Preface Table of Contents SIPROTEC Notes to SIPROTEC objects DNP V3.0 Device Profile Overcurrent Protection 7SJ80 Point lists Glossary Motor Protection 7SK80 Voltage and Frequency Protection 7RW80 Communication module DNP 3.0 Bus mapping / Point lists Edition: September 2010 C53000-L2040-A320-2 Index 1 2 3 Liability statement Copyright We have checked the contents of this manual against the described hardware and software. Nevertheless, deviations may occur so that we cannot guarantee the entire harmony with the product. Copyright (c) SIEMENS AG 2010. All rights reserved. The contents of this manual will be checked in periodical intervals, corrections will be made in the following editions. We look forward to your suggestions for improvement. We reserve the right to make technical improvements without notice. V01.10.01 Siemens Aktiengesellschaft Manual No. C53000-L2040-A320-2 Copying of this document and giving it to others and the use or communication of the contents thereof, are forbidden without express authority. Offenders are liable to the payment of damages. All rights are reserved, especially in the event or grant of a patent or registration of a utility model or design. Registered trademarks SIPROTEC, SINAUT, SICAM, and DIGSI are registered trademarks of SIEMENS AG. Other names and terms can be trademarks the use of which may violate the rights of thirds. Preface Aim of the Manual The manual is devided into the following topics: * Notes to SIPROTEC objects * DNP V3.0 Device Profile * Point lists General information about design, configuration, and operation of SIPROTEC devices are laid down in the SIPROTEC 4 system manual, order no. E50417-H1176-C151. Target Audience Protection engineers, commissioning engineers, persons who are involved in setting, testing and service of protection, automation, and control devices, as well as operation personnel in electrical plants and power stations. Additional literature This manual describes the DNP 3.0 Device Profile of the SIPROTEC devices. The following additional manuals inform you about the DNP point lists and the function, operation, assembly and commissioning of the SIPROTEC devices: Manual Contents Order number Overcurrent Protection Function, operation, assembly and commissioning of the SIPROTEC device 7SJ80 SIPROTEC 7SJ80 V4.6 E50417-G1140-C343 Motor Protection SIPROTEC 7SK80 V4.6 Function, operation, assembly and commissioning of the SIPROTEC device 7SK80 E50417-G1140-C344 Voltage and Frequency Protction 7RW80 V4.6 Function, operation, assembly and commissioning of the SIPROTEC device 7RW80 C53000-G1140-C233 DNP 3.0 Communication Database DNP communication database of the SIPROTEC devices C53000-L1840-A001-03 SIPROTEC DNP 3.0 - Bus mapping / Point lists 7SJ80/7SK80/7RW80 C53000-L2040-A320-2 3 Preface The DNP V3.0 specification and the structure of the DNP messages are defined in: > DNP V3.00 Subset Definitions Edition 2.00, November 1995 DNP Users Group, Document Nr.: P009-OIG.SUB > DNP V3.00 Data Object Library Edition 0.02, July 1997 DNP Users Group Document Nr.: P009-OBL > DNP V3.00 Data Link Layer Edition 0.02, May 1997 DNP Users Group Document Nr.: P009-OPD.DL > DNP V3.00 Application Layer Edition 0.03, May 1997 DNP Users Group Document Nr.: P009-OPD.APP > DNP V3.00 Transport Functions Edition 0.01, May 1997 DNP Users Group Document Nr.: P009-OPD.TF Applicability of the Manual This manual is valid for * SIPROTEC devices 7SJ80/7SK80/7RW80 with - firmware version 4.6 or higher - DNP communication module version 02.00.01 or higher. For device parameterization DIGSI 4 version 4.8 or higher and DNP standard mappings 3-1 to 3-n (n = device type dependent number of standard mappings) have to be used. Additional Support Should further information be desired or should particular problems arise which are not covered sufficiently for the purchaser's purpose, the matter should be referred to the local Siemens representative. Training Courses Individual course offerings may be found in our Training Catalogue, or questions may be directed to our training center. Please contact your Siemens representative. 4 SIPROTEC DNP 3.0 - Bus mapping / Point lists 7SJ80/7SK80/7RW80 C53000-L2040-A320-2 Preface Instructions and Warnings The warnings and notes contained in this manual serve for your own safety and for an appropriate lifetime of the device. Please observe them! The following terms are used: DANGER indicates that death, severe personal injury or substantial property damage will result if proper precautions are not taken. Warning indicates that death, severe personal injury or substantial property damage can result if proper precautions are not taken. Caution indicates that minor personal injury or property damage can result if proper precautions are not taken. This particularly applies to damage on or in the device itself and consequential damage thereof. Note indicates information about the device or respective part of the instruction manual which is essential to highlight. Warning! Hazardous voltages are present in this electrical equipment during operation. Non- observance of the safety rules can result in severe personal injury or property damage. Only qualified personnel shall work on and around this equipment after becoming thoroughly familiar with all warnings and safety notices of this manual as well as with the applicable safety regulations. The successful and safe operation of this device is dependent on proper handling, installation, operation, and maintenance by qualified personnel under observance of all warnings and hints contained in this manual. In particular the general erection and safety regulations (e.g. IEC, DIN, VDE, EN or other national and international standards) regarding the correct use of hoisting gear must be observed. Non-observance can result in death, personal injury or substantial property damage. QUALIFIED PERSONNEL For the purpose of this instruction manual and product labels, a qualified person is one who is familiar with the installation, construction and operation of the equipment and the hazards involved. In addition, he has the following qualifications: * Is trained and authorized to energize, de-energize, clear, ground and tag circuits and equipment in accordance with established safety practices. * Is trained in the proper care and use of protective equipment in accordance with established safety practices. * Is trained in rendering first aid. SIPROTEC DNP 3.0 - Bus mapping / Point lists 7SJ80/7SK80/7RW80 C53000-L2040-A320-2 5 Preface Typographic and Symbol Conventions The following text formats are used when literal information from the device or to the device appear in the text flow: Parameter names, i.e. designators of configuration or function parameters which may appear word-for-word in the display of the device or on the screen of a personal computer (with operation software DIGSI 4), are marked in bold letters of a monospace type style. Parameter options, i.e. possible settings of text parameters, which may appear word-for-word in the display of the device or on the screen of a personal computer (with operation software DIGSI 4), are written in italic style, additionally. "Annunciations", i.e. designators for information, which may be output by the relay or required from other devices or from the switch gear, are marked in a monospace type style in quotation marks. Deviations may be permitted in drawings when the type of designator can be obviously derived from the illustration. 