 10 6x 100 x 10 6x 120 x 10 Auxiliary conductors (Cu) Max. number of auxiliary conductors x cross-section (solid/stranded) Standard connection = strain-relief clamp * Without end sleeve * With end sleeve acc. to DIN 46228 Part 2 * With twin end sleeve 2 x 0.5 mm2 (AWG 20) ... 2 x 1.5 mm2 (AWG 16) Optional connection = tension spring * Without end sleeve * With end sleeve acc. to DIN 46228 Part 2 2 x 0.5 mm2 (AWG 20) ... 2 x 2.5 mm2 (AWG 14) 2 x 0.5 mm2 (AWG 20) ... 2 x 1.5 mm2 (AWG 16) Position signaling switches Tension spring terminals 1 x 0.5 mm2 (AWG 20) ... 1 x 2.5 mm2 (AWG 14) Weights 3-pole * Fixed-mounted circuit breakers * Withdrawable circuit breakers * Guide frames kg 56 kg 60 kg 31 59 63 39 64 68 45 85 121 52 82 88 60 82 88 60 90 96 70 4-pole * Fixed-mounted circuit breakers * Withdrawable circuit breakers * Guide frames kg 67 kg 72 kg 37 71 76 47 77 82 54 103 146 62 99 106 84 99 106 84 108 108 119 Dimensions 3-/4-pole W mm 460/590 704/914 Fixed-mounted H mm D mm 434 291 434 291 Withdrawable H mm D mm 465.5 471 465.5 471 D H W 2 x 0.5 mm2 (AWG 20) ... 2 x 1.5 mm2 (AWG 16); 1 x 2.5 mm2 (AWG 14) 1 x 0.5 mm2 (AWG 20) ... 1 x 1.5 mm2 (AWG 16) NSS0_00535 Minimum main conductor cross-sections for 4-pole withdrawable circuit breakers: 4 x 120 x 10 mm. Calculating the power consumption of the CubicleBUS modules for SENTRON WL with CubicleBUS system CubicleBUS module Number of modules per CubicleBUS ETU45B Electronic Trip Unit ETU76B Electronic Trip Unit Metering function PLUS 1 1 1 Breaker Status Sensor BSS 1 1 COM15 PROFIBUS communication module ZSI module Digital output modules with rotary coding switch, relay outputs Digital output modules, configurable, relay outputs Analog output modules Digital input modules BDA PLUS 30 Siemens * 04/2018 Max. continuous current per module from the CubicleBUS 120 mA 170 mA Max. startup current per module from the CubicleBUS 2000 mA 2000 mA 120 mA 40 mA 120 mA 110 mA 1 1-2 125 mA 50 mA 180 mA 280 mA 125 mA 125 mA 1 180 mA 125 mA 1-2 1-2 1 110 mA 30 mA 250 mA 800 mA 125 mA 350 mA (c) Siemens AG 2018 3WL1 Air Circuit Breakers 3WL1 Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC), IEC General data Size I to III Type 3WL1 Manual operating mechanism with mechanical closing N 230 9 Switching on/charging Max. force required to operate the hand lever the energy store Required number of strokes on the hand lever Manual operating mechanism with mechanical and electrical closing Charging the energy store Closing coil (CC) * Primary operating range 0.85 ... 1.1 x Us * Extended operating range for battery operation At 24 V DC, 48 V DC 60 V DC, 110 V DC 220 V DC * Rated control supply voltage Us 50/60 Hz AC DC * Power consumption AC/DC * Min. command duration at Us for the closing coil 0.7 ... 1.26 x Us V 110 ... 127; 208 ... 240 V 24; 30; 48; 60; 110 ... 125; 220 ... 250 VA/ 15/15 W ms 60 1 A TDz (slow)/1 A * Short-circuit protection Smallest permissible DIAZED fuse (operational class gL)/ automatic circuit breaker with C characteristic Manual/motorized operating mechanism with mechanical and electrical closing For data, see above. Manual operating mechanism Motor 0.85 ... 1.1 x Us * Primary operating range * Extended operating range for battery operation At 24 V DC, 48 V DC 60 V DC, 110 V DC 220 V DC * Power consumption of motor AC/DC VA/ 135/135 W s 10 * Time required to charge the spring energy store at 1 x Us For data, see above. Closing coil For motor and closing coil 0.7 ... 1.26 x Us * Short-circuit protection Smallest permissible DIAZED fuse (operational class gL)/ automatic circuit breaker with C characteristic; Motor and closing coil for same rated control supply voltages 6 A TDz (slow)/2 A * Smallest permissible DIAZED fuse (operational class gL)/ At Us = 24 ... 30 V automatic circuit breaker with C characteristic (for different At Us = 48 ... 60 V rated control supply voltages) At Us = 110 ... 125 V DC/ 110 ... 127 V AC At Us = 220 ... 250 V DC/ 208 ... 240 V AC 6A 6A 2A 2A Signals of the Electronic Trip Unit Protection functions acc. to EN 60947; Current indication 10%; Metering function for base quantities 1%; Metering function for derived quantities 4% Measuring accuracy of the Electronic Trip Unit Auxiliary releases Undervoltage releases * Response values UVR (F3) and UVR-td (F4) Pickup Dropout 0.85 ... 1.1 * Primary operating range * Extended operating range for battery operation At 24 V DC, 30 V DC, 48 V DC, 110 V DC, 220 V DC * Rated control supply voltage Us Instantaneous 50/60 Hz AC DC V 110 ... 127/208 ... 240/380 ... 415 V 24/30/48/60/110 ... 125/220 ... 2501) Delayed 50/60 Hz AC DC V 110 ... 127; 208 ... 240; 380 ... 415 V 48; 110 ... 125; 220 ... 250 * Power consumption (pickup/uninterrupted duty) * Opening time of the circuit breaker at Us = 0 - Version UVR (F3) Without delay With delay - Version UVR-td (F8) With delay, td = 0.2 to 3.2 s Reset through additional NC contact - direct tripping * Short-circuit protection Smallest permissible DIAZED fuse (operational class gL)/ automatic circuit breaker with C characteristic 1) 0.85 x Us (circuit breaker can be closed) 0.35 ... 0.7x Us (circuit breaker is opened) AC DC 0.85 ... 1.26 VA 20/5 W 20/5 ms 200 80 ms ms 200 s 0.2 ... 3.2 ms 100 1 A TDz (slow)/1 A 24 V and 30 V only with undervoltage release UVR (F3). Siemens * 04/2018 31 (c) Siemens AG 2018 3WL1 Air Circuit Breakers 3WL1 Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC), IEC General data Size I to III Type 3WL1 Auxiliary releases Shunt releases (ST) (F1, F2) * For continuous command (100% OP), locks out on momentary-contact commands - Response value Pickup > 0.7 x Us (circuit breaker is tripped) 0.85 ... 1.1 x Us - Primary operating range - Extended operating range for battery operation At 24 V DC, 48 V DC 60 V DC, 110 V DC 220 V DC - Rated control supply voltage Us 50/60 Hz AC DC - Power consumption AC/DC V 110 ... 127; 208 ... 240 V 24; 30; 48; 60; 110 ... 125; 220 ... 250 VA/W 15/15 ms 60 - Min. command duration at Us - Opening time of circuit breaker at Us = 100% 5% OP At AC/DC ms 80 - Short-circuit protection Smallest permissible DIAZED fuse (operational class gL)/ automatic circuit breaker with C characteristic 1 A TDz (slow)/1 A - Response value > 0.7 x Us (circuit breaker is tripped) Pickup 0.85 ... 1.1 x Us - Primary operating range - Extended operating range for battery operation At 24 V DC, 48 V DC 60 V DC, 110 V DC 220 V DC - Rated control supply voltage Us 50/60 Hz AC DC - Power consumption AC/DC - Opening time of circuit breaker at Us = 100% VA/W 15/15 ms 25 At AC/DC ms 50 - Short-circuit protection Smallest permissible DIAZED fuse (operational class gL)/ automatic circuit breaker with C characteristic - Rated control supply voltage Us 1 A TDz (slow)/1 A 50/60 Hz AC DC V 110; 230 V 110; 220 0.85 ... 1.1 x Us - Primary operating range - Power consumption 0.7 ... 1.26 x Us V 110 ... 127; 208 ... 240 V 24; 48; 110 ... 125; 220 ... 250 - Min. command duration at Us * With spring energy store consisting of shunt release and capacitor storage device 0.7 ... 1.26 x Us AC/DC VA/W 1/1 - Storage time at Us/ Recharging time at Us max. 5 min/min. 5 s - Opening time of the circuit breaker, short-circuit protection As with "for continuous command" Remote reset solenoid for mechanical tripped indicator (F7) 0.85 ... 