Edition: September 2010
C53000-L2040-A320-2
SIPROTEC
Overcurrent Protection
7SJ80
Motor Protection
7SK80
Voltage and Frequency
Protection
7RW80
Communication module
DNP 3.0
Bus mapping / Point lists
Preface
Table of Contents
Notes to SIPROTEC objects 1
DNP V3.0 Device Profile 2
Point lists 3
Glossary
Index
Siemens Aktiengesellschaft Manual No. C53000-L2040-A320-2
Copyright
Copyright © SIEMENS AG 2010. All rights reserved.
Copying of this document and giving it to others and the use or
communication of the contents thereof, are forbidden without ex-
press authority. Offenders are liable to the payment of damages. All
rights are reserved, especially in the event or grant of a patent or
registration of a utility model or design.
Registered trademarks
SIPROTEC, SINAUT, SICAM, and DIGSI are registered trade-
marks of SIEMENS AG. Other names and terms can be trade-
marks the use of which may violate the rights of thirds.
Liability statement
We have checked the contents of this manual against the
described hardware and software. Nevertheless, deviations
may occur so that we cannot guarantee the entire harmony
with the product.
The contents of this manual will be checked in periodical in-
tervals, corrections will be made in the following editions.
We look forward to your suggestions for improvement.
We reserve the right to make technical improvements with-
out notice.
V01.10.01
3SIPROTEC DNP 3.0 - Bus mapping / Point lists 7SJ80/7SK80/7RW80
C53000-L2040-A320-2
Preface
Aim of the Manual The manual is devided into the following topics:
Notes to SIPROTEC objects
DNP V3.0 Device Profile
Point lists
General information about design, configuration, and operation of SIPROTEC devices
are laid down in the SIPROTEC 4 system manual, order no. E50417-H1176-C151.
Target Audience Protection engineers, commissioning engineers, persons who are involved in setting,
testing and service of protection, automation, and control devices, as well as operation
personnel in electrical plants and power stations.
Additional
literature This manual describes the DNP 3.0 Device Profile of the SIPROTEC devices.
The following additional manuals inform you about the DNP point lists and the func-
tion, operation, assembly and commissioning of the SIPROTEC devices:
Manual Contents Order numbe r
Overcurrent Protection
SIPROTEC 7SJ80
V4.6
Function, operation, assembly and commissioning
of the SIPROTEC device 7SJ80
E50417-G1140-C343
Motor Protection
SIPROTEC 7SK80
V4.6
Function, operation, assembly and commissioning
of the SIPROTEC device 7SK80
E50417-G1140-C344
Voltage and
Frequency Protction
7RW80
V4.6
Function, operation, assembly and commissioning
of the SIPROTEC device 7RW80
C53000-G1140-C233
DNP 3.0
Communication
Database
DNP communication database of the SIPROTEC
devices
C53000-L1840-A001-03
Preface
4SIPROTEC DNP 3.0 - Bus mapping / Point lists 7SJ80/7SK80/7RW80
C53000-L2040-A320-2
The DNP V3.0 specification and the structure of the DNP messages are defined in:
>DNP V3.00 Subset Definitions
Edition 2.00, November 1995
DNP Users Group,
Document Nr.: P009-OIG.SUB
>DNP V3.00 Data Object Library
Edition 0.02, July 1997
DNP Users Group
Document Nr.: P009-OBL
>DNP V3.00 Data Link Layer
Edition 0.02, May 1997
DNP Users Group
Document Nr.: P009-OPD.DL
>DNP V3.00 Application Layer
Edition 0.03, May 1997
DNP Users Group
Document Nr.: P009-OPD.APP
>DNP V3.00 Transport Functions
Edition 0.01, May 1997
DNP Users Group
Document Nr.: P009-OPD.TF
Applicability of the
Manual This manual is valid for
SIPROTEC devices 7SJ80/7SK80/7RW80 with
firmware version 4.6 or higher
DNP communication module version 02.00.01 or higher.
For device parameterization DIGSI 4 version 4.8 or higher and
DNP standard mappings 3-1 to 3-n (n = device type dependent number of standard
mappings) have to be used.
Additional Support Should further information be desired or should particular problems arise which are
not covered sufficiently for the purchaser's purpose, the matter should be referred to
the local Siemens representative.
Training Courses Individual course offerings may be found in our Training Catalogue, or questions may
be directed to our training center. Please contact your Siemens representative.