6 SIPROTEC DNP 3.0 - Bus mapping / Point lists 7SJ80/7SK80/7RW80 C53000-L2040-A320-2 Table of Contents Table of Contents Preface.................................................................................................................................................. 3 Table of Contents ................................................................................................................................ 7 1 2 3 Notes to SIPROTEC objects ............................................................................................................... 9 1.1 Binary Inputs / Annunciations ............................................................................................... 10 1.1.1 Error with a summary alarm ................................................................................................. 10 1.1.2 Alarm Summary Event.......................................................................................................... 10 1.1.3 Stop Data Transmission ....................................................................................................... 11 1.2 Binary Outputs / Commands ................................................................................................ 11 1.2.1 Single Commands ................................................................................................................ 11 1.2.2 Control mode REMOTE........................................................................................................ 11 1.2.3 Changing the setting group .................................................................................................. 12 1.3 Analog Inputs / Measured values ......................................................................................... 12 1.4 Metered measurands............................................................................................................ 13 DNP V3.0 Device Profile .................................................................................................................... 15 2.1 Implementation Table ........................................................................................................... 16 2.2 Device Profile Document ...................................................................................................... 18 Point lists............................................................................................................................................ 21 3.1 Functional Scope.................................................................................................................. 22 SIPROTEC DNP 3.0 - Bus mapping / Point lists 7SJ80/7SK80/7RW80 C53000-L2040-A320-2 7 Table of Contents 3.2 Binary Input Points................................................................................................................ 25 3.2.1 Auto-Reclose Function ......................................................................................................... 25 3.2.2 Overcurrent Protection.......................................................................................................... 25 3.2.3 InRush Function.................................................................................................................... 25 3.2.4 Directional Overcurrent Protection........................................................................................ 25 3.2.5 Negative Sequence Protection ............................................................................................. 26 3.2.6 Over/Underfrequency Protection .......................................................................................... 26 3.2.7 Under/Overvoltage Protection .............................................................................................. 26 3.2.8 (sensitive) Ground Fault Protection ...................................................................................... 26 3.2.9 Startup Counter for Motor ..................................................................................................... 27 3.2.10 Startup Supervision of Motors .............................................................................................. 27 3.2.11 Trip Circuit Supervision......................................................................................................... 27 3.2.12 Internal Mode Status............................................................................................................. 27 3.2.13 Control switches return position indication(double point commands)................................... 27 3.2.14 Internal controls .................................................................................................................... 28 3.2.15 Output channels return position indication (Single point commands)................................... 28 3.2.16 Internal controls .................................................................................................................... 29 3.3 Control Relay Output Blocks/Binary Output Status .............................................................. 31 3.3.1 External commands (Double point commands).................................................................... 31 3.3.2 Internal commands ............................................................................................................... 32 3.3.3 Output channel (user defined single point output commands) ............................................. 32 3.4 Counters ............................................................................................................................... 34 3.5 Analog Inputs........................................................................................................................ 35 3.5.1 Recorded measured values.................................................................................................. 35 3.5.2 Min/Max values..................................................................................................................... 35 3.5.3 Statistic values...................................................................................................................... 36 Glossary.............................................................................................................................................. 39 Index.................................................................................................................................................... 41 8 SIPROTEC DNP 3.0 - Bus mapping / Point lists 7SJ80/7SK80/7RW80 C53000-L2040-A320-2 Notes to SIPROTEC objects 1 This chapter contains notes for the use and evaluation of certain SIPROTEC objects which are available via DNP3.0 communication. 1.1 Binary Inputs / Annunciations 10 1.2 Binary Outputs / Commands 11 1.3 Analog Inputs / Measured values 12 1.4 Metered measurands 13 SIPROTEC DNP 3.0 - Bus mapping / Point lists 7SJ80/7SK80/7RW80 C53000-L2040-A320-2 9 Notes to SIPROTEC objects Note The description of the standard mappings / point lists (ref. to chap. 3) contains the preallocation of the mapping files at delivery or first assignment of a mapping in DIGSI 4 to the SIPROTEC device. Changes of the allocation and the scaling of the measured values are possible in adaptation to the concrete installation enviroment (ref. to page 3). 