1.1 x Us - Primary operating range Remote reset solenoid for mechanical tripped indicator (F7) - Extended operating range for battery operation At 24 V DC, 48 V DC 110 V DC 220 V DC - Power consumption AC/DC 0.7 ... 1.26 x Us VA/W 50/50 - Min. command duration at Us for the remote reset solenoid ms 60 - Short-circuit protection Smallest permissible DIAZED fuse (operational class gL)/ automatic circuit breaker with C characteristic 2 A TDz (slow)/1 A at 24 V DC and 48 V DC, 1 A TDz (slow)/1 A at 110 V and 208 ... 250 V Contact position-driven auxiliary switches (S1, S2, S3, S4, S7, S8) Rated insulation voltage Ui V 500 AC/DC Rated operational voltage Ue V 500 AC/DC kV 4 Rated impulse withstand voltage Uimp Breaking capacity * Alternating current 50/60 Hz * Direct current Short-circuit protection 32 - Rated operational voltage Ue - Rated operational current Ie/AC-12 Ie/AC-15 - Rated operational voltage Ue - Rated operational current Ie/DC-12 Ie/DC-13 * Largest permissible DIAZED fuse (operational class gL) * Largest permissible miniature circuit breaker with C characteristic Siemens * 04/2018 V 24 ... 230 A 10 A 4 380/400 10 3 V 24 48 A 10 A 8 8 4 110 3.5 1.2 10 A TDz, 10 A Dz 10 A 220 1 0.4 (c) Siemens AG 2018 3WL1 Air Circuit Breakers 3WL1 Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC), IEC General data Size I to III Type 3WL1 Ready-to-close signaling switches (S20) (acc. to DIN VDE 0630) Breaking capacity Short-circuit protection * Alternating current - Rated operational voltage Ue - Rated operational current Ie V 250 A 8 * Direct current - Rated operational voltage Ue - Rated operational current Ie V 125 A 0.4 Largest permissible DIAZED fuse (operational class gL) 250 0.2 2 A Dz (quick) Tripped signaling switches (S24) and signaling switches for auxiliary releases (S22, S23) (acc. to DIN VDE 0630) Breaking capacity * Alternating current - Rated operational voltage Ue - Rated operational current Ie/AC-12 V 250 A 8 * Direct current - Rated operational voltage Ue - Rated operational current Ie/DC-12 V A 24 6 125 0.4 250 0.2 Short-circuit protection Largest permissible DIAZED fuse (operational class gL) 6 A Dz (quick) Tripped signaling switch Signal duration after tripping Until manual or electrical remote reset (option) Position signaling switch on guide frame Type of contact * Signal: - "Circuit breaker in connected position" - "Circuit breaker in test position" - "Circuit breaker in disconnected position" 50/60 Hz AC DC Rated insulation voltage Ui - Ie/AC-12 V 440 V 250 - Ie/DC-13 24 V 10 A, 110/127 V 10 A, 220/240 V 10 A, 320/440 V 10 A 220/240 V 4 A, 320/440 V 3 A, 24 V 10 A, 48 V 2.5 A, 220/240 V 0.2 A, 24 V 3.0 A, 220/240 V 0.1 A - A 300 (AC) 120 V 6 A, 240 V 3 A - R 300 (DC) 125 V 0.22 A, 250 V 0.11 A - Ie/AC-15 - Ie/DC-12 Short-circuit protection 1 CO 1 CO 1 CO kV 4 Rated impulse withstand voltage Uimp * Rated operational current Ie or V 250 Rated operational voltage Ue Breaking capacity 3 CO 2 CO 1 CO * Largest permissible DIAZED fuse (operational class gL) * Largest permissible automatic circuit breaker with C characteristic 8 A TDz (slow) 8 A TDz (slow) Siemens * 04/2018 33 (c) Siemens AG 2018 3WL1 Air Circuit Breakers 3WL1 Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC), IEC General data Protection functions Parameterization by ETU15B D ETU25B D ETU27B D&S -0.5-0.55-0.6-0.65-0.70.75-0.8-0.85-0.9-1 -- -0.4-0.45-0.5-0.55-0.60.65-0.7-0.8-0.9-1 -- -0.4-0.45-0.5-0.55-0.60.65-0.7-0.8-0.9-1 -- 10 s fixed ------------ 10 s fixed --At tsd = 20 ms (M) --- -1.25-1.5-2-2.5-3-4-6-8-10-12 0-M-100-200-300-400 ms -- 10 s fixed --At tsd = 20 ms (M) 1 -1.25-1.5-2-2.5-3-4-6-8-10-12 0-M-100-200-300-400 ms -- -- -2-3-4-5-6-7-8 ------ -- -Fixed for Ii 20 In, max. 50 kA ------ -- -Fixed for Ii 20 In, max. 50 kA permanently installed - - -- -- -- ----- ----- A-B-C-D-E -100-200-300-400-500 ms -- --- --- --- -- -- -- --- --- --- --- --- --- -- -- -- -------- ----- --- -- -- -- -------------- -------------- -------------- Function overview of the electronic trip system Overload protection Function can be switched on/off Setting range IR = In x ... R overload protection L Switchable (I t- or I t-dependent function) 2 4 Setting range for time-lag class tR at I2t Setting range for time-lag class tR at I4t R Thermal memory can be switched on/off Phase failure sensitivity N-conductor protection Function can be switched on/off N-conductor setting range IN = In x ... Short-time delayed short-circuit protection Function can be switched on/off Setting range Isd = In x ... s d Setting range of delay time tsd Switchable short-time delayed short-circuit protection s d (I2t-dependent function) Setting range of delay time tsd at I2t ZSI function i Instantaneous short-circuit protection N S E 0 _ 0 0 8 8 8 b Function can be switched on/off Setting range Ii = In x ... Ground-fault protection Tripping and alarm functions Tripping function can be switched on/off Alarm function can be switched on/off Detection of the ground-fault current through summation current formation with internal or external g N-conductor transformer Detection of ground-fault current through external current transformer g Setting range of the response current Ig for tripping NSE0_00889a Setting range of the response current Ig for alarm Setting range of the delay time tg Switchable ground-fault characteristic (I2t-dependent function) Setting range for delay time tg at I2t ZSI-G function Parameter set changeover Switchable between parameter set A and B LCD Alphanumeric LCD (4-line) Graphical LCD (24 V, external power supply required) Communication CubicleBUS integrated Communications capability via PROFIBUS DP Metering function Metering capability with metering function Plus LED display Electronic Trip Unit active Alarm ETU fault L tripping operation S tripping operation I tripping operation N tripping operation NSE0_00890 G tripping operation G alarm Tripping operation as a result of extended protection function Communication Signals from signaling switches with external CubicleBUS modules (relays) Overload warning Load shedding, load absorbing Leading signal overload trip 200 ms Temperature alarm Phase unbalance Instantaneous short-circuit trip Short-time delayed short-circuit trip Overload trip Neutral conductor trip NSE0_00891 Ground-fault protection trip Ground-fault alarm Auxiliary relay ETU fault N S I G Delay time figures given in ms. M = Motor protection, corresponds to 20 ms. D = Rotary coding switch D & S = Rotary coding and slide switch K = Communication M/K = Menu/Communication 34 Siemens * 04/2018 Available. -- Not available. Optional. For the setting range of the response current Ig, see page 35. (c) Siemens AG 2018 3WL1 Air Circuit Breakers 3WL1 Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC), IEC General data Protection functions Parameterization by ETU45B D& S ETU76B M/K -0.4-0.45-0.5-0.55-0.6-0.65-0.7-0.8-0.9-1 0.4 ... 1 2-3.5-5.5-8-10-14-17-21-25-30 s 1-2-3-4-5 s At tsd = 20 ms (M) 0.5 ... 1 1.25-1.5-2-2.5-3-4-6-8-10-12 M-100-200-300-400 ms 2 ... 30 s 1 ... 5 s (on/off) 0.2 ... 2 1.25 x In ... 0.8 x Icw M-80 ... 4000 ms 100-200-300-400 ms By CubicleBUS module 1.5-2.2-3-4-6-8-10-12-0.8 x Ics Module can be retrofitted - 100 ... 