Preface
5
SIPROTEC DNP 3.0 - Bus mapping / Point lists 7SJ80/7SK80/7RW80
C53000-L2040-A320-2
Instructions and
Warnings The warnings and notes contained in this manual serve for your own safety and for an
appropriate lifetime of the device. Please observe them!
The following terms are used:
DANGER
indicates that death, severe personal injury or substantial property damage will result
if proper precautions are not taken.
Warning
indicates that death, severe personal injury or substantial property damage can result
if proper precautions are not taken.
Caution
indicates that minor personal injury or property damage can result if proper precau-
tions are not taken. This particularly applies to damage on or in the device itself and
consequential damage thereof.
Note
indicates information about the device or respective part of the instruction manual
which is essential to highlight.
QUALIFIED PERSONNEL
For the purpose of this instruction manual and product labels, a qualified person is one
who is familiar with the installation, construction and operation of the equipment and
the hazards involved. In addition, he has the following qualifications:
Is trained and authorized to energize, de-energize, clear, ground and tag circuits
and equipment in accordance with established safety practices.
Is trained in the proper care and use of protective equipment in accordance with es-
tablished safety practices.
Is trained in rendering first aid.
Warning!
Hazardous voltages are present in this electrical equipment during operation. Non–
observance of the safety rules can result in severe personal injury or property dam-
age.
Only qualified personnel shall work on and around this equipment after becoming thor-
oughly familiar with all warnings and safety notices of this manual as well as with the
applicable safety regulations.
The successful and safe operation of this device is dependent on proper handling, in-
stallation, operation, and maintenance by qualified personnel under observance of all
warnings and hints contained in this manual.
In particular the general erection and safety regulations (e.g. IEC, DIN, VDE, EN or
other national and international standards) regarding the correct use of hoisting gear
must be observed. Non–observance can result in death, personal injury or substantial
property damage.
Preface
6SIPROTEC DNP 3.0 - Bus mapping / Point lists 7SJ80/7SK80/7RW80
C53000-L2040-A320-2
Typographic and
Symbol Conven-
tions
The following text formats are used when literal information from the device or to the
device appear in the text flow:
Parameter names, i.e. designators of configuration or function parameters which
may appear word-for-word in the display of the device or on the screen of a personal
computer (with operation software DIGSI 4), are marked in bold letters of a mono-
space type style.
Parameter options, i.e. possible settings of text parameters, which may appear
word-for-word in the display of the device or on the screen of a personal computer
(with operation software DIGSI 4), are written in italic style, additionally.
Annunciations”, i.e. designators for information, which may be output by the relay
or required from other devices or from the switch gear, are marked in a monospace
type style in quotation marks.
Deviations may be permitted in drawings when the type of designator can be obviously
derived from the illustration.
Table of Conten ts
7
SIPROTEC DNP 3.0 - Bus mapping / Point lists 7SJ80/7SK80/7RW80
C53000-L2040-A320-2
Table of Contents
Preface.................................................................................................................................................. 3
Table of Contents ................. ... ... ... .... ................... ... ... .... ................... ... ... .... ................... ..................... 7
1 Notes to SIPROTEC objects ............................................................................................................... 9
1.1 Binary Inputs / Annunciations ............................................................................................... 10
1.1.1 Error with a summary alarm .................................................................................................10
1.1.2 Alarm Summary Event.......................................................................................................... 10
1.1.3 Stop Data Transmission ....................................................................................................... 11
1.2 Binary Outputs / Commands ................................................................................................ 11
1.2.1 Single Commands ................................................................................................................ 11
1.2.2 Control mode REMOTE........................................................................................................11
1.2.3 Changing the setting group .................................................................................................. 12
1.3 Analog Inputs / Measured values ......................................................................................... 12
1.4 Metered measurands............................................................................................................ 13
2 DNP V3.0 Device Profile.................................................................................................................... 15
2.1 Implementation Table ........................................................................................................... 16
2.2 Device Profile Document ......................................................................................................18
3 Point lists............................................................................................................................................ 21
3.1 Functional Scope.................................................................................................................. 22
Table of Contents
8SIPROTEC DNP 3.0 - Bus mapping / Point lists 7SJ80/7SK80/7RW80
C53000-L2040-A320-2
3.2 Binary Input Points................................................................................................................ 25