1.1 Binary Inputs / Annunciations Note Depending on the device composition and the existing protection packages not all of the indicated binary inputs or protection annunciations (and corresponding DNP points) may be available in the SIPROTEC device 1.1.1 Error with a summary alarm The "Error with a summary alarm" is ON if at least one of the following internal alarms assumes the value ON: * "Error 5V", "Error neutral CT", "Error 1A/5A wrong", "Error A/D converter". Reference 1.1.2 ref to chap. 3.2.12 Alarm Summary Event The "Alarm summary event" is indicated, if at least one of the following internal alarms assumes the ON status: * "Error Board 1", "Error Board 2", "Error Board 3", "Error Board 4", "Error Board 5", "Error Board 6", "Error Board 7", * "Alarm NO calibration", "Failure Battery", "Alarm Real Time Clock", * "Failure Phase Sequence", "VT Fuse Failure", "Failure Voltage Balance", "Failure Voltage Summation Phase - Ground", "Failure General Voltage Supervision", * "Failure Current Balance", "Failure Current Summation", "Failure General Current Supervision". Reference 10 ret. to chap. 3.2.12 SIPROTEC DNP 3.0 - Bus mapping / Point lists 7SJ80/7SK80/7RW80 C53000-L2040-A320-2 Binary Outputs / Commands 1.1.3 Stop Data Transmission The functionality "Stop data transmission" is not supported via DNP communication. If "Stop data transmission" is active nevertheless data via DNP will be transmitted furthermore. The annunciation "DataStop" signals the activation of "Stop data transmission" however and can be evaluated correspondingly in the DNP master. Reference 1.2 ref. to chap. 3.2.12 Binary Outputs / Commands Note The allocation of the output relays to the switching devices and to the output channels is defined during parametrization of the SIPROTEC devices. Depending on the device composition there may be less than indicated output relays (and corresponding DNP message points) available in the SIPROTEC device. 1.2.1 Single Commands The command output mode (pulse output, continuous output) is changeable for the single commands using parametrization software DIGSI 4. The switching direction OFF for single commands with pulse output is not permitted and is rejected in the SIPROTEC device. Reference 1.2.2 ref. to chap. 3.3.3 Control mode REMOTE Control mode with control authority is REMOTE, option of unlocked control with DNP. * Changing the Control mode REMOTE" to UNLOCKED permits one unlocked control operation via DNP. After execution of the command, the "Control mode REMOTE" in the SIPROTEC device will automatically be reset to LOCKED. * A programmed test "Switch in position" for unlocked control operations will always be executed. If, after changing the "Control mode REMOTE" to UNLOCKED, no command is received via DNP for a period of 5 minutes, then the "Control mode REMOTE" is automatically reset to LOCKED. SIPROTEC DNP 3.0 - Bus mapping / Point lists 7SJ80/7SK80/7RW80 C53000-L2040-A320-2 11 Notes to SIPROTEC objects Reference 1.2.3 ref. to chap. 3.3.2 Changing the setting group Switching on one setting group automatically switches off the current active setting group. Transmission of the value OFF is insignificant for the change of the setting group and is refused by the device. A change of the setting group is only possible via DNP if the parameter CHANGE TO ANOTHER SETTING GROUP (parameter address = 302) has the value "Protocol". Reference 1.3 ref. to chap. 3.3.2 Analog Inputs / Measured values Note Depending on the device composition not all of the indicated analog inputs (and corresponding DNP message points) may be available in the SIPROTEC device. The given scaling values for the measured values in the standard mapping apply to installations with the following nominal operating values: Measurement: Full Scale Voltage (parameter address 1101): - >100 ... 1000 kV Measurement: Full Scale Current (parameter address 1102): - >10 ... 1000 A Product of: * Transformers - Rated Primary Voltage (parameter address 0202) and * Ratio factor Vph/Vdelta (parameter address 0206) - >100 ... 1000 kV Transformers- CT Rated primary current (parameter address 0217) * >10 ... 1000 A Power values: * Product of Full Scale Voltage and Full Scale Current multiplied by 3 - >100 ... 1000 MW (MVAR) Note Changes of the scaling of the measured values are possible in adaptation to the concrete installation environment (ref. to manual "DNP 3.0 Communication Database"). 12 SIPROTEC DNP 3.0 - Bus mapping / Point lists 7SJ80/7SK80/7RW80 C53000-L2040-A320-2 Metered measurands 1.4 Scaling Metered measurands The scaling of the metered measurands, which are derived from measured values, refers to: 60000 impulses per hour for V = Vprim and I = Iprim Vprim = Full Scale Voltage (parameter address = 1101) Iprim = FULL SCALE CURRENT parameter address = 1102) Example In the parameter set is configured: Iprim = 1000 A and Vprim = 400.0 kV, 60000 impulses correspond so that: 1 h * 1000 A * 400 kV * 3 = 692.82 MWh Note * The type of the update (cyclic, with or without deletion) and the update interval must be programmed for the metered measurands with the parametrization software DIGSI 4. * The scaling of the metered measurands at binary inputs ("Wp(puls)" and "Wq(puls)") depends on the externally connected pulse generator. SIPROTEC DNP 3.0 - Bus mapping / Point lists 7SJ80/7SK80/7RW80 C53000-L2040-A320-2 13 Notes to SIPROTEC objects 14 SIPROTEC DNP 3.0 - Bus mapping / Point lists 7SJ80/7SK80/7RW80 C53000-L2040-A320-2 DNP V3.0 Device Profile 2 2.1 Implementation Table 16 2.2 Device Profile Document 18 SIPROTEC DNP 3.0 - Bus mapping / Point lists 7SJ80/7SK80/7RW80 C53000-L2040-A320-2 15 DNP V3.0 Device Profile 2.1 Implementation Table The following table gives a list of all objects recognized and returned by the SIPROTEC device. For static objects, requests sent with qualifiers 00, 01, 06, 07 or 08 will be responded with qualifiers 00 or 01. Requests sent with qualifiers 17 or 28 will be responded with qualifiers 17 or 28. For change-event objects, qualifiers17 or 28 are always responded. In the table below text shaded 00, 01 (start stop) indicates Subset Level 3 functionality (beyond Subset Level 2), text shaded as 07, 08 (limited qty) indicates functionality beyond Subset Level 3. 