I-12
Noise
Filter
Specifications
No. Items TAH-04-683 TAH-06-683 TAH-10-683 TAH-20-683 TAH-30-683
1 Rated Voltage[V] AC Three Phase 500
2 Rated Current[A] 46102030
3 Test Voltage (Terminal-Mounting Plate) 2,000 VAC (Cutoff Current = 100mA), 1minute at room temperature and humidity
4 Isolation Resistance (Terminal-Mounting Plate) 500 VDC 100MW minute at room temperature and humidity
5 Leakage current 250/500V 60Hz 2.5mA/5.0mA max
6 Voltage drop 1.5V max 1.0V max
7 Safety agency approval temperatures -25 to +85C (Refer to Derating Curve)
8 Operating temperature -40 to +85C (Refer to Derating Curve)
9 Operating humidity 20 to 95%RH (Non condensing)
10 Storage temperature/humidity -40 to +85C/20 to 95%RH (Non condensing)
11 Vibration 10 to 55Hz, 19.6m/s2(2G), 3min. Period, 1hour each X, Y and Z axis
12 Impact 196.1m/s2(20G), 11ms Once each X, Y and Z axis
13 Safety agency approvals UL1283, CSA C22.2 No.8 (C-UL) , DIN EN133200 VDE0565 Teil3-1, ENEC
14 Case size (without projection) /Mass 63X64X128 mm (WXHXD) /620g max (Option : -D refer to external view)
TAH series
Three phase input type
TAH -10 -683 -O
Ordering information
1Model Name
2Rated Current
3Line to ground capacitor code:See table 1.1.
table1.1 Line to ground capacitor code
Code Leakage Current
(Input 250/500V 60Hz)
Line to ground
capacitor
(nominal value)
683 2.5mA/5.0mA max 68000pF
4Options
D :DIN rail installation type
1 2 3 4
Features of TAH series
Circuit Diagram Derating Curve
Ambient Temperature [C]
Load Factor [%]
70 80 90-20 40 50 60
20
0
-40 -30
100
80
60
40
Ultra high-attenuation type of common mode noise from 10kHz to 1MHz
- Three Phase 500 VAC - Quick and easy push-down terminal
Just connect the wires, push down and tighten
the screws with a screwdriver
*
The dimensions change when the option is set.
Refer to External view.
LOAD
Case
LINE
4
5
6
1
2
3
CY : Line to ground capacitor
CY
CY
: Mounting Plate
DIN rail installation type is optionThe terminal cover is retracted inside the unit