3.2.1 Auto-Reclose Function ......................................................................................................... 25
3.2.2 Overcurrent Protection.......................................................................................................... 25
3.2.3 InRush Function.................................................................................................................... 25
3.2.4 Directional Overcurrent Protection........................................................................................ 25
3.2.5 Negative Sequence Protection ............................................................................................. 26
3.2.6 Over/Underfrequency Protection .......................................................................................... 26
3.2.7 Under/Overvoltage Protection .............................................................................................. 26
3.2.8 (sensitive) Ground Fault Protection ...................................................................................... 26
3.2.9 Startup Counter for Motor ..................................................................................................... 27
3.2.10 Startup Supervision of Motors .............................................................................................. 27
3.2.11 Trip Circuit Supervision......................................................................................................... 27
3.2.12 Internal Mode Status............................................................................................................. 27
3.2.13 Control switches return position indication(double point commands)................................... 27
3.2.14 Internal controls .................................................................................................................... 28
3.2.15 Output channels return position indication (Single point commands)................................... 28
3.2.16 Internal controls .................................................................................................................... 29
3.3 Control Relay Output Blocks/Binary Output Status .............................................................. 31
3.3.1 External commands (Double point commands).................................................................... 31
3.3.2 Internal commands ............................................................................................................... 32
3.3.3 Output channel (user defined single point output commands) ............................................. 32
3.4 Counters ............................................................................................................................... 34
3.5 Analog Inputs........................................................................................................................ 35
3.5.1 Recorded measured values.................................................................................................. 35
3.5.2 Min/Max values..................................................................................................................... 35
3.5.3 Statistic values...................................................................................................................... 36
Glossary.............................................................................................................................................. 39
Index.................................................................................................................................................... 41
9SIPROTEC DNP 3.0 - Bus mapping / Point lists 7SJ80/7SK80/7RW80
C53000-L2040-A320-2
Notes to SIPROTEC objects 1
This chapter contains notes for the use and evaluation of certain SIPROTEC objects
which are available via DNP3.0 communication.
1.1 Binary Inputs / Annunciations 10
1.2 Binary Outputs / Commands 11
1.3 Analog Inputs / Measured values 12
1.4 Metered measurands 13
Notes to SIPROTEC objects
10 SIPROTEC DNP 3.0 - Bus mapping / Point lists 7SJ80/7SK80/7RW80
C53000-L2040-A320-2
1.1 Binary Inputs / Annunciations
1.1.1 Error with a summary alarm
The "Error with a summary alarm" is ON if at least one of the following internal alarms
assumes the value ON:
"Error 5V", "Error neutral CT", "Error 1A/5A wrong", "Error A/D converter".
Reference ref to chap. 3.2.12
1.1.2 Alarm Summary Event
The "Alarm summary event" is indicated, if at least one of the following internal alarms
assumes the ON status:
“Error Board 1“, “Error Board 2“, "Error Board 3“, "Error Board 4“, "Error Board 5“,
“Error Board 6“, "Error Board 7“,
"Alarm NO calibration“, "Failure Battery“, "Alarm Real Time Clock",
"Failure Phase Sequence", "VT Fuse Failure", "Failure Voltage Balance", "Failure
Voltage Summation Phase – Ground", "Failure General Voltage Supervision",
"Failure Current Balance", "Failure Current Summation", "Failure General Current
Supervision".
Reference ret. to chap. 3.2.12
Note
The description of the standard mappings / point lists (ref. to chap. 3) contains the pre-
allocation of the mapping files at delivery or first assignment of a mapping in DIGSI 4
to the SIPROTEC device.
Changes of the allocation and the scaling of the measured values are possible in ad-
aptation to the concrete installation enviroment (ref. to page 3).
Note
Depending on the device composition and the existing protection packages not all of
the indicated binary inputs or protection annunciations (and corresponding DNP
points) may be available in the SIPROTEC device
Binary Outputs / Commands
11
SIPROTEC DNP 3.0 - Bus mapping / Point lists 7SJ80/7SK80/7RW80
C53000-L2040-A320-2
1.1.3 Stop Data Transmission
The functionality "Stop data transmission" is not supported via DNP communication.
If "Stop data transmission" is active nevertheless data via DNP will be transmitted fur-
thermore.
The annunciation "DataStop" signals the activation of "Stop data transmission" how-
ever and can be evaluated correspondingly in the DNP master.
Reference ref. to chap. 3.2.12
1.2 Binary Outputs / Commands
1.2.1 Single Commands
The command output mode (pulse output, continuous outp ut) is changeable for the
single commands using parametrization software DIGSI 4.