1 OBJECTS Object Variation 16 Description REQUEST Function Codes (dec) RESPONSE Qualifier Codes (hex) 1 0 Binary Input Any Variations 1 (read) 00, 01 06 07, 08 17, 28 (start-stop) (no range) (limited qfy) (index) 1 2 Binary Input with Status 1 (read) 00, 01 06 07, 08 17, 28 (start-stop) (no range) (limited qfy) (index) 2 0 Binary Input Change Any Variations 1 (read) 06 07, 08 (no range) (limited qfy) 2 2 Binary Input Change with Time 1 (read) 06 07, 08 (no range) (limited qfy) 10 0 Binary Output Any Variations 1 (read) 00, 01 06 07, 08 17, 28 (start-stop) (no range) (limited qfy) (index) 10 2 Binary Output with Status 1 (read) 00, 01 06 07, 08 17, 28 12 1 Contol Relay Output Block 3 4 5 6 (select) (operate) (direct op.) (dir. op. noack) 20 0 Binary Counter Any Variations 1 20 1 32-Bit Binary Counter (with Flag) 22 0 22 1 Function Codes (dec) Qualifier Codes (hex) 129 (response) 00, 01 17, 28 (start-stop) (index) 129 130 (response) (unsol. resp) 17, 28 (index) (start-stop) (no range) (limited qfy) (index) 129 (response) 00, 01 17, 28 (start-stop) (index) 00, 01 07, 08 17, 28 (start-stop) (limited qfy) (index) 129 (response) (read) 00, 01 06 07, 08 17, 28 (start-stop) (no range) (limited qfy) (index) 1 (read) 00, 01 06 07, 08 17, 28 (start-stop) (no range) (limited qfy) (index) Counter Change Event Any Variations 1 (read) 06 07, 08 (no range) (limited qfy) 32-Bit Counter Change Event without Time 1 (read) 06 07, 08 (no range) (limited qfy) echo of response SIPROTEC DNP 3.0 - Bus mapping / Point lists 7SJ80/7SK80/7RW80 C53000-L2040-A320-2 Implementation Table OBJECTS Object Variation Description REQUEST Function Codes (dec) RESPONSE Qualifier Codes (hex) Function Codes (dec) Qualifier Codes (hex) 30 0 16-Bit Analog Input Any Variations 1 (read) 00, 01 06 07, 08 17, 28 (start-stop) (no range) (limited qfy) (index) 30 1 32-Bit Analog Input with Status 1 (read) 00, 01 06 07, 08 17, 28 (start-stop) (no range) (limited qfy) (index) 129 (response) 00, 01 17, 28 (start-stop) (index) 30 2 16-Bit Analog Input with Status 1 (read) 00, 01 06 07, 08 17, 28 (start-stop) (no range) (limited qfy) (index) 129 (response) 00, 01 17, 28 (start-stop) (index) 32 0 Analog Change Event Any Variations 1 (read) 06 07, 08 (no range) (limited qfy) 32 1 32-Bit Analog Change Event without Time 1 (read) 06 07, 08 (no range) (limited qfy) 129 130 (response) (unsol. resp) 17, 28 (index) 32 2 16-Bit Analog Change Event without Time 1 (read) 06 07, 08 (no range) (limited qfy) 129 130 (response) (unsol. resp) 17, 28 (index) 50 1 Time and Date 2 (write) 07 (limited qfy = 1) 60 1 Class 0 Data 1 (read) 06 (no range) 60 2 Class 1 Data 1 (read) 06 07, 08 (no range) (limited qfy) 60 3 Class 2 Data 1 (read) 06 07, 08 (no range) (limited qfy) 60 4 Class 3 Data 1 (read) 06 07, 08 (no range) (limited qfy) 80 1 Internal Indications 2 (write) 00 SIPROTEC DNP 3.0 - Bus mapping / Point lists 7SJ80/7SK80/7RW80 C53000-L2040-A320-2 (start-stop) (index must = 7) 17 DNP V3.0 Device Profile 2.2 Device Profile Document DNP V3.0 DEVICE PROFILE DOCUMENT Vendor Name: SIEMENS AG Device Name: 7SJ80/7SK80/7RW80 Highest DNP Level Supported: For Requests DNP-L2 Device Function: Master Slave For Responses DNP-L2 Notable objects, functions, and/or qualifiers supported in addition to the Highest DNP Levels Supported (the complete list is described in the attached table): For static (non-change-event) object requests, request qualifier codes 00 and 01 (start-stop), 07 and 08 (limited quantity), and 17 and 28 (index) are supported in addition to request qualifier code 06 (no range). Static object requests sent with qualifiers 00, 01, 06, 07, or 08, will be responded with qualifiers 00 or 01. Static object requests sent with qualifiers 17 or 28 will be responded with qualifiers 17 or 28. For change-event object requests, qualifiers 17 or 28 are always responded. 16-bit Analog Change Events with Time may be requested. The write function code for Object 50 (Time and Date), variation 1, is supported. The features outlined within this Device Profile have successfully passed DNP Conformance Test of Subset Level 2 outlined in DNP3-2000 IED Certification Procedure. Maximum Data Link Frame Size (octets): Maximum Application Fragment Size (octets): Transmitted____292_____________ Transmitted _Configurable up to 2048 Received______292_____________ Maximum Data Link Re-tries: Received_______2048_______ Maximum Application Layer Re-tries: None Fixed at Configurable, range _0_to _255_ None Configurable, range ____ to _______ (Fixed is not permitted) Requires Data Link Layer Confirmation: Never Always Sometimes If 'Sometimes', when? ______________________________________ Configurable If 'Configurable', how? by the protection data processing program DIGSI 4 18 SIPROTEC DNP 3.0 - Bus mapping / Point lists 7SJ80/7SK80/7RW80 C53000-L2040-A320-2 Device Profile Document Requires Application Layer Confirmation: Never Always (not recommended) When reporting Event Data (Slave devices only) When sending multi-fragment responses (Slave devices only) Sometimes If 'Sometimes', when? ___________________________________ Configurable If 'Configurable', how? by the protection data processing program DIGSI 4 Timeouts while waiting for: Data Link Confirm Complete Appl. Fragment Application Confirm Complete Appl. Response None None None None Fixed at _____ Fixed at _____ Fixed at _____ Fixed at _____ Variable Variable Variable Variable Configurable Configurable Configurable Configurable Others: Default value are configurable by the protection data processing program DIGSI 4 Sends/Executes Control Operations: WRITE Binary Outputs SELECT/OPERATE DIRECT OPERATE DIRECT OPERATE - NO ACK Never Never Never Never Always Always Always Always Sometimes Sometimes Sometimes Sometimes Configurable Configurable Configurable Configurable Count > 1 Pulse On Pulse Off Latch On Latch Off Never Never Never Never Never Always Always Always Always Always Sometimes Sometimes Sometimes Sometimes Sometimes Configurable Configurable Configurable Configurable Configurable Queue Clear Queue Never Never Always Always Sometimes Sometimes Configurable Configurable Note: CONTROL RELAY OUTPUT BLOCK parameters (count, on-time, off-time) are ignored. TimeSync Information: a.) TimeSync Period Never Fixed at ________seconds Configurable, range ____1____to __86400_seconds b.) Maximum time base drift over 10 minute interval: c.) Maximum Internal Time Reference Error when set via DNP: d.) Maximum Delay Measurement error: e.) Maximum response time: c.) Event data time-tag error - if different than (c): Binary Input Change Events __________ms Counter Change Events __________ms Frozen Counter Change Events __________ms Analog Change Events __________ms Frozen Analog Change Events __________ms SIPROTEC DNP 3.0 - Bus mapping / Point lists 7SJ80/7SK80/7RW80 C53000-L2040-A320-2 ____30__ms _____1__ms ____20__ms ___100__ms 19 DNP V3.0 Device Profile Reports Binary Input Change Events when no spe- Reports time-tagged Binary Input Change Events when no specific variation requested: cific variation requested: Never Only time-tagged Only non-time-tagged Configurable to send both, one or the other (attach explanation) Sends Unsolicited Responses: Never Binary Input Change With Time Binary Input Change With Relative Time Configurable (attach explanation) Sends Static Data in Unsolicited Responses: Never When Device Restarts When Status Flags Change Never Configurable (Unsolicited data response mode are switched on/off via the configuration tool ) Only certain objects Sometimes (attach explanation) No other options are permitted. ENABLE/DISABLE UNSOLICITED Function codes supported Default Counter Object/Variation: Counters Roll Over at: No Counters Reported Configurable (attach explanation) 16 Bits 32 Bits Other Value _____________ Point-by-point list attached No Counters Reported Configurable (attach explanation) Default Object ___20_____ Default Variation ___01_____ Point-by-point list attached Sends 32-Bit counters. Sends Multi-Fragment Responses: 20 Yes No SIPROTEC DNP 3.0 - Bus mapping / Point lists 7SJ80/7SK80/7RW80 C53000-L2040-A320-2 3 Point lists 3.1 Functional Scope 22 3.2 Binary Input Points 25 3.3 Control Relay Output Blocks/Binary Output Status 31 3.4 Counters 34 3.5 Analog Inputs 35 SIPROTEC DNP 3.0 - Bus mapping / Point lists 7SJ80/7SK80/7RW80 C53000-L2040-A320-2 21 Point lists 3.1 Functional Scope Depending of the functional scope, some of the following described functions, annunciations, commands, measured and metered values are not available. 