400 ms By CubicleBUS module 1.5 x In ... 0.8 x Ics Module can be retrofitted A-B-C-D-E A-B-C-D-E A ... E A ... E Function overview of the electronic trip system Overload protection Function can be switched on/off Setting range IR = In x ... Switchable overload protection (I2t- or I4t-dependent function) Setting range for time-lag class tR at I2t Setting range for time-lag class tR at I4t Thermal memory can be switched on/off Phase failure sensitivity N-conductor protection Function can be switched on/off N-conductor setting range IN = In x ... Short-time delayed short-circuit protection Function can be switched on/off Setting range Isd = In x ... Setting range of delay time tsd Switchable short-time delayed short-circuit protection (I2t-dependent function) Setting range of delay time tsd at I2t ZSI function Instantaneous short-circuit protection Function can be switched on/off Setting range Ii = In x ... Ground-fault protection Tripping and alarm functions Tripping function can be switched on/off Alarm function can be switched on/off Detection of the ground-fault current through summation current formation with internal or external N-conductor transformer Detection of ground-fault current through external current transformer Setting range of the response current Ig for tripping Setting range of the response current Ig for alarm Setting range of the delay time tg 100-200-300-400-500 ms Switchable ground-fault characteristic 2 (I t-dependent function) Setting range for delay time tg at I2t 100-200-300-400-500 ms ZSI-G function By CubicleBUS module Parameter set changeover Switchable between parameter set A and B -LCD Alphanumeric LCD (4-line) Graphical LCD (24 V, external power supply required) -Communication CubicleBUS integrated Communications capability via PROFIBUS DP Metering function Metering capability with metering function Plus LED display Electronic Trip Unit active Alarm ETU fault L tripping operation S tripping operation I tripping operation N tripping operation G tripping operation (Only with ground-fault protection module) G alarm (Only with ground-fault protection module) Tripping operation as a result of extended protection functions Communication Signals from signaling switches with external CubicleBUS modules (relays) Overload warning Load shedding, load absorbing Leading signal overload trip 200 ms Temperature alarm Phase unbalance Instantaneous short-circuit trip Short-time delayed short-circuit trip Overload trip Neutral conductor trip Ground-fault protection trip (Only with ground-fault protection module) Ground-fault alarm (Only with ground-fault protection module) Auxiliary relay ETU fault Setting range of the response current Ig Size I and size II Size III A 100 A 400 A B 300 A 600 A C 600 A 800 A D 900 A 1000 A E 1200 A 1200 A 100 ... 500 ms 100 ... 500 ms By CubicleBUS module - (Only with ground-fault protection module) (Only with ground-fault protection module) (Only with ground-fault protection module) (Only with ground-fault protection module) Increment size when settings are made for the ETU76B using the menu From ... to Increment size From ... to Increment size 0 ... 1 0.1 1000 ... 1600 50 1 ... 100 1 1600 ... 10000 100 100 ... 500 5 10000 ... max 1000 500 ... 1000 10 For the legend, see page 34. Siemens * 04/2018 35 (c) Siemens AG 2018 3WL1 Air Circuit Breakers 3WL1 Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC), IEC Configuration aids Characteristic curves2) n 1,25 ... 12 x i R min 100 10 sd min sd max 1,25 ... 12 x n sd max 0 ... 0,4 s 0,1 sd min i i > 20 x n max. 50 kA 0,01 0,1 1 10 100 / n 3WL circuit breaker with ETU27B Electronic Trip Unit, LSIN characteristic curve NSE0_01521 [s] 1000 10000 Opening time Opening time [s] n N n 10000 100 g min R max 0,4 ... 1,0 x 1000 1 3WL circuit breaker with ETU25B Electronic Trip Unit, LSI characteristic curve 10 NSE0_01527 [s] 10000 100 / n 3WL circuit breaker with ETU15B Electronic Trip Unit i > 20 x n max. 50 kA 10 100 / 0,01 1 10 sd min 0,1 0,1 i max n 1 0,1 sd max 0 ... 0,4 s i min 0,01 sd max n 10 0,1 10 sd min 100 2 ... 8 x 100 1 0,5 ... 1,0 x n g max 1000 NSE0_01523a 0,4 ... 1,0 x 1000 R max NSE0_01519 R max 1000 1 Opening time [s] Opening time [s] R min R min NSE0_01520 10000 10000 Opening time Every Electronic Trip Unit type and every setting has its own characteristic curve. Only a selection is shown in the following. The characteristic curves each show the largest and smallest setting range of 3WL circuit breakers with 1000 A rated current at 500 V rated voltage with various trip units. In order to obtain a complete tripping characteristic curve, the relevant parts of the characteristic curves have to be combined. The characteristic curves show the behavior of the Electronic Trip Unit when it is activated by a current that is already flowing before the tripping operation. If the overcurrent tripping occurs immediately after closing and the Electronic Trip Unit is therefore not yet activated, the opening time is extended, depending on the level of the overcurrent by up to 15 ms. To determine the break-times of the circuit breakers, approximately 15 ms must be added to the opening times shown for the arcing time. For tolerances, see legend below. The characteristic curves shown apply to ambient temperatures at the circuit breaker between -5 and +55 C. The trip unit can be operated at ambient temperatures of -20 to +70 C. An extended tolerance band can apply at these temperatures. sd 1,25 ... 12 x n 100 2 sd = const 10 100 ... 1200 A 1) 1 1 g max 0,1 ... 0,5 s 0,1 2 sd g min = const sd = const 0,1 ... 0,4 s 0,1 0,02 ... 0,4 s 0,01 100 1000 10000 0,01 100000 0,1 A 3WL circuit breaker with ETU27B Electronic Trip Unit, G characteristic curve Tolerances for the current settings L: Tripping operations between 1.05 and 1.2 x IR S: -0%, +20% I: -0%, +20% G: -0%, +20% Tolerances for the tripping times L: -20%, +0% for I2t characteristic curve S: -0%, +60 ms or -0%, 10% for tripping times greater than 600 ms I: <50 ms G: -0%, +60 ms or -0%, 10% for tripping times greater than 600 ms 36 Siemens * 04/2018 1 10 100 / n 3WL circuit breaker with ETU45B Electronic Trip Unit, S characteristic curve 1) Sizes I and II: 100 ... 1200 A Size III: 400 ... 1200 A. 2) With a single-pole load in the lowest rated current range, the response times of the short-circuit trip can increase by approx. 10% and the tripping times by approx. 15% with respect to the characteristic curve. (c) Siemens AG 2018 3WL1 Air Circuit Breakers 3WL1 Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC), IEC Configuration aids In order to obtain a complete tripping characteristic curve, the relevant parts of the characteristic curves have to be combined. The characteristic curves show the behavior of the Electronic Trip Unit when it is activated by a current that is already flowing before the tripping operation. If the overcurrent tripping occurs immediately after closing and the Electronic Trip Unit is therefore not yet activated, the opening time is extended, depending on the level of the overcurrent by up to 15 ms. In order to determine the total break-times of the circuit breakers, approximately 15 ms must be added to the opening times shown for the arcing time. 2 g 0,1 ... 