The switching direction OFF for single commands with pulse output is not permitted
and is rejected in the SIPROTEC device.
Reference ref. to chap. 3.3.3
1.2.2 Control mode REMOTE
Control mode with control authority is REMOTE, option of unlocked control with DNP.
Changing the Control mode REMOTE“ to UNLOCKED permits one unlocked con-
trol operation via DNP. After execution of the command, the “Control mode RE-
MOTE“ in the SIPROTEC device will automatically be reset to LOCKED.
A programmed test “Switch in position“ for unlocked control operations will always
be executed.
If, after changing the “Control mode REMOTE“ to UNLOCKED, no command is re-
ceived via DNP for a period of 5 minutes, then the “Control mode REMOTE“ is auto-
matically reset to LOCKED.
Note
The allocation of the output relays to the switching devices and to the output channels
is defined during parametrization of the SIPROTEC devices.
Depending on the device composition there may be less than indicated output relays
(and corresponding DNP message points) available in the SIPROTEC device.
Notes to SIPROTEC objects
12 SIPROTEC DNP 3.0 - Bus mapping / Point lists 7SJ80/7SK80/7RW80
C53000-L2040-A320-2
Reference ref. to chap. 3.3.2
1.2.3 Changing the setting group
Switching on one setting group automatically switches off the current active setting
group. Transmission of the value OFF is insignificant for the change of the setting
group and is refused by the device.
A change of the setting group is only possible via DNP if the parameter CHANGE TO
ANOTHER SETTING GROUP (parameter address = 302) has the value "Protocol".
Reference ref. to chap. 3.3.2
1.3 Analog Inputs / Measured values
The given scaling values for the measured values in the standard mapping apply to
installations with the following nominal operating values:
Measurement: Full Scale Voltage (parameter address 1101):
>100 ... 1000 kV
Measurement: Full Scale Current (parameter address 1102):
>10 ... 1000 A
Product of:
Transformers – Rated Primary Voltage (parameter address 0202) and
Ratio factor Vph/Vdelta (parameter address 0206)
>100 ... 1000 kV
Transformers– CT Rated primary current (parameter address 0217)
>10 ... 1000 A
Power values:
Product of Full Scale Voltage and Full Scale Current multiplied by
>100 ... 1000 MW (MVAR)
Note
Depending on the device composition not all of the indicated analog inputs (and cor-
responding DNP message points) may be available in the SIPROTEC device.
3
Note
Changes of the scaling of the measured values are possible in adaptation to the con-
crete installation environment (ref. to manual “DNP 3.0 Communication Database”).
Metered measurand s
13
SIPROTEC DNP 3.0 - Bus mapping / Point lists 7SJ80/7SK80/7RW80
C53000-L2040-A320-2
1.4 Metered measurands
Scaling The scaling of the metered measurands, which are derived from measured values, re-
fers to:
60000 impulses per hour for V = Vprim and I = Iprim
Vprim = Full Scale Voltage
(parameter address = 1101)
Iprim = FULL SCALE CURRENT
parameter address = 1102)
Example In the parameter set is configured:
Iprim = 1000 A and Vprim = 400.0 kV,
60000 impulses correspond so that:
1 h * 1000 A * 400 kV * √3 = 692.82 MWh
Note
The type of the update (cyclic, with or without deletion) and the update interval must
be programmed for the metered measurands with the parametrization software
DIGSI 4.
The scaling of the metered measurands at binary inputs ("Wp(puls)" and
"Wq(puls)") depends on the externally connected pulse generator.
Notes to SIPROTEC objects
14 SIPROTEC DNP 3.0 - Bus mapping / Point lists 7SJ80/7SK80/7RW80
C53000-L2040-A320-2
15SIPROTEC DNP 3.0 - Bus mapping / Point lists 7SJ80/7SK80/7RW80
C53000-L2040-A320-2
DNP V3.0 Device Profile 2
2.1 Implementation Table 16
2.2 Device Profile Document 18
DNP V3.0 Device Profile
16 SIPROTEC DNP 3.0 - Bus mapping / Point lists 7SJ80/7SK80/7RW80
C53000-L2040-A320-2
2.1 Implementation Table
The following table gives a list of all objects recognized and returned by the SIPRO-
TEC device.
For static objects, requests sent with qualifiers 00, 01, 06, 07 or 08 will be responded
with qualifiers 00 or 01.
Requests sent with qualifiers 17 or 28 will be responded with qualifiers 17 or 28.
