FEB 16, 2006 revised to JUN 15, 2006 Page 9 of 11 www.power-one.com
HHS40 DC-DC Series Data Sheet
40A Half-Brick Converter
Notes:
1. When the output voltage is trimmed up, the output power from
the converter must not exceed its maximum rating. The power is
determined by measuring the output voltage on the output pins,
and multiplying it by the output current.
2. In order to avoid creating apparent load regulation degradation, it
is important that the trim resistors are connected directly to the
remote sense pins, and not to the load or to traces going to the
load.
3. The output voltage increase can be accomplished by either the
trim or by the remote sense or by the combination of both. In
any case the absolute maximum output voltage increase shall
not exceed the limits defined in section 6 above.
4. Either Rup or Rdown should be used to adjust the output voltage
according to the equations above. If both Rup and Rdown are
used simultaneously, they will form a resistive divider and the
equations above will not apply
Safety Consideratio ns
The HHS40 Series converters feature 1500 Volt DC
isolation from input to output. The input-to-output
resistance is greater than 10MΩ. These converters are
provided with Basic insulation between input and output
circuits according to all IEC60950 based standards.
Nevertheless, if the system using the converter needs
to receive safety agency approval, certain rules must be
followed in the design of the system. In particular, all of
the creepage and clearance requirements of the end-
use safety requirements must be observed. These
documents include UL60950 - CSA60950-00 and
EN60950, although other or additional requirements
may be needed for specific applications.
The HHS40 Series converters have no internal fuse.
An external fuse must be provided to protect the system
from catastrophic failure, as illustrated in figure 5. Refer
to the “Input Fuse Selection for DC/DC converters”
application note on www.power-one.com for proper
selection of the input fuse. Both input traces and the
chassis ground trace (if applicable) must be capable of
conducting a current of 1.5 times the value of the fuse
without opening. The fuse must not be placed in the
grounded input line, if any.
In order for the output of the HHS40 Series converter to
be considered as SELV (Safety Extra Low Voltage) or
TNV-1, according to all IEC60950 based standards, one
of the following requirements must be met in the system
design:
• If the voltage source feeding the module is SELV or
TNV-2, the output of the converter may be
grounded or ungrounded.
• If the voltage source feeding the module is ELV, the
output of the converter may be considered SELV
only if the output is grounded per the
requirements of the standard.
• If the voltage source feeding the module is a
Hazardous Voltage Secondary Circuit, the
voltage source feeding the module must be
provided with at least Basic insulation
between the source to the converter and any
hazardous voltages. The entire system,
including the HHS40 converter, must pass a
dielectric withstand test for Reinforced
insulation. Design of this type of systems
requires expert engineering and under-
standing of the overall safety requirements
and should be performed by qualified
personnel.
Thermal Considerations
The HHS40 Series converters are designed for
natural or forced convection cooling. The
maximum allowable output current of the
converters is determined by meeting the derating
criteria for all components used in the converters.
For example, the maximum semiconductor
junction temperature is not allowed to exceed
120 °C to ensure reliable long-term operation of
the converters.
The graphs in Figures 8 & 9 show the maximum
output current of the HHS40 Series converters at
different ambient temperatures under both natural
and forced convection. (longitudinal airflow
direction, from pin 1 to pin 4).
For example, from Figure 8, the HHS40ZE
operating at 55 °C can deliver up to 27 A reliably
with 200 LFM forced air, while up to 36 A reliably
with 400 LFM forced air.