0,5 s 0,01 1000 10000 100000 n = const 100 R 2 ... 30s for 1 ... 5s for 10 3WL circuit breaker with ETU45B and ETU76B Electronic Trip Unit, G characteristic curve 10000 1000 NSE0_01526a = const 2 sd 1,25 x 100 n ... 0,8 x cw 10 2 1 2 4 sd 1 0,1 0,1 sd = const = const 0,1 ... 0,4 s 0,02 ... 4 s 0,01 0,1 0,01 0,1 = const 100 ... 1200 A 1) 0,1 Opening time [s] NSE0_01522a 4 R [s] g 10 A 10000 Opening time 100 100 The characteristic curves shown apply to ambient temperatures at the circuit breaker between -5 and +55 C. The trip unit can be operated at ambient temperatures of -20 to +70 C (ETU76B with graphic display up to +55 C). An extended tolerance band can apply at these temperatures. 1000 1000 1 For tolerances, see legend below. 0,4 ... 1,0 x NSE0_01525a 10000 Opening time [s] Every Electronic Trip Unit type and every setting has its own characteristic curve. Only a selection is shown in the following. The characteristic curves each show the largest and smallest setting range of 3WL circuit breakers with 1000 A rated current at 500 V rated voltage with various trip units. 1 10 100 / n 1 10 / n 1 / cw 3WL circuit breaker with ETU76B Electronic Trip Unit, S characteristic curve 3WL circuit breaker with ETU45B and ETU76B Electronic Trip Unit, L characteristic curve NSE0_01524a Opening time [s] 10000 1000 Further characteristic curves are shown in the manual and the planning and configuring tool SIMARIS design, or ask your Siemens contact person. Tolerances for the current settings L: Tripping operations between 1.05 and 1.2 x IR S: -0%, +20% I: -0%, +20% G: -0%, +20% 100 10 Tolerances for the tripping times L: -20%, +0% for I2t characteristic curve S: -0%, +60 ms or -0%, 10% for tripping times greater than 600 ms I: <50 ms G: -0%, +60 ms or -0%, 10% for tripping times greater than 600 ms 1 i 1,5 x 0,1 n ... 0,8 x cs 0,01 0,1 1 10 / n 1 / cs 3WL circuit breaker with ETU45B and ETU76B Electronic Trip Unit, I characteristic curve 1) Sizes I and II: 100 ... 1200 A Size III: 400 ... 1200 A. Siemens * 04/2018 37 (c) Siemens AG 2018 3WL1 Air Circuit Breakers 3WL1 Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC), IEC Configuration aids Dimensional drawings External current transformers for N-conductor without copper connection pieces Voltage transformers for 3WL air circuit breakers + 58 61 62 65 68 71 72 75 78 260 3 8,9 16 8 R 13,1 R 22 87 2 NSE0_01375 55 60 40 22 81 96,8 51 52 Size I, 3WL9111-0AA21-0AA0 12 13 14 125 1 11 11 NSE0_01103 S 18 Size II, 3WL9111-0AA22-0AA0 Size I, 3WL9111-0AA31-0AA0 41 51 88 95 113 170 91 24 54 115 131 65,5 83 55 130 68 51 44 O 13,5 R 27 15 NSE0_01376 External current transformers for N-conductor with copper connection pieces 51 36 70 83 Current transformers for overload protection in the N-conductor 3 Size III, 3WL9111-0AA23-0AA0 NSE0_00606b 51 160 184 50,5 O 13,5 130 68 51 44 NSE0_01377 45 3x10 30 30 R 15 3 31 Size II, 3WL9111-0AA32-0AA0 107 123 161 97 Door cutout with edge protector 170 91 24 Door cutout for operator panel 295 NSE0_00607b 131 Size III, 3WL9111-0AA33-0AA0 30 30 30 3x10 240 340 90 113 52 Inner dimensions with edge protector O 13,5 Door cutout for operator panel using the door sealing frame 170 91 24 130 68 51 44 NSE0_00164c Option with/without door interlocking 314 123 300 40 3 NSE0_00610d R5 R5 2 40 180 140 175 350 O5,5 120 O5,5 65 Dimensions for option with door interlocking 140 160 184 120 O5,5 185 NSE0_00608b 2) Center 3WL circuit breaker operator panel 3) 8 mounting holes for door sealing frame 4) 3 mounting holes for door sealing frame 38 Siemens * 04/2018 11,5 1) Mounting surface 1 12 21 4 40 Dimensions for option with door interlocking (c) Siemens AG 2018 3WL1 Air Circuit Breakers 3WL1 Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC), IEC Configuration aids CubicleBUS modules Breaker Data Adapter (BDA Plus) 3WL9 111-0AT2.-0AA0 3WL9 111-0AT33-0AA0 70 81,9 45,5 38 19 153 NSE0_02085 94 47,5 86 NSE0_02086 6 30 Door cutout for operator panel using IP55 protective cover 400 395 NSE0_01030b NSE0_01029c Protective cover, IP55 4 x R5 435 85 70 68 295-300 72 72 340-350 4 x 5,5 341 Mounting surface for circuit breaker or guide frame 313 17 Breaker installation level Breaker installation level Siemens * 04/2018 148 39 (c) Siemens AG 2018 3WL1 Air Circuit Breakers 3WL1 Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC), IEC Configuration aids Size I, up to 2000 A, fixed-mounted version, 3- and 4-pole Standard version, horizontal connection 21 20 8 14 a 5,5 210 230 40 7 3 139 58 320 410 NSE0_00617k 150 110 20 h 90 90 90 60 55 O13 Vertical connection h b 267,5 60 127,5 30 O13,5 NSE0_00619a NSE0_00618i 3 113,5 128,5 M8 60 90 90 90 55 55 55 55 82 M8 26 d c 60 90 90 90 NSE0_00613c 3 h 6 421 e NSE0_00612i O13,5 h Front connection (single) 47 Front connection (double hole) 47 55 55 55 55 m NSE0_00616c 3 40 82 M8 Siemens * 04/2018 14 c m 40 f 6 421 g NSE0_00615i 40 O13,5 60 90 90 60 90 90 45 NSE0_00614i 90 NSE0_00620a 15 3 15 150 270 300 390 275 123,5 18 327,5 3 17 5 a 4 19 9 76 275 NSE0_00611i 6 127 90 (c) Siemens AG 2018 3WL1 Air Circuit Breakers 3WL1 Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC), IEC Configuration aids Dimensions in mm Item number Dimensions & Grooves (4 mm wide, 5 mm deep) for supporting phase partitions in the system ( * SIGUT screw terminals 437 ) * Screwless connections 440 * COM15/COM16 462 * Dimension to inside surface of the closed cabinet door 106 + Fixing points for mounting the circuit breaker in the system (grid dimensions in mm) 4 x M8 screw nut (150) and 4 x 9 (110) Auxiliary connector with: , "Safe OFF" locking device 33.5 - Key operation 60.5 2 Space for cable harness to electrical auxiliary circuit connections 20 Z suffix or breaking capacity X Standard A05, A16 or DC 3 Maximum device height 462 462 5 Mounting space for removal of the arc chutes 541 591 6 Top edge of arc chutes 401 451 789 Safety clearances See below Connection dimensions in mm Max. rated circuit breaker current * 1000 A AC, breaking capacity N and S only * 1250 - 2000 A AC or breaking capacity H or 2000 A DC a 10 15 b 10 15 Busbar thickness c 10 15 d 11 6 Clearance e 451 461 Clearance f 34 39 Overhang g 541 551 Clearance h 35 l 80 Terminal face length Safety clearances in mm SZ I, fixed-mounted version ... from grounded or non-conductive parts ... from live parts Above 71) At rear Above 7 At side 8 At rear 9 Above 7 At side Operational voltage, breaking capacity Standard arc chutes - 401 mm IT system 500 V AC, N/S 460 0 0 615 20 20 550 500 V AC, H 460 0 0 715 20 20 550 690 V AC, N/S 460 0 0 765 50 125 -- 690 V AC, H 460 0 0 965 75 140 -- Operational voltage, breaking capacity High arc chutes - 451 mm (A05, A16 or DC) 690 V AC 515 0 0 965 75 140 5503) 690 V AC + 20% H 515 0 0 1015 100 140 -- 1000 V AC, H 515 0 0 1015 100 140 -- 1000 V DC 550 0 0 2) 2) 2) -- 1) Values for struts, grids and perforated sheets. When using plates with conductive surfaces: values on request. 