7SJ80 Table 3-1 7SJ80 Functional scope No. 22 Function Ref. to Chapter 103 Setting Group Change Option 3.2.14 104 Oscillographic Fault Records - 112 50/51 (Charac. Phase) Overcurrent Protection 3.2.2 113 50N/51N (Charac. Ground) Overcurrent Protection 3.2.2 115 67, 67-TOC Directional Overcurrent Protection 3.2.4 116 67N, 67N-TOC Directional Overcurrent Protection 3.2.4 117 Cold Load Pickup 3.3.2 122 2nd Harmonic Inrush Restraint 3.2.3 127 50 1Ph Single Phase Overcurrent Protection - 130 (sens.) Ground fault dir. characteristic 3.2.8 131 (sensitive) Ground fault 3.2.8 140 46 Negative Sequence Protection 3.2.5 142 49 Thermal Overload Protection - 150 27, 59 Under/Overvoltage Protection 3.2.7 154 81 Over/Underfrequency Protection 3.2.6 161 25 Function group 1 Synchronism and Voltage Check - 170 50BF Breaker Failure Protection - 171 79 Auto-Reclose Function 3.2.1 172 52 Breaker Wear Monitoring - 180 Fault Locator - 181 Line Sections for Fault Locator - 182 74TC Trip Circuit Supervision 3.2.11 192 Capacitive voltage measurement - 617 Port B usage - SIPROTEC DNP 3.0 - Bus mapping / Point lists 7SJ80/7SK80/7RW80 C53000-L2040-A320-2 Functional Scope 7SK80 Table 3-2 7SK80 Functional scope No. Function Ref. to Chapter 103 Setting Group Change Option 3.2.14 104 Oscillographic Fault Records - 112 50/51 (Charac. Phase) Overcurrent Protection 3.2.2 113 50N/51N (Charac. Ground) Overcurrent Protection 3.2.2 116 67N, 67N-TOC Directional Overcurrent Protection 3.2.4 117 Cold Load Pickup 3.3.2 122 2nd Harmonic Inrush Restraint 3.2.3 130 (sens.) Ground fault dir. characteristic 3.2.8 131 (sensitive) Ground fault 3.2.8 140 46 Negative Sequence Protection 3.2.5 141 48 Startup Supervision of Motors 3.2.10 142 49 Thermal Overload Protection - 143 66 Startup Counter for Motors 3.2.9 144 Load Jam Protection 150 27, 59 Under/Overvoltage Protection 3.2.7 154 81 Over/Underfrequency Protection 3.2.6 170 50BF Breaker Failure Protection - 172 52 Breaker Wear Monitoring - 182 74TC Trip Circuit Supervision 3.2.11 190 External Temperature Input - 191 Ext. Temperature Input Connection Type - 192 Capacitive voltage measurement - 617 Port B usage - SIPROTEC DNP 3.0 - Bus mapping / Point lists 7SJ80/7SK80/7RW80 C53000-L2040-A320-2 23 Point lists 7RW80 Table 3-3 7RW80 Functional scope No. 24 Function Ref. to Chapter 103 Setting Group Change Option 3.2.14 104 Oscillographic Fault Records - 143 24 Overexcitation Protection 146 Jump of Voltage Vector - 150 27, 59 Under/Overvoltage Protection 3.2.7 152 VT Broken wire supervision - 154 81 Over/Underfrequency Protection 3.2.6 155 Load Restoration - 161 25 Function group 1 Synchronism and Voltage Check - 182 74TC Trip Circuit Supervision 3.2.11 617 Port B usage - SIPROTEC DNP 3.0 - Bus mapping / Point lists 7SJ80/7SK80/7RW80 C53000-L2040-A320-2 Binary Input Points 3.2 Binary Input Points Binary Input Points Static (Steady-State) Object Number: 1 Change Event Object Number: 2 Request Function Codes supported: 1 (read) Static Variation reported when variation 0 requested: 1 (Binary Input with status) Change Event Variation reported when variation 0 requested: 2 (Binary Input Change with Time) Point Index Name 3.2.1 Description Class Auto-Reclose Function 0 >79 ON >79 ON; Automatic reclosure ON; ON = 1, OFF = 0 3 1 CB is NOT ready Circuit breaker is NOT ready; ON = 1, OFF = 0 2 2 79 DynBlock 79 - Auto-reclose is dynamically BLOCKED; ON = 1, OFF = 0 3 3 79 in progress 79 - in progress; ON = 1, OFF = 0 2 4 79 Close 79 - Close command; ON = 1 3 5 79 Successful 79 - cycle successful; ON = 1, OFF = 0 3 6 79 Lockout 79 - Lockout; ON = 1, OFF = 0 1 7 79 L_N Sequence 79-A/R single phase reclosing sequence; Program earthfault is running = 1, Program is deactivated = 0 3 8 79 L-L Sequence 79-A/R multi-phase reclosing sequence; ON = 1, OFF = 0 3 3.2.2 Overcurrent Protection 9 50/51 PH ACT 50/51 O/C is ACTIVE; ON = 1, OFF = 0 3 10 50N/51N ACT 50N/51N is ACTIVE; ON = 1, OFF = 0 3 11 50 (N) / 51 (N) PU 50(N)/51(N) O/C PICKUP; ON = 1, OFF = 0 2 12 50/51 Ph A PU 50/51 Phase A picked up; ON = 1, OFF = 0 2 13 50/51 Ph B PU 50/51 Phase B picked up; ON = 1, OFF = 0 2 14 50/51 Ph C PU 50/51 Phase C picked up; ON = 1, OFF = 0 2 15 50N/51NPickedup 50N/51N picked up; ON = 1, OFF = 0 2 16 50 (N)/51(N)TRIP 50(N)/51(N) TRIP; ON = 1 2 3.2.3 InRush Function 17 PhA InrushBlk Phase A trip blocked by inrush detection; ON = 1, OFF = 0 3 18 PhB InrushBlk Phase B trip blocked by inrush detection; ON = 1, OFF = 0 3 19 PhC InrushBlk Phase C trip blocked by inrush detection; ON = 1, OFF = 0 3 20 INRUSH X-BLK Cross blk: PhX blocked Phy; ON = 1, OFF = 0 3 3.2.4 Directional Overcurrent Protection 21 67 ACTIVE 67/67-TOC is ACTIVE; activate = 1, deactivate = 0 3 22 67N ACTIVE 67N/67N-TOC is ACTIVE; activate = 1, deactivate = 0 3 23 67/67N pickedup 67/67N picked up; ON = 1, OFF = 0 2 24 67 A picked up 67/67-TOC Phase A picked up; ON = 1, OFF = 0 2 25 67 B picked up 67/67-TOC Phase B picked up; ON = 1, OFF = 0 2 26 67 C picked up 67/67-TOC Phase C picked up; ON = 1, OFF = 0 2 SIPROTEC DNP 3.0 - Bus mapping / Point lists 7SJ80/7SK80/7RW80 C53000-L2040-A320-2 25 Point lists Binary Input Points Static (Steady-State) Object Number: 1 Change Event Object Number: 2 Request Function Codes supported: 1 (read) Static Variation reported when variation 0 requested: 1 (Binary Input with status) Change Event Variation reported when variation 0 requested: 2 (Binary Input Change with Time) Point Index Name Class 27 67N picked up 67N/67N-TOC picked up; ON = 1, OFF = 0 2 28 67/67N TRIP 67/67N TRIP; ON = 1, OFF = 0 2 3.2.5 Negative Sequence Protection 29 46 ACTIVE 46 is ACTIVE; ON = 1, OFF = 0 3 30 46-2 picked up 46-2 picked up; ON = 1, OFF = 0 2 31 46-TOC pickedup 46-TOC picked up; ON = 1, OFF = 0 2 32 46 TRIP 46 TRIP picked up; ON = 1, OFF = 0 2 33 46-1 picked up 46-1 picked up; ON = 1, OFF = 0 2 3.2.6 Over/Underfrequency Protection 34 81 ACTIVE 81 ACTIVE; ON = 1, OFF = 0 3 35 81-1 picked up 81-1 picked up; ON = 1, OFF = 0 2 36 81-2 picked up 81-2 picked up; ON = 1, OFF = 0 2 37 81-1 TRIP 81-1 TRIP; ON = 1, OFF = 0 2 38 81-2 TRIP 81-2 TRIP; ON = 1, OFF = 0 2 3.2.7 Under/Overvoltage Protection 39 27 ACTIVE 27 Undervoltage protection is ACTIVE; ON = 1, OFF = 0 3 40 27-1 picked up 27-1 Undervoltage picked up; ON = 1, OFF = 0 2 41 27-1 TRIP 27-1 Undervoltage TRIP; ON = 1, OFF = 0 2 42 59 ACTIVE 59-Overvoltage protection is ACTIVE; ON = 1, OFF = 0 3 43 59-1 picked up 59 picked up; ON = 1, OFF = 0 2 44 59-1 TRIP 59 TRIP; ON = 1, OFF = 0 2 3.2.8 26 Description (sensitive) Ground Fault Protection 45 50Ns/67Ns ACT 50Ns/67Ns is ACTIVE; ON = 1, OFF = 0 3 46 64 Pickup 64 displacement voltage pick up; ON = 1, OFF = 0 2 47 64 Trip 64 displacement voltage element TRIP; ON = 1, OFF = 0 2 48 50Ns-2 Pickup 50Ns-2 Pickup; ON = 1, OFF = 0 2 49 50Ns-2 TRIP 50Ns-2 TRIP; ON = 1, OFF = 0 2 50 50Ns-1 Pickup 50Ns-1 Pickup; ON = 1, OFF = 0 2 51 50Ns-1 TRIP 50Ns-1 TRIP; ON = 1, OFF = 0 2 52 Sens. Gnd Ph A Sensitive Ground fault picked up in Ph A; ON = 1, OFF = 0 2 53 Sens. Gnd Ph B Sensitive Ground fault picked up in Ph B; ON = 1, OFF = 0 2 54 Sens. Gnd Ph C Sensitive Ground fault picked up in Ph C; ON = 1, OFF = 0 2 55 SensGnd Forward Sensitive Gnd fault in forward direction; ON = 1, OFF = 