For change-event objects, qualifiers17 or 28 are always responded.
In the table below text shaded 00, 01 (start stop) indicates Subset Level 3 functionality
(beyond Subset Level 2), text shaded as 07, 08 (limited qty) indicates functionality be-
yond Subset Level 3.
1
OBJECTS REQUEST RESPONSE
Object Vari-
ation Description Function Codes
(dec) Qualifier Codes
(hex) Function Codes
(dec) Qualifier Codes
(hex)
1 0 Binary Input -
Any Variations
1(read) 00, 01 (start-stop)
06 (no range)
07, 08 (limited qfy)
17, 28 (index)
1 2 Binary Input with Status 1 (read) 00, 01 (start-stop)
06 (no range)
07, 08 (limited qfy)
17, 28 (index)
129 (response) 00, 01 (start-stop)
17, 28 (index)
2 0 Binary Input Change -
Any Variations
1(read) 06 (no range)
07, 08 (limited qfy)
2 2 Binary Input Change with Time 1 (read) 06 (no range)
07, 08 (limited qfy)
129 (response)
130 (unsol. resp)
17, 28 (index)
10 0 Binary Output -
Any Variations
1(read) 00, 01 (start-stop)
06 (no range)
07, 08 (limited qfy)
17, 28 (index)
10 2 Binary Output with Status 1 (read) 00, 01 (start-stop)
06 (no range)
07, 08 (limited qfy)
17, 28 (index)
129 (response) 00, 01 (start-stop)
17, 28 (index)
12 1 Contol Relay Output Block 3 (select)
4(operate)
5(direct op.)
6(dir. op. noack)
00, 01 (start-stop)
07, 08 (limited qfy)
17, 28 (index)
129 (response) echo of response
20 0 Binary Counter -
Any Variations
1(read) 00, 01 (start-stop)
06 (no range)
07, 08 (limited qfy)
17, 28 (index)
20 1 32-Bit Binary Counter
(with Flag)
1(read) 00, 01 (start-stop)
06 (no range)
07, 08 (limited qfy)
17, 28 (index)
22 0 Counter Change Event -
Any Variations
1(read) 06 (no range)
07, 08 (limited qfy)
22 1 32-Bit Counter Change Event
without Time
1(read) 06 (no range)
07, 08 (limited qfy)
Implementation Table
17
SIPROTEC DNP 3.0 - Bus mapping / Point lists 7SJ80/7SK80/7RW80
C53000-L2040-A320-2
30 0 16-Bit Analog Input -
Any Variations
1(read) 00, 01 (start-stop)
06 (no range)
07, 08 (limited qfy)
17, 28 (index)
30 1 32-Bit Analog Input with Status 1 (read) 00, 01 (start-stop)
06 (no range)
07, 08 (limited qfy)
17, 28 (index)
129 (response) 00, 01 (start-stop)
17, 28 (index)
30 2 16-Bit Analog Input with Status 1 (read) 00, 01 (start-stop)
06 (no range)
07, 08 (limited qfy)
17, 28 (index)
129 (response) 00, 01 (start-stop)
17, 28 (index)
32 0 Analog Change Event -
Any Variations
1(read) 06 (no range)
07, 08 (limited qfy)
32 1 32-Bit Analog Change Event
without Time
1(read) 06 (no range)
07, 08 (limited qfy)
129 (response)
130 (unsol. resp)
17, 28 (index)
32 2 16-Bit Analog Change Event
without Time
1(read) 06 (no range)
07, 08 (limited qfy)
129 (response)
130 (unsol. resp)
17, 28 (index)
50 1 Time and Date 2 (write) 07 (limited qfy = 1)
60 1 Class 0 Data 1 (read) 06 (no range)
60 2 Class 1 Data 1 (read) 06 (no range)
07, 08 (limited qfy)
60 3 Class 2 Data 1 (read) 06 (no range)
07, 08 (limited qfy)
60 4 Class 3 Data 1 (read) 06 (no range)
07, 08 (limited qfy)
80 1 Internal Indications 2 (write) 00 (start-stop)
(index must = 7)
OBJECTS REQUEST RESPONSE
Object Vari-
ation Description Function Codes
(dec) Qualifier Codes
(hex) Function Codes
(dec) Qualifier Codes
(hex)
DNP V3.0 Device Profile
18 SIPROTEC DNP 3.0 - Bus mapping / Point lists 7SJ80/7SK80/7RW80
C53000-L2040-A320-2
2.2 Device Profile Document
DNP V3.0
DEVICE PROFILE DOCUMENT
Vendor Name: SIEMENS AG
Device Name: 7SJ80/7SK80/7RW80
Highest DNP Level Supported:
For Requests DNP-L2
For Responses DNP-L2
Device Function:
Master Slave
Notable objects, functions, and/or qualifiers supported in addition to the Highest DNP Levels Supported (the
complete list is described in the attached table):
For static (non-change-event) object requests, request qualifier codes 00 and 01 (start-stop), 07 and 08 (lim-
ited quantity), and 17 and 28 (index) are supported in addition to request qualifier code 06 (no range). Static
object requests sent with qualifiers 00, 01, 06, 07, or 08, will be responded with qualifiers 00 or 01. Static ob-
ject requests sent with qualifiers 17 or 28 will be responded with qualifiers 17 or 28. For change-event object
requests, qualifiers 17 or 28 are always responded.