2) With insulating shield; for clearance, see "non-conductive parts" 3) Ue = 1000 V with breaking capacity H and Z option Z = A05 Siemens * 04/2018 41 (c) Siemens AG 2018 3WL1 Air Circuit Breakers 3WL1 Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC), IEC Configuration aids Size I, up to 2000 A, withdrawable version, 3- and 4-pole Standard version, horizontal connection 320 270 20 NSE0_00624h 382,5 367,5 327 12 350 260 14 NSE0_00630i 21 3 275 150 15 4 O1 69 123,5 10 31 40 30 55 13 210 300 10 327,5 5 287 a 16 a 4 3 19 76 275 NSE0_00621k 27 42 220 10 55 90 90 90 15 45 10 6 11 12 13 ,5 13 O NSE0_00627 j 55 55 55 55 68 25 139 270 320 410 Vertical connection 350 260 287 69 55 40 c 169,5 10 15 90 90 90 69 287 373 m 90 6 h 90 350 260 55 55 NSE0_00626h 69 Siemens * 04/2018 90 55 m NSE0_00625h h 287 373 26 11 42 15 13,5 62,5 NSE0_00623b NSE0_00622a 403 55 13,5 10 90 90 90 15 14 55 350 260 55 55 3 169,5 10 Front connection (double hole) 62,5 c NSE0_00628i 267,5 127,5 30 287 l Front connection (single) 6 150 165 O13,5 90 90 90 15 493 10 3 34 121 3 69 282,5 142,5 26 l 33 12 60 NSE0_00632i NSE0_00631i 55 55 55 55 M 350 260 b j 40 14 NSE0_00629i Flat terminals (c) Siemens AG 2018 3WL1 Air Circuit Breakers 3WL1 Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC), IEC Configuration aids Dimensions in mm Item number Dimensions Z suffix or breaking capacity X Standard A05, A16 or DC & Grooves (4 mm wide, 5 mm deep) for supporting phase partitions in the system ( * SIGUT screw terminals (one-part) 465 (446) 515 (496) ) * Screwless connections 468 518 * Dimension to inside surface of the closed cabinet door 58.0 . Fixing holes 9 / Circuit breaker in connected position 88.5 0 Circuit breaker in test position 121.5 1 Circuit breaker in disconnected position 140.5 2 Space for cable harness to electrical auxiliary circuit connections 20 3 Maximum device height 468 518 4 Guide frame upper edge 460 510 789 Safety clearances See below Auxiliary connector with: Connection dimensions in mm Max. rated circuit breaker current * Up to 1000 A AC, breaking capacity N and S only * 1250 - 2000 A AC or breaking capacity H a 10 15 b 10 15 Busbar thickness c 10 15 d 11 6 Clearance e 403 413 Clearance f 34 39 Overhang g 493 503 Clearance h 35 j 38 l 59 m 80 Terminal face length Safety clearances in mm SZ I, withdrawable versions ... from grounded or non-conductive parts ... from live parts Above 7 At side At rear Above 7 At side 8 At rear 9 IT system Above 7 Arc chute covers Without1) / with Without/with Without/with Without/with Without/with Without/with Without Operational voltage, breaking capacity Standard arc chutes - 4 = 460 mm 500 V AC, N/S 460 / 460 0 / 402) 0/0 615 / 480 20 / 100 20 / 14 550 500 V AC, H 460 / 460 0 / 402) 0/0 715 / 480 50 / 50 20 / 14 550 690 V AC, N/S 460 / 460 0 / 402) 0/0 765 / 480 50 / 100 125 / 14 -- 690 V AC, H 460 / 460 0 / 402) 0/0 965 / 480 75 / 225 140 / 14 -- Operational voltage, breaking capacity High arc chutes - 4 = 510 mm (A05, A16 or DC) 690 V AC, H 510 / -- 0 / -- 0 / -- 965 / -- 75 / -- 140 / -- 5503) 690 V AC + 20% H 510 / -- 0 / -- 0 / -- 1015 / -- 100 / -- 140 / -- -- 1000 V AC 510 / -- 0 / -- 0 / -- 1015 / -- 100 / -- 140 / -- -- 1) Values for struts, grids and perforated sheets. When using plates with conductive surfaces: values on request. 2) Value for plates that cover the lateral openings in the guide frame, 0 mm for struts and grids 3) Ue = 1000 V with breaking capacity H and Z option Z = A05 Siemens * 04/2018 43 (c) Siemens AG 2018 3WL1 Air Circuit Breakers 3WL1 Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC), IEC Configuration aids Size II, up to 4000 A, fixed-mounted version, 3- and 4-pole Standard version, horizontal connection 14 NSE0_00633b 20 19 a NSE0_00642 270 440 570 130 90 30 90 30 139 460 590 128 a Vertical connection 3200 A AC and 4000 A DC 30 NSE0_00640c 100 90 40 130 130 130 142 162 h 90 3 h 421 90 90 NSE0_00635e 3,5 NSE0_00634e e c 82 M8 90 26 d NSE0_01868a NSE0_00641b 90 O1 130 130 130 Front connection (double hole) 90 O1 3,5 40 90 90 90 m NSE0_00638d 421 3 M8 14 82 m 40 f 6 NSE0_00637e 40 47 g O 13,5 10 20 k M8 Front connection (single) 44 30 30 290 134,5 98 30 h 6 130 85 Nm 3 47 130 Vertical connection 4000 A AC (terminal face length k = 40 mm) b O13,5 113 128 130 7 7 345,5 79,5 110 90 21 3 3 c 6 127 NSE0_00639k 150 40 ,5 20 10 3 h 130 13 O 130 85 45 150 210 230 NSE0_00636f 15 5,5 76 123,5 150 5 4 3 275 275 18 327,5 17 90 Siemens * 04/2018 130 130 130 M8 200 130 200 (c) Siemens AG 2018 3WL1 Air Circuit Breakers 3WL1 Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC), IEC Configuration aids Dimensions in mm Item number Dimensions & Grooves (4 mm wide, 5 mm deep) for supporting phase partitions in the system ( * SIGUT screw terminals 437 ) * Screwless connections 440 * COM15/COM16 462 * Dimension to inside surface of the closed cabinet door 106 + Fixing points for mounting the circuit breaker in the system (grid dimensions in mm) 4 x M8 screw nut (150) and 4 x 9 (110) 2 Space for cable harness to electrical auxiliary circuit connections Auxiliary connector with: 20 Ue, Z suffix or breaking capacity X Standard DC: 600 V A05, A15 or C DC: > 600 V 3 Maximum device height 462 462 5 Mounting space for removal of the arc chutes 541 591 6 Top edge of arc chutes 401 451 789 Safety clearances See below Connection dimensions in mm Max. rated circuit breaker current * Up to 2000 A AC * Up to 2000 A DC * 25004)A AC * 3200 A AC/4000 A DC a 10 10 15 30 b 15 15 15 30 Busbar thickness c 10 10 20 20 d 11 11 6 6 Clearance e 451 451 461 461 Clearance f 34 34 39 39 Overhang g 541 541 551 551 Clearance h 35 m 80 Terminal face length -- Safety clearances in mm SZ II, fixed-mounted version ... from grounded or non-conductive parts ... from live parts Above1) 7 At rear Above 7 At side 8 At rear 9 Above 7 At side Operational voltage Standard arc chutes - 401 mm IT system 500 V AC 460 0 0 715 50 20 550 690 V AC 460 0 0 1065 100 140 -- 300 V DC 495 0 0 2) 2) 2) -- 600 V DC 650 0 0 2) 2) 2) -- Operational voltage, breaking capacity High arc chutes - 451 mm (A05, A16 or DC) 690 V AC, H 510 0 0 1015 100 140 6003) 690 V AC, C 510 0 0 775 100 125 -- 690 V AC + 20% H 620 0 0 1015 100 125 -- 1000 V AC, H 620 0 0 1015 100 125 -- 1150 V AC 620 0 0 2) 2) 2) -- 1000 V DC 615 0 0 2) 2) 2) -- 3WL52 Double high arc chutes - 501 mm (A17) 1) Values for struts, grids and perforated sheets. When using plates with conductive surfaces: values on request. 