0 2 56 SensGnd Reverse Sensitive Gnd fault in reverse direction; ON = 1, OFF = 0 2 SIPROTEC DNP 3.0 - Bus mapping / Point lists 7SJ80/7SK80/7RW80 C53000-L2040-A320-2 Binary Input Points Binary Input Points Static (Steady-State) Object Number: 1 Change Event Object Number: 2 Request Function Codes supported: 1 (read) Static Variation reported when variation 0 requested: 1 (Binary Input with status) Change Event Variation reported when variation 0 requested: 2 (Binary Input Change with Time) Point Index Name 3.2.9 Description Class Startup Counter for Motor 57 66 ACTIVE 66 Motor start protection ACTIVE; ON = 1, OFF = 0 3 58 66 TRIP 66 Motor start protection TRIP; ON = 1, OFF = 0 2 3.2.10 Startup Supervision of Motors 59 START-SUP ACT Startup supervision is ACTIVE; ON = 1, OFF = 0 3 60 START-SUP TRIP Startup supervision TRIP; ON = 1, OFF = 0 2 61 START-SUP pu Startup supervision Pickup; ON = 1, OFF = 0 2 3.2.11 Trip Circuit Supervision 62 74TC ACTIVE 74TC Trip circuit supervision is ACTIVE; ON = 1, OFF = 0 3 63 FAIL: Trip cir. 74TCFailure Trip Circuit; ON = 1, OFF = 0 1 3.2.12 Internal Mode Status 64 Cntrl Auth Control Authority; LOCAL=1, REMOTE=0 3 65 ModeLOCAL Control mode LOCAL; UNLOCKED=1, LOCKED=0 3 66 Relay OK Relay OK; ON = 1, OFF = 0 1 67 Running Setting calculation is running; ON = 1, OFF = 0 3 68 ProtActive At least one protection funct. is active; ON=1, OFF=0 2 69 Error Sum Alarm Error with a summary alarm; ON = 1, OFF = 0 (ref. to chap. 1.1.1) 2 70 Alarm Sum Event Alarm Summary Event; ON = 1, OFF = 0 (ref. to chap. 1.1.2) 2 71 Relay Pickup Relay Pickup; ON = 1, OFF = 0 1 72 Relay TRIP General TRIP of the relay; ON = 1 1 73 Test mode Test mode; ON=1, OFF=0 3 3.2.13 Control switches return position indication(double point commands) 74 52 Breaker input state of switch breaker; 0=open, 1=close 1 75 52 Breaker status switch breaker failure status; 0=switch breaker position is open or close, 1= switch breaker is in an intermediate position or position state is incorrect. 1 76 Switch 1 input state of switch 1; 0=open, 1=close 1 77 switch 1 status switch 1 failure status; 0= switch 1 position is open or close, 1= switch 1 is in an intermediate position or position state is incorrect. 1 78 Switch 2 input state of switch 2; 0=open, 1=close 1 79 switch 2 status switch 2 failure status; 0= switch 1 position is open or close, 1= switch 1 is in an intermediate position or position state is incorrect. 1 80 Switch 3 input state of switch 3; 0=open, 1=close 1 81 switch 3 status switch 3 failure status; 0= switch 2 position is open or close, 1= switch 2 is in an intermediate position or position state is incorrect. 1 SIPROTEC DNP 3.0 - Bus mapping / Point lists 7SJ80/7SK80/7RW80 C53000-L2040-A320-2 27 Point lists Binary Input Points Static (Steady-State) Object Number: 1 Change Event Object Number: 2 Request Function Codes supported: 1 (read) Static Variation reported when variation 0 requested: 1 (Binary Input with status) Change Event Variation reported when variation 0 requested: 2 (Binary Input Change with Time) Point Index Name Class 82 Switch 4 input state of switch 4; 0=open, 1=close 1 83 switch 4 status switch 4 failure status; 0= switch 3 position is open or close, 1= switch 3 is in an intermediate position or position state is incorrect. 1 84 Switch 5 input state of switch 5; 0=open, 1=close 1 85 switch 5 status switch 5 failure status; 0= switch 4 position is open or close, 1= switch 4 is in an intermediate position or position state is incorrect. 1 86 Switch 6 input state of switch 6; 0=open, 1=close 1 87 switch 6 status switch 6 failure status; 0= switch 5 position is open or close, 1= switch 5 is in an intermediate position or position state is incorrect. 1 88 Switch 7 input state of switch 7; 0=open, 1=close 1 89 switch 7 status switch 7 failure status; 0= switch 6 position is open or close, 1= switch 6 is in an intermediate position or position state is incorrect. 1 90 Switch 8 input state of switch 8; 0=open, 1=close 1 91 switch 8 status switch 8 failure status; 0= switch 6 position is open or close, 1= switch 6 is in an intermediate position or position state is incorrect. 1 3.2.14 Internal controls 92 Group A Protection Parameter Group A; 0 = Group A is deactivated, 1= Group A is activated and Group B,C,D are deactivated. 1 93 Group B Protection Parameter Group B; 0 = Group B is deactivated, 1= Group B is activated and Group A,C,D are deactivated. 1 94 Group C Protection Parameter Group C; 0 = Group C is deactivated, 1= Group C is activated and Group A,B,D are deactivated. 1 95 Group D Protection Parameter Group D; 0 = Group D is deactivated, 1= Group D is activated and Group A,B,C are deactivated. 1 96 ModeREMOTE Control mode REMOTE; UNLOCKED=1, LOCKED=0 3 3.2.15 28 Description Output channels return position indication (Single point commands) 97 >switch 1 0 = Open (off), 1= Close (on) 1 98 >switch 2 0 = Open (off), 1= Close (on) 1 99 >switch 3 0 = Open (off), 1= Close (on) 1 100 >switch 4 0 = Open (off), 1= Close (on) 1 101 >switch 5 0 = Open (off), 1= Close (on) 1 102 >switch 6 0 = Open (off), 1= Close (on) 1 103 >switch 7 0 = Open (off), 1= Close (on) 1 104 >switch 8 0 = Open (off), 1= Close (on) 1 105 >switch 9 0 = Open (off), 1= Close (on) 1 106 >switch 10 0 = Open (off), 1= Close (on) 1 107 >switch 11 0 = Open (off), 1= Close (on) 1 SIPROTEC DNP 3.0 - Bus mapping / Point lists 7SJ80/7SK80/7RW80 C53000-L2040-A320-2 Binary Input Points Binary Input Points Static (Steady-State) Object Number: 1 Change Event Object Number: 2 Request Function Codes supported: 1 (read) Static Variation reported when variation 0 requested: 1 (Binary Input with status) Change Event Variation reported when variation 0 requested: 2 (Binary Input Change with Time) Point Index Name Description Class 108 >switch 12 0 = Open (off), 1= Close (on) 1 109 >switch 13 0 = Open (off), 1= Close (on) 1 110 >switch 14 0 = Open (off), 1= Close (on) 1 111 >switch 15 0 = Open (off), 1= Close (on) 1 112 >switch 16 0 = Open (off), 1= Close (on) 1 113 >switch 17 0 = Open (off), 1= Close (on) 1 114 >switch 18 0 = Open (off), 1= Close (on) 1 115 >switch 19 0 = Open (off), 1= Close (on) 1 116 >switch 20 0 = Open (off), 1= Close (on) 1 117 >switch 21 0 = Open (off), 1= Close (on) 1 118 >switch 22 0 = Open (off), 1= Close (on) 1 119 >switch 23 0 = Open (off), 1= Close (on) 1 120 >switch 24 0 = Open (off), 1= Close (on) 1 121 >switch 25 0 = Open (off), 1= Close (on) 1 3.2.16 Internal controls 122 <unnamed>1 User input 1 2 123 <unnamed> User input 2 2 124 <unnamed> User input 3 2 125 <unnamed> User input 4 2 126 <unnamed> User input 5 2 127 <unnamed> User input 6 2 128 <unnamed> User input 7 2 129 <unnamed> User input 8 2 130 <unnamed> User input 9 2 131 <unnamed> User input 10 2 132 <unnamed> User input 11 2 133 <unnamed> User input 12 2 134 <unnamed> User input 13 2 135 <unnamed> User input 14 2 136 <unnamed> User input 15 2 137 <unnamed> User input 16 2 138 <unnamed> User input 17 2 139 <unnamed> User input 18 2 140 <unnamed> User input 19 2 SIPROTEC DNP 3.0 - Bus mapping / Point lists 7SJ80/7SK80/7RW80 C53000-L2040-A320-2 29 Point lists Binary Input Points Static (Steady-State) Object Number: 1 Change Event Object Number: 2 Request Function Codes supported: 1 (read) Static Variation reported when variation 0 requested: 1 (Binary Input with status) Change Event Variation reported