2) With insulating shield; for clearance, see "non-conductive parts" 3) Ue = 1000 V with breaking capacity H and Z option Z = A05 4) Does not apply to 3WL5: 3WL5 see dimensions 3200 A AC Siemens * 04/2018 45 (c) Siemens AG 2018 3WL1 Air Circuit Breakers 3WL1 Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC), IEC Configuration aids Size II, up to 4000 A, withdrawable version, 3- and 4-pole Standard version, horizontal connection 382,5 367,5 327 NSE0_00646f 90 530 400 90 90 5545 130 130 20 14 90 9 40 10 270 350 480 O13,5 327,5 3 27 42 10 220 69 40 31 O14 45 10 130 10 55 21 30 NSE0_00649b j 30 a 275 150 5 123,5 4 76 275 a 287 NSE0_00652c NSE0_00643c 139 270 460 590 138 95 Vertical connection 3200 A AC and 4000 A DC Vertical connection 4000 A AC (terminal face length k = 40 mm) 100 10 k 69 5545 130 130 4,6 10 177 197 130 55 130 12 287 59 33 10 Siemens * 04/2018 59 3 69 282,5 142,5 26 46 400 40 45 130 130 130 m f c 169,5 130 NSE0_00654c NSE0_00653a 90 m 14 130 Flat terminals M 90 3 6 10 10 40 45,1 130 55 69 h d 10 40 530 400 90 90 40 55 45 130 130 130 287 g 373 NSE0_00645d 3 287 h NSE0_00647c 13,5 26 e 62,5 40 90 NSE0_00648d NSE0_00644c 40 40 O13,5 62,5 90 90 373 400 90 90 121 200 130 Front connection (double hole) 530 c 169,5 45 200 Front connection (single) 6 10 20 69 157 172 109,5 NSE0_00651b 287 3 NSE0_01869 315,5 30 NSE0_00650c b 290 135 100 30 30 j 30 530 400 (c) Siemens AG 2018 3WL1 Air Circuit Breakers 3WL1 Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC), IEC Configuration aids Dimensions in mm Item number Dimensions Ue, Z suffix or breaking capacity X Standard DC: 600 V A05, A15 or C DC: > 600 V & Grooves (4 mm wide, 5 mm deep) for supporting phase partitions in the system Auxiliary connector with: ( * SIGUT screw terminals (one-part) 465 (446) 515 (496) ) * Screwless connections 468 518 * Dimension to inside surface of the closed cabinet door 58.0 . Fixing holes 9 / Circuit breaker in connected position 88.5 0 Circuit breaker in test position 121.5 1 Circuit breaker in disconnected position 140.5 2 Space for cable harness to electrical auxiliary circuit connections 20 3 Maximum device height 468 518 4 Guide frame upper edge 460 510 789 Safety clearances See below Connection dimensions in mm Max. rated circuit breaker current * Up to 2000 A AC/2000 A DC * 2500 A AC * 3200 A AC/4000 A DC a 10 15 30 b 10 15 30 Busbar thickness c 10 20 20 d 11 6 6 Clearance e 403 413 413 Clearance f 34 39 39 Overhang g 493 503 503 Clearance h 35 j 38 -- m 80 -- Terminal face length Safety clearances in mm SZ II, withdrawable version ... from grounded or non-conductive parts ... from live parts Above 7 Above 7 At side At rear IT system At side 8 At rear 9 Above 7 Without/with Without/with Without Arc chute covers Without1) / with Without/with Operational voltage Standard arc chutes - 4 = 460 mm 500 V AC 460 / 460 0 / 702) 0/0 715 / 480 50 / 50 14 / 14 550 690 V AC 460 / 460 0 / 702) 0/0 1065 / 480 100 / 225 30 / 14 -- 300 V DC 495 / -- 0 / -- 0 / -- 3) 3) 3) -- 600 V DC 650 / -- 0 / -- 0 / -- 3) 3) 3) -6004) Without/with Without/with Operational voltage, breaking capacity High arc chutes - 4 = 510 mm (A05, A16 or DC) 690 V AC, H 510 / -- 0 / -- 0 / -- 1015 / -- 105 / -- 30 / -- 690 V AC, C 510 / -- 0 / -- 0 / -- 775 / -- 100 / -- 30 / -- 690 V AC + 20% H 620 / -- 0 / -- 0 / -- 1015 / -- 100 / -- 140 / -- -- 1000 V AC, H 620 / -- 0 / -- 0 / -- 1015 / -- 100 / -- 140 / -- -- 1150 V AC 620 / -- 0 / -- 0 / -- 3) 3) 3) -- 1000 V DC 615 / -- 0 / -- 0 / -- 3) 3) 3) -- 1) Values for struts, grids and perforated sheets. When using plates with conductive surfaces: values on request. 2) Value for plates that cover the lateral openings in the guide frame, 0 mm for struts and grids 3) With insulating shield; for clearance, see "non-conductive parts" 4) Ue = 1000 V with breaking capacity H and Z option Z = A05 Siemens * 04/2018 47 (c) Siemens AG 2018 3WL1 Air Circuit Breakers 3WL1 Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC), IEC Configuration aids Size III, up to 6300 A, fixed-mounted version, 3- and 4-pole Standard version, horizontal connection 21 14 12 35 210 15 210 210 160 130 h 30 5,5 150 210 230 NSE0_00658h 890 O13,5 7 7 3 110 (150) 4x O11 20 NSE0_00661j 139 704 4x M10 248 914 Vertical connection (terminal face length k = 40 mm) 10 107 3 NSE0_00663a k NSE0_00662c 330,5 94,5 120 15 30 10 85 O14 142 162 210 210 210 M10 Front connection (single) O1 3,5 160 160 160 NSE0_00657d 421 3 20 82 M10 130 26 11 h 6 160 5050 h NSE0_00656d 451 47 210 210 210 Front connection (double hole) 47 160 5050 O13 160 160 160 m NSE0_00660d 421 NSE0_00659e 6 3 48 M10 14 20 82 m 40 34 541 40 ,5 130 Siemens * 04/2018 210 210 210 45 127 15 3 NSE00664a 205 76 270 680 3 18 275 150 30 17 327,5 19 5 123,5 4 20 30 275 NSE0_00655c 130 6 210 210 210 130 (c) Siemens AG 2018 3WL1 Air Circuit Breakers 3WL1 Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC), IEC Configuration aids Dimensions in mm Item number Dimensions & Grooves (4 mm wide, 5 mm deep) for supporting phase partitions in the system ( * SIGUT screw terminals 437 ) * Screwless connections 440 * COM15/COM16 462 * Dimension to inside surface of the closed cabinet door 106 + Fixing points for mounting the circuit breaker in the system (grid dimensions in mm) 4 x M10 screw nut (150) and 4 x 11 (110) 2 Space for cable harness to electrical auxiliary circuit connections Auxiliary connector with: 20 Ue, Z suffix or breaking capacity X 690 V AC, H > 690 V AC, A05, or C 3 Maximum device height 462 462 5 Mounting space for removal of the arc chutes 541 591 6 Top edge of arc chutes 401 451 789 Safety clearances See below Connection dimensions in mm h 35 k 40 m 80 Terminal face length Safety clearances in mm SZ III, fixed-mounted version ... from grounded or non-conductive parts Above1) 7 At side ... from live parts IT system At rear Above 7 At side 8 At rear 9 Above 7 Operational voltage Standard arc chutes - 401 mm 500 V AC 460 0 0 515 20 20 450 690 V AC 460 0 0 965 100 125 -- Operational voltage High arc chutes - 451 mm (> 690 V AC, A05 or C) 690 V AC 510 0 0 965 100 125 5002) 690 V AC + 10% H 615 0 0 865 100 125 -- 690 V AC + 20% H 615 0 0 865 100 125 -- 1000 V AC 615 0 0 865 100 125 -- 1150 V AC 615 0 0 3) 3) 3) -- 1) Values for struts, grids and perforated sheets. When using plates with conductive surfaces: values on request. 2) Ue = 1000 V with breaking capacity H and Z option Z = A05 or breaking capacity C 3) With insulating shield; for clearance, see "non-conductive parts" Siemens * 04/2018 49 (c) Siemens AG 2018 3WL1 Air Circuit Breakers 3WL1 Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC), IEC Configuration aids Size III, up to 6300 A, withdrawable version, 3- and 4-pole Standard version, horizontal connection 382,5 367,5 327 NSE0_00668_h 14 20 5 840 NSE0_00665c 10 160 160 287 10 76 69 27 42 45 220 57 85 210 210 210 57 800 160 NSE0_00674h 30 275 150 O14 40 31 270 590 10 123,5 465,5 275 468,5 630 160 160 9 327,5 30 4 21 O13 30 30 30 j ,5 NSE0_00671h 139 270 704 260 217 914 Vertical connection, up to 6300 A Flange connection, up to 4000 A 840 630 704 160 57 a b b 10 210 121 10 590 l 287 69 l 282,5 142,5 26 NSE0_00673h 5 57 85 10 30 210 210 800 914 704 914 Front connection (double hole) 11 50 85 26 10 57 Siemens * 04/2018 210 210 590 800 210 160 50 50 160 160 287 m 373 14 493 6 m 34 287 h 69 6 20 169,5 40 O13,5 62,5 h 373 403 NSE0_00666c 160 20 169,5 10 40 160 630 160 50 50 NSE0_00669c 13,5 160 50 50 840 NSE0_00667d 840 630 160 50 50 85 210 590 210 800 210 69 Front connection (single) 62,5 210 590 800 NSE0_00670d 24 177 197 160 160 33 NSE0_00675b NSE0_00672c 330,5 94,5 124,5 30 O14 160 12 j M 10 20 NSE0_00676c 840 630 (c) Siemens AG 2018 3WL1 Air Circuit Breakers 3WL1 Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC), IEC Configuration aids Dimensions in mm Item number Dimensions Ue, Z suffix or breaking capacity X 690 V AC, H > 690 V AC, A05, or C & Grooves (4 mm wide, 5 mm deep) for supporting phase partitions in the system ( * SIGUT screw terminals (one-part) 465 (446) 515 (496) ) * Screwless connections 468 518 * Dimension to inside surface of the closed cabinet door 58.0 . Fixing holes 9 / Circuit breaker in connected position 88.5 0 Circuit breaker in test position 121.5 1 Circuit breaker