when variation 0 requested: 2 (Binary Input Change with Time) Point Index Name Description Class 141 <unnamed> User input 20 2 142 <unnamed> User input 21 2 143 <unnamed> User input 22 2 144 <unnamed> User input 23 2 145 <unnamed> User input 24 2 146 <unnamed> User input 25 2 147 <unnamed> User input 26 2 148 <unnamed> User input 27 2 149 <unnamed> User input 28 2 150 <unnamed> User input 29 2 151 <unnamed> User input 30 2 152 <unnamed> User input 31 2 153 <unnamed> User input 32 2 154 <unnamed> User input 33 2 155 <unnamed> User input 34 2 156 <unnamed> User input 35 2 157 <unnamed> User input 36 2 158 <unnamed> User input 37 2 159 <unnamed> User input 38 2 160 <unnamed> User input 39 2 1The names are defined during indication allocation using parametrization softwareDIGSI 4 30 SIPROTEC DNP 3.0 - Bus mapping / Point lists 7SJ80/7SK80/7RW80 C53000-L2040-A320-2 Control Relay Output Blocks/Binary Output Status 3.3 Control Relay Output Blocks/Binary Output Status Binary Output Status Points Object Number: 10 Request Function Codes supported: 1 (Read) Default Variation reported when variation 0 requested: 2 (Binary Output Status) Control Relay Output Blocks/Binary Output Status Object Number: 12 Request Function Codes supported: Point Index 3 (select), 4 (operate), 5 (direct operate), 6 (direct operate, no ack) Name 3.3.1 Description Supported Control Relay Output Block Fields External commands (Double point commands) 0 52Breaker Trip Breaker switch Trip, Pulse On (On Time Fixed1) 1 52Breaker Close Breaker switch Close, Pulse On (On Time Fixed) 2 Switch 1 Trip switch 1 Trip, Pulse On (On Time Fixed) 3 Switch 1 Close switch 1 Close, Pulse On (On Time Fixed) 4 Switch 2 Trip switch 2 Trip, Pulse On (On Time Fixed) 5 Switch 2 Close switch 2 Close, Pulse On (On Time Fixed) 6 Switch 3 Trip switch 3 Trip, Pulse On (On Time Fixed) 7 Switch 3 Close switch 3 Close, Pulse On (On Time Fixed) 8 Switch 4 Trip switch 4 Trip, Pulse On (On Time Fixed) 9 Switch 4 Close switch 4 Close, Pulse On (On Time Fixed) 10 Switch 5 Trip switch 5 Trip, Pulse On (On Time Fixed) 11 Switch 5 Close switch 5 Close, Pulse On (On Time Fixed) 12 Switch 6 Trip switch 6 Trip, Pulse On (On Time Fixed) 13 Switch 6 Close switch 6 Close, Pulse On (On Time Fixed) 14 Switch 7 Trip switch 7 Trip, Pulse On (On Time Fixed) 15 Switch 7 Close switch 7 Close, Pulse On (On Time Fixed) 16 Switch 8 Trip switch 8 Trip, Pulse On (On Time Fixed) 17 Switch 8 Close switch 8 Close, Pulse On (On Time Fixed) SIPROTEC DNP 3.0 - Bus mapping / Point lists 7SJ80/7SK80/7RW80 C53000-L2040-A320-2 31 Point lists Binary Output Status Points Object Number: 10 Request Function Codes supported: 1 (Read) Default Variation reported when variation 0 requested: 2 (Binary Output Status) Control Relay Output Blocks/Binary Output Status Object Number: 12 Request Function Codes supported: Point Index 3 (select), 4 (operate), 5 (direct operate), 6 (direct operate, no ack) Name 3.3.2 Description Supported Control Relay Output Block Fields Internal commands 18 Group A Select parametergroup A and deactivate parametergroup B,C,D ref. to chap. 1.2.3 Latch On 19 Group B Select parametergroup B and deactivate parametergroup A,C,D Latch On 20 Group C Select parametergroup C and deactivate parametergroup A,B,D Latch On 21 Group D Select parametergroup D and deactivate parametergroup A,B,C Latch On 22 ModeREMOTE Mode remote control; Latch On = UNLOCKED Lath Off = LOCKED (ref. to chap.1.2.2 ) Latch On; Latch Off 3.3.3 Output channel (user defined single point output commands) Please ref to chap. 1.2.1 for additional notes. 32 23 Output 12 Output channel 1 Latch On, Latch Off, Pulse On 24 Output 2 Output channel 2 Latch On, Latch Off, Pulse On 25 Output 3 Output channel 3 Latch On, Latch Off, Pulse On 26 Output 4 Output channel 4 Latch On, Latch Off, Pulse On 27 Output 5 Output channel 5 Latch On, Latch Off, Pulse On 28 Output 6 Output channel 6 Latch On, Latch Off, Pulse On 29 Output 7 Output channel 7 Latch On, Latch Off, Pulse On 30 Output 8 Output channel 8 Latch On, Latch Off, Pulse On 31 Output 9 Output channel 9 Latch On, Latch Off, Pulse On 32 Output 10 Output channel 10 Latch On, Latch Off, Pulse On 33 Output 11 Output channel 11 Latch On, Latch Off, Pulse On 34 Output 12 Output channel12 Latch On, Latch Off, Pulse On 35 Output 13 Output channel 13 Latch On, Latch Off, Pulse On SIPROTEC DNP 3.0 - Bus mapping / Point lists 7SJ80/7SK80/7RW80 C53000-L2040-A320-2 Control Relay Output Blocks/Binary Output Status Binary Output Status Points Object Number: 10 Request Function Codes supported: 1 (Read) Default Variation reported when variation 0 requested: 2 (Binary Output Status) Control Relay Output Blocks/Binary Output Status Object Number: 12 Request Function Codes supported: Point Index 3 (select), 4 (operate), 5 (direct operate), 6 (direct operate, no ack) Name Description Supported Control Relay Output Block Fields 36 Output 14 Output channel 14 Latch On, Latch Off, Pulse On 37 Output 15 Output channel 15 Latch On, Latch Off, Pulse On 38 Output 16 Output channel 16 Latch On, Latch Off, Pulse On 39 Output 17 Output channel 17 Latch On, Latch Off, Pulse On 40 Output 18 Output channel 18 Latch On, Latch Off, Pulse On 41 Output 19 Output channel 19 Latch On, Latch Off, Pulse On 42 Output 20 Output channel 20 Latch On, Latch Off, Pulse On 43 Output 21 Output channel 21 Latch On, Latch Off, Pulse On 44 Output 22 Output channel 22 Latch On, Latch Off, Pulse On 45 Output 23 Output channel 23 Latch On, Latch Off, Pulse On 46 Output 24 Output channel 24 Latch On, Latch Off, Pulse On 47 Output 25 Output channel 25 Latch On, Latch Off, Pulse On 1The On-Time is fixed within theSIPROTEC parameter package for each commond object. The Control Relay Output Block information on-time will be ignored. 2The names are defined during indication allocation using parametrization softwareDIGSI 4 SIPROTEC DNP 3.0 - Bus mapping / Point lists 7SJ80/7SK80/7RW80 C53000-L2040-A320-2 33 Point lists 3.4 Counters Counters Static (Steady-State) Object Number: 20 Change Event Object Number: 22 Request Function Codes supported: 1 (read) Static Variation reported when variation 0 requested: 1 (32-Bit Counter with Flag) Change Event Variation reported when variation 0 requested: 1 (32-Bit Counter without Time) Point Index 34 Name Description Scaling(232-1 of the unsigned longvalue corresponds to...) 0 Wp+= Wp Forward (metered measurand derived from measured value) 232-1 impulses 1 Wq+= Wq Forward (metered measurand derived from measured value) 232-1 impulses 2 Wp-= Wp Reverse (metered measurand derived from measured value) 232-1 impulses 3 Wq-= Wq Reverse (metered measurand derived from measured value) 232-1 impulses 4 Wp(puls) = Pulsed Energy Wp (active)(metering impulses at binary input) 232-1 impulses 5 Wq(puls) = Pulsed Energy Wq (reactive)(metering impulses at binary input) 232-1 impulses SIPROTEC DNP 3.0 - Bus mapping / Point lists 7SJ80/7SK80/7RW80 C53000-L2040-A320-2 Analog Inputs 3.5 Analog Inputs Analog Inputs Static (Steady-State) Object Number: 30 Change Event Object Number: 32 Request Function Codes supported: 1 (read) Static Variation reported when variation 0 requested: 02 (16-Bit Analog Input) Change Event Variation reported when variation 0 requested:02 (Analog Change Event without Time) Point Index Name 3.5.1 Description Scaling(32767 corresponds to ...) Default Change Event assigned Class Recorded measured values 0 la= Current phase a 3276.7 A 1 1 lb= Current phase b 3276.7 A 1 2 lc= Current phase c 3276.7 A 1 3 I0= Current I0 3276.7 A 1 4 Va= Voltage phase a 32.767 kV 1 5 Vb= Voltage phase b 32.767 kV 1 6 Vc= Voltage phase c 32.767 kV 1 7 Va-b= Voltage phase a to phase b 32.767 kV 1 8 Vb-c= Voltage phase b to phase c 32.767 kV 1 9 Vc-a= Voltage phase c to phase a 32.767 kV 1 10 V= Voltage Ground 32.767 kV 1 11 P= Active power 32767 kW 1 12 Q= Reactive power 32767 kVar 1 13 S= Apparent power 32767 kVar 1 14 Freq= frequency 327.67 Hz 1 15 cos = power factor 3.2767 1 16 UsrMv1 user defined measurement 3276.7 1 17 UsrMv2 user defined measurement 3276.7 1 18 UsrMv3 user defined measurement 3276.7 1 19 UsrMv4 user defined measurement 3276.7 1 20 UsrMv5 user defined measurement 3276.7 1 21 UsrMv6 user defined measurement 3276.7 1 22 UsrMv7 user defined measurement 3276.7 1 23 UsrMv8 user defined measurement 3276.7 1 24 UsrMv9 user defined measurement 3276.7 1 25 UsrMv10 user defined measurement 3276.7 1 26 UsrMv11 user defined measurement 3276.7 1 27 UsrMv12 user defined measurement 3276.7 1 3276.7 A 3 3.5.2 28 la Min= Min/Max values Current phase a minimum SIPROTEC DNP 3.0 - Bus mapping / Point lists 7SJ80/7SK80/7RW80 C53000-L2040-A320-2 35 Point lists Analog Inputs Static (Steady-State) Object Number: 30 Change Event Object Number: 32 Request Function Codes supported: 1 (read) Static Variation reported when variation 0 requested: 02 (16-Bit Analog Input) Change Event Variation reported when variation 0 requested:02 (Analog Change Event without Time) Point Index Name Description Scaling(32767 corresponds to ...) Default Change Event assigned Class 29 la Max= Current phase a maximum 3276.7 A 3 30 lb Min= Current phase b minimum 3276.7 A 3 31 lb Max= Current phase b maximum 3276.7 A 3 32 lc Min= Current phase c minimum 3276.7 A 3 33 lc Max= Current phase c maximum 3276.7 A 3 34 Va-n Min= Voltage phase a minimum 32.767 kV 3 35 Va-nMax= Voltage phase a maximum 32.767 kV 3 36 Vb-nMin= Voltage phase b minimum 32.767 kV 3 37 Vb-nMax= Voltage phase b maximum 32.767 kV 3 38 Vc-nMin= Voltage phase c minimum 32.767 kV 3 39 Vc-nMax= Voltage phase c maximum 32.767 kV 3 40 Vn Min= Voltage neutral minimum 32.767 kV 3 41 Vn Max= Voltage neutral maximum 32.767 kV 3 42 P Min= Active power minimum 32767 kW 3 43 P Max= Active power maximum 32767 kW 3 44 Q Min= Reactive power minimum 32767 kVar 3 45 Q Max= Reactive power maximum 32767 kVar 3 46 S Min= Apparent power minimum 32767 kVar 3 47 S Max= Apparent power maximum 32767 kVar 3 48 f Min= frequency Minimum 327.67 Hz 3 49 f Max= frequency Maximum 327.67 Hz 3 50 cos min= Power factor minimum 3.2767 3 51 cos max= Power factor maximum 3.2767 3 If Object 30 Variation 01 (32-Bit Analog Input) requesten, additional: 3.5.3 36 Statistic values 52 (0)Ia= Trip Current phase a 32767 A 1 53 (0)Ib= Trip Current phase b 32767 A 1 54 (0)Ic= Trip Current phase c 32767 A 1 55 Sum Ia = Accumulation of interrupted current Ph A 327.67 kA 3 56 Sum Ib = Accumulation of interrupted current Ph B 327.67 kA 3 57 Sum Ic = Accumulation of interrupted current Ph C 327.67 kA 3 SIPROTEC DNP 3.0 - Bus mapping / Point lists 7SJ80/7SK80/7RW80 C53000-L2040-A320-2 Analog Inputs Analog Inputs Static (Steady-State) Object Number: 30 Change Event Object Number: 32 Request Function Codes supported: 1 (read) Static Variation reported when variation 0 requested: 02 (16-Bit Analog Input) Change Event Variation reported when variation 0 requested:02 (Analog Change Event without Time) Point Index Name Description Scaling(32767 corresponds to ...) Default Change Event assigned Class 32767 h 1 58 Op. Hours= Counter of operating hours 59 <unnamed> User input 2 3 60 <unnamed> User input 2 3 SIPROTEC DNP 3.0 - Bus mapping / Point lists 7SJ80/7SK80/7RW80 C53000-L2040-A320-2 37 Point lists 38 SIPROTEC DNP 3.0 - Bus mapping / Point lists 7SJ80/7SK80/7RW80 C53000-L2040-A320-2 Glossary AME Asynchronous interface module with (electrical) isolated RS485 interface for the SIPROTEC devices from Siemens. AMO Asynchronous interface module with optical interface for the SIPROTEC devices from Siemens. AR Automatic Recloser CFC Continuous Function Chart DC Double Command DIGSI Parameterization system for SIPROTEC devices DNP Distributed Network Protocol DP Double-point Indication Input data/ input direction Data from the DNP slave to the DNP master. Mapping Allocation of the SIPROTEC data objects to the DNP point index. Output data/ output direction Data from the DNP master to the DNP slave. RTU Remote Terminal Unit SC Single Command SP Single-point Indication SIPROTEC DNP 3.0 - Bus mapping / Point lists 7SJ80/7SK80/7RW80 C53000-L2040-A320-2 39 40 SIPROTEC DNP 3.0 - Bus mapping / Point lists 7SJ80/7SK80/7RW80 C53000-L2040-A320-2 Index Index A N Additional support ............................................4 Alarm summary event ....................................10 Analog Inputs .......................................... 12, 35 Applicability of manual .....................................4 Note (definition) ................................................5 B Binary Input Points .................................. 10, 25 Binary Outputs / Commands ................... 11, 31 P Parameter names .............................................6 Parameter options ............................................6 Pulse output ...................................................11 pulse output ....................................................11 Q C Caution (definition) ...........................................5 Command output ............................................11 continuous output ...........................................11 Control authority .............................................11 Control mode ..................................................11 Copyright ..........................................................2 Counters .........................................................34 D Danger (definition) ............................................5 Device Profile Document ...............................18 DNP messages ................................................4 DNP V3.0 specification ....................................4 I Qualified personnel (definition) ........................5 S Scaling of the metered measurands ..............13 Scaling values ................................................12 Setting group ..................................................12 Stop data transmission ...................................11 Subset Level 2 ................................................16 Subset Level 3 ................................................16 Summary alarm ..............................................10 Symbol conventions .........................................6 T Target audience of manual ..............................3 Typographic conventions .................................6 Implementation Table ....................................16 V M Validity ..............................................................4 Metered measurands .....................................13 W Warning (definition) ..........................................5 SIPROTEC DNP 3.0 - Bus mapping / Point lists 7SJ80/7SK80/7RW80 C53000-L2040-A320-2 41 Index 42 SIPROTEC DNP 3.0 - Bus mapping / Point lists 7SJ80/7SK80/7RW80 C53000-L2040-A320-2