in disconnected position 140.5 2 Space for cable harness to electrical auxiliary circuit connections 20 3 Maximum device height 468 518 4 Guide frame upper edge 460 510 789 Safety clearances See below Auxiliary connector with: Connection dimensions in mm Max. rated circuit breaker current * Up to 4000 A AC * 5000 V AC * 6300 V AC a 40 40 5 b 210 210 245 h 35 -- -- j 38 l 59 -- -- m 80 -- -- Clearances Terminal face length Safety clearances in mm SZ III, withdrawable version ... from grounded or non-conductive parts ... from live parts Above 7 Above 7 At side At rear IT system At side 8 At rear 9 Above 7 Without/with Without/with Without Arc chute covers Without1) / with Without/with Operational voltage Standard arc chutes - 4 = 460 mm 500 V AC 460 / 460 0 / 402) 0/0 510 / 480 20 / 50 14 / 14 460 690 V AC 460 / 460 0 / 402) 0/0 965 / 480 100 / 200 14 / 14 -- Without/with Without/with Operational voltage, breaking capacity High arc chutes - 4 = 510 mm (> 690 V AC, A05, A16 or C) 690 V AC 510 / -- 0 / -- 0 / -- 965 / -- 100 / -- 14 / -- 5103) 1000 V AC, H 615 / -- 0 / -- 0 / -- 865 / -- 100 / -- 14 / -- -- 1000 V AC, C 615 / -- 0 / -- 0 / -- 865 / -- 100 / -- 14 / -- -- 1150 V AC 615 / -- 0 / -- 0 / -- 4) 4) 4) -- 1) Values for struts, grids and perforated sheets. When using plates with conductive surfaces: values on request. 2) Value for plates that cover the lateral openings in the guide frame, 0 mm for struts and grids 3) Ue = 1000 V with breaking capacity H and Z option Z = A05 or breaking capacity C 4) With insulating shield; for clearance, see "non-conductive parts" Siemens * 04/2018 51 (c) Siemens AG 2018 3WL1 Air Circuit Breakers 3WL1 Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC), IEC Configuration aids Circuit diagrams Terminal assignment diagram optional Accessories (Auxiliary switch S1, S2 = Standard) Internal wiring Terminals External wiring L / L+ U /U s c N / L- e.g. current transformer in the star point of power transformer or a summation current transformer 1200 A /1A 14 Remote reset solenoid F7 12 11 10 Jumper if no N transformer 9 8 N 7 L3 6 L2 L1 5 4 24 V DC input 3 Termination resistor, if no external CB module! 2 8 7 Signaling switch on 1st auxiliary release S22 6 5 4 3 Signaling switch on 2nd auxiliary release S23 2 1 2 3 4 5 6 7 8 9 9 2nd tripped signaling switch S25 1NO COM15/COM16 (Option F02/F12) L / L+ Us/Uc Tripped signaling switch (optional) Internal 10 Electrical ON button S10 External 11 Stored energy status indication S21 Y1 12 Close - + 13 Free - + 14 DPWrite Free Enable 1st tripped signaling switch (RESET position) S24 Open - + OUT F1, 2 1 IN Not available with communication connection "F02" or "F12". COM15/COM16 module is at position "-X7". 13 G transformer S2 G transformer S1 N transformer S2 N transformer S1 ext. voltage transformer Com ext. voltage transformer L3 ext. voltage transformer L2 ext. voltage transformer L1 0 V DC 24 V DC CubicleBUS + CubicleBUS - 1 L / L+ Uc N / L- 14 1st auxiliary release F1 "ST" 13 12 S1 "NO" 11 10 S1 "NC" 9 Closing coil N / L- Uc L / L+ 8 7 6 5 "Ready to close" signal S20 4 S2 "NO" 3 2 S2 "NC" 1 F4 only "quick OFF" F4 only "quick OFF" 2nd auxiliary release: F2 "ST", F3 "UVR", F4 "UVR td" 14 EMERGENCY STOP or jumper L / L+ Uc N / L- 13 12 11 10 S3 "NO" or S7 "NO" 9 8 S3 "NC" or S7 "NO" 7 6 S4 "NO" or S8 "NO" 5 4 S4 "NC" or S8 "NO" Charging motor opt. motor main switch S12 (sw) M (br) 3 L / L+ Uc N / L- 2 1 NSE0_00605r 52 Siemens * 04/2018 (c) Siemens AG 2018 3WL1 Air Circuit Breakers 3WL1 Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC), IEC Configuration aids Example of an overall circuit diagram for 3WL circuit breakers (3WL1. ..-.....-4GN4-Z C11+ C22 + K07) Manual / motorized operating mechanism with stored-energy feature, with electrical ON button (option C11), with ready-toclose signaling switch (option C22), with Electronic Trip Unit L1 (L+) release contact LSING with undervoltage release "UVR" (F3), with shunt trip "ST" (F1), with tripped signaling switch (option K07), with auxiliary switch 4 NO + 4 NC. L1 (L+) OFF -X5.6 -X5.4 -X5.10 -X5.8 -X6.4 -X6.2 -X6.12 -X6.10 ETU L TRIP electr. ON version S RESET -S10 -A1 5 1 3 -X6.6 -X7.12 -X7.14 -X5.12 -X6.14 -X6.7 -X7.9 -X5.2 ON I N N G R -S11 -S24 -S20 -F5 -S2 -S1 -Q1 P QS -S4 -S3 -T1 M -T2 NSE0_01558b -T3 -S12 -X5.5 -X5.3 -X5.9 -X5.7 -X6.3 -X6.1 -X6.9 -X6.11 6 2 4 -X8.9 N (L-) -X8.10 -X7.13 -X6.5 * -X5.11 -X6.13 -F1 -X6.8 -X5.1 N (L-) U< -Y1 mech. ON mech. OFF -F3 * Short terminals, if no N transformer Function diagram of 3WL air circuit breaker -A1 -S1/-S2 -S3/-S4 -S7 (optional) F1 F2 S20 F3 -S8 (optional) F4 M1 Q1 P 1 -S10 -S11 -S12 Y1 A1 2 T1 T2 T3 T4 3 NSE0_01559e 3WL1. ..-.....-...2 3WL1. ..-.....-...4 3WL1. ..-.....-...7 3WL1. ..-.....-...8 S1 & S2 S3 & S4 S24 S25 F5 L S I N N G ETU Electronic Trip Unit 1st auxiliary switch block (2 NO + 2 NC) 2nd auxiliary switch block (2 NO + 2 NC) 2nd auxiliary switch block, S7 (2 NO) can be used if there is no S3 - S3 and S7 have the same terminal assignment/mounting location 2nd auxiliary switch block, S8 (2 NO) can be used if there is no S4 - S4 and S8 have the same terminal assignment/mounting location (2 NO + 2 NC) S1+S2 (4 NO + 4 NC) S1+S2+S3+S4 (6 NO + 2 NC) S1+S2+S7+S8 (5 NO + 3 NC) S1+S2+S3+S8 -S20 -S24 Electrical ON button Internal motor shutdown switch (if spring is tensioned) Motor shutdown switch (no automatic tensioning of spring) Ready-to-close signaling switch Tripped signaling switch -F1 -F3 -F5 1st auxiliary release, shunt release 2nd auxiliary release, undervoltage release Tripping solenoid -M -P -QS -Q1 -T1/-T2/-T3 -X5/-X6/-X7/-X8 -Y1 -R Motor for "charging energy store" Spring energy store Actuator lever for "charging energy store" Main contacts Current transformers Terminals Closing coil Display and reset button for Electronic Trip Unit -X8.9/-X8.10 Connection option: external N transformer Siemens * 04/2018 53 (c) Siemens AG 2018 3WL1 Air Circuit Breakers 3WL1 Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC), IEC Configuration aids Example of the mode of operation of Zone Selective Interlocking function in power distribution 5 6 1 2 3 4 ZSI module ZSI module SENTRON 3WL 3 4 5 6 ZSI module SENTRON 3WL 3 4 5 6 SENTRON 3WL SENTRON 3WL ZSI module SENTRON 3VL NSE0_01898 3 4 5 6 Circuit diagram for a Zone Selective Interlocking function with multiple infeed and several outgoing units with 3WL circuit breakers NSE0_01897 ZSI module SENTRON 3WL 3 4 5 6 SENTRON 3WL 3 4 5 6 ZSI module SENTRON 3WL 3 4 5 6 ZSI module SENTRON 3WL 3 4 5 6 ZSI module ZSI module SENTRON 3WL 3 4 5 6 3VL and 3WL circuit breakers used in various staggered levels ZSI module SENTRON 3WL 3 4 5 6 ZSI module 5 6 1 2 3 4 ZSI module SENTRON 3WL 3 4 5 6 NSE0_01899 SENTRON 3WL SENTRON 3WL 3 4 5 6 ZSI module ZSI module SENTRON 3WL 3 4 5 6 ZSI function: Connection using a tie-breaker, use of 3WL circuit breakers More information Up-to-date information on the Internet at: http://www.siemens.com/sentron 54 Siemens * 04/2018 (c) Siemens AG 2018 3WL1 Air Circuit Breakers 3WL1 Non-Automatic Air Circuit Breakers up to 4000 A (DC) General data Technical specifications Size I II 3WL11 20 3WL12 10 Type Rated current In at 40 C Main conductor A 2000 3WL12 20 3WL12 40 ... 1000 2000 4000 Rated operational voltage Ue (1000 V version, see Catalog LV 10, order code "A05") V DC 1000 ... 600/1000 ... 600/1000 ... 600/1000 Rated insulation voltage Ui V DC 1000 1000 1000 1000 kV 12 kV 4 kV 2.5 12 4 2.5 12 4 2.5 12 4 2.5 Yes B Yes Yes C -25/+70 C -40/+70 A 2000 A 1910 A 1850 A 1710 -25/+70 -40/+70 -25/+70 -40/+70 -25/+70 -40/+70 1000 1000 1000 1000 2000 2000 2000 1950 4000 3640 3500 3250 W 150 280 770 1640 35 34 35 34 35 34 * Electrical make time (through activation solenoid)1) * Electrical opening time (through shunt release) ms 35 ms 38 ms 100 ms 73 100 73 100 73 100 73 * Electrical opening time (instantaneous undervoltage release) ms 73 73 73 73 Yes Isolating function acc. to EN 60947-2 Utilization category Permissible ambient temperature * Operation * Storage Permissible load At rear horizontal main circuit connections (Cu painted black) Up to 40 C Up to 55 C Up to 60 C Up to 70 C Power loss at In for symmetrical loads Withdrawable circuit breakers Switching times * Make time * Opening time Endurance3) * Mechanical (without maintenance) * Mechanical (with maintenance)2) * Electrical (without maintenance) * 1000 V version * Electrical (with maintenance)2) Operating cycles 10 000 Operating cycles 15 000 Operating cycles 1000 Operating cycles 1000 Operating cycles 2000 Switching frequency * 600 V version * 1000 V version 1/h -1/h 20 10000 15000 6000 1000 15000 10000 15000 6000 1000 15000 10000 15000 4000 1000 15000 60 20 60 20 60 20 30 30 30 30 Mounting position Dhmax. = 1 mm Rated impulse withstand voltage Uimp * Main conducting paths * Auxiliary circuits * Control circuits and/or NSE0_00061a NSE0_00062a NSE0_00927 IP20 without cabinet door, IP41 with door sealing frame, IP55 with cover Degree of protection Standard connection = strain-relief clamp * Without end sleeve * With end sleeve acc. to DIN 46228 Part 2 * With twin end sleeve 2 x 0.5 mm2 (AWG 20) ... 2 x 1.5 mm2 (AWG 16); 1 x 2.5 mm2 (AWG 14) 1 x 0.5 mm2 (AWG 20) ... 1 x 1.5 mm2 (AWG 16) 2 x 0.5 mm2 (AWG 20) ... 2 x 1.5 mm2 (AWG 16) Optional connection = tension spring * Without end sleeve * With end sleeve acc. to DIN 46228 Part 2 2 x 0.5 mm2 (AWG 20) ... 2 x 2.5 mm2 (AWG 14) 2 x 0.5 mm2 (AWG 20) ... 2 x 1.5 mm2 (AWG 16) Weights 3-pole * Fixed-mounted circuit breakers * Withdrawable circuit breakers * Guide frames kg 43 kg -kg -- 56 60 31 56 60 31 64 68 45 4-pole * Fixed-mounted circuit breakers * Withdrawable circuit breakers * Guide frames kg 50 kg -kg -- 67 72 37 67 72 37 77 82 54 Auxiliary conductors (Cu) Max. number Auxiliary conductors x cross-section (solid/stranded) 1) 2) Make time through activation solenoid for synchronization purposes (short-time excited) 50 ms. Maintenance means: Replace main contact elements and arc chutes (see Operating Manual). 3) Further technical specifications on request. Size I II Type 3WL11 3WL12 Breaking capacity DC DC kA kA kA kA 20 20 20 20 35 30 25 20 kA kA kA kA -20 --- -351)/302)/253)/204) --- Rated short-circuit breaking capacity Up to 220 V DC Up to 300 V DC Up to 600 V DC Up to 1000 V DC Icc Icc Icc Icc Rated short-time withstand current Icw 0.5 s 1s 2s 3s 1) 2) At Ue = 220 V DC At Ue = 300 V DC 3) 4) At Ue = 600 V DC At Ue = 1000 V DC Siemens * 04/2018 55 (c) Siemens AG 2018 3WL1 Air Circuit Breakers 3WL1 Non-Automatic Air Circuit Breakers up to 4000 A (DC) Configuration aids Characteristic curves [s] 10000 R= 0.4 ... 1.0 n 2 ... 10 s at 6 = 1.25 R ... 4 R= 1000 R = 0.4 R n = 1.0 n I R= B 100 B A R n 10 s [B] 2 s [A] A 10 1 0,01 0,1 I= R 1.5 R MAX 4 n I= NSE0_01578 MIN 1.25 I= 0,1 1 10 / n DIGmat S100 characteristic curve Dimensional drawings DIGmat S100 DIGmat S100 DIGmat S100 drilling pattern Note: For dimensional drawings for non-automatic circuit breakers up to 4000 A (DC), see page 38 to 47. 56 Siemens * 04/2018 (c) Siemens AG 2018 3WL1 Air Circuit Breakers 3WL1 Non-Automatic Air Circuit Breakers up to 4000 A (DC) Configuration aids Circuit diagrams L1 AC230 N PE + DC24 AC230 X1.2 X1.1 X5.2 X5.1 DIGmat S100 Auxiliary power Emergency STOP" + X4.i1+ DC24 X4.i1- X2.1 + Digital input + Shunt (60mV) - X2.3 - X4.i2+ X4.i2Automatic RESET" Digital output X4.01 X4.01 X4.02 X4.02 X4.03 X4.03 X4.04 X4.04 + - + - + - + - -K1 14 -Q01 11 Automatic / Reset NSE0_01577a Excitation / Alarm 12 12 -K2 14 11 1 3 5 -X6.14 -X5.12 SENTRON 3WL -F1 -F3 -X6.13 -X5.11 -Q01 2 4 6 Circuit diagrams of the DIGmat S100 and the 3WL non-automatic air circuit breaker Application examples of size 2 - non-automatic circuit breakers (DC) Rated operational voltage Required series-connected contact gaps at rated voltage For 3-pole non-automatic air circuit breakers For 4-pole non-automatic air circuit breakers (operational currents up to 4000 A/conducting path) (operational currents up to 4000 A/conducting path) Up to 300 V + 10% NSS0_00539 1-pole, 2-pole 2 parallel conducting paths, only with grounded system 1-pole, 3 parallel conducting paths, only with grounded system 2-pole 2 parallel conducting paths 2-pole, only with grounded system 1-pole, 2 parallel conducting paths, only with grounded system 2-pole 1-pole, only with grounded system 2-pole, only with grounded system 1-pole, only with grounded system Over 300 V + 10% Up to 600 V + 10% Over 600 V + 10% Up to 1000 V + 10% (version for 1000 V required, order with "-Z" and code A05) The connection to the circuit breakers is not dependent on direction and polarity; the circuit diagrams can be adapted accordingly. of 1 m from the connecting bars, the circuit breaker can be used at full operational current load. ] Grounded system If the parallel or series connections are made directly to the connecting bars, for thermal reasons the continuous load on the circuit breakers must only be 80% of the permissible operational current. If the parallel or series connection is made at a distance Load Siemens * 04/2018 57 (c) Siemens AG 2018 3WL1 Air Circuit Breakers 3WL1 Non-Automatic Air Circuit Breakers up to 4000 A (DC) Configuration aids Application examples of size 1 - non-automatic circuit breakers (DC) Permissible interconnections Circuit diagrams for size 1 1000 V DC non-automatic air circuit breakers Non-grounded system + (-) - (+) Grounded system + (-) - (+) Ground Load *B,B;;B Load More information Up-to-date information on the Internet at: www.siemens.com/sentron 58 Siemens * 04/2018 (c) Siemens AG 2018 (c) Siemens AG 2018 Siemens AG Energy Management Low Voltage & Products Postfach 10 09 53 93009 REGENSBURG GERMANY www.siemens.com/lowvoltage Subject to change without prior notice PDF (3ZW1012-3WL11-0AC1) PH 0718 60 En Produced in Germany (c) Siemens AG 2018 The information provided in this brochure contains merely general descriptions or characteristics of performance which in case of actual use do not always apply as described or which may change as a result of further development of the products. An obligation to provide the respective characteristics shall only exist if expressly agreed in the terms of contract. Availability and technical specifications are subject to change without notice. All product designations may be trademarks or product names of Siemens AG or supplier companies whose use by third parties for their own purposes could violate the rights of the owners.