16-bit Analog Change Events with Time may be requested.
The write function code for Object 50 (Time and Date), variation 1, is supported.
The features outlined within this Device Profile have successfully passed DNP Conformance Test of Subset
Level 2 outlined in DNP3-2000 IED Certification Procedure.
Maximum Data Link Frame Size (octets):
Transmitted____292_____________
Received______292_____________
Maximum Application Fragment Size (octets):
Transmitted _Configurable up to 2048
Received_______2048_______
Maximum Data Link Re-tries:
None
Fixed at
Configurable, range _0_to _255_
Maximum Application Layer Re-tries:
None
Configurable, range ____ to _______
(Fixed is not permitted)
Requires Data Link Layer Confirmation:
Never
Always
Sometimes If 'Sometimes', when? ______________________________________
Configurable If 'Configurable', how? by the protection data processing program DIGSI 4
Device Profile Document
19
SIPROTEC DNP 3.0 - Bus mapping / Point lists 7SJ80/7SK80/7RW80
C53000-L2040-A320-2
Requires Application Layer Confirmation:
Never
Always (not recommended)
When reporting Event Data (Slave devices only)
When sending multi-fragment responses (Slave devices only)
Sometimes If 'Sometimes', when? ___________________________________
Configurable If 'Configurable', how? by the protection data processing program DIGSI 4
Timeouts while waiting for:
Data Link Confirm None Fixed at _____ Variable Configurable
Complete Appl. Fragment None Fixed at _____ Variable Configurable
Application Confirm None Fixed at _____ Variable Configurable
Complete Appl. Response None Fixed at _____ Variable Configurable
Others: Default value are configurable by the protection data processing program DIGSI 4
Sends/Executes Control Operations:
WRITE Binary Outputs Never Always Sometimes Configurable
SELECT/OPERATE Never Always Sometimes Configurable
DIRECT OPERATE Never Always Sometimes Configurable
DIRECT OPERATE - NO ACK Never Always Sometimes Configurable
Count > 1 Never Always Sometimes Configurable
Pulse On Never Always Sometimes Configurable
Pulse Off Never Always Sometimes Configurable
Latch On Never Always Sometimes Configurable
Latch Off Never Always Sometimes Configurable
Queue Never Always Sometimes Configurable
Clear Queue Never Always Sometimes Configurable
Note:
CONTROL RELAY OUTPUT BLOCK parameters (count, on-time, off-time) are ignored.
TimeSync Information:
a.) TimeSync Period
Never
Fixed at ________seconds
Configurable, range ____1____to __86400_seconds
b.) Maximum time base drift over 10 minute interval: ____30__ms
c.) Maximum Internal Time Reference Error when set via DNP: _____1__ms
d.) Maximum Delay Measurement error: ____20__ms
e.) Maximum response time: ___100__ms
c.) Event data time-tag error – if different than (c):
Binary Input Change Events __________ms
Counter Change Events __________ms
Frozen Counter Change Events __________ms
Analog Change Events __________ms
Frozen Analog Change Events __________ms
DNP V3.0 Device Profile
20 SIPROTEC DNP 3.0 - Bus mapping / Point lists 7SJ80/7SK80/7RW80
C53000-L2040-A320-2
Reports Binary Input Change Events when no spe-
cific variation requested:
Never
Only time-tagged
Only non-time-tagged
Configurable to send both, one or the
other (attach explanation)
Reports time-tagged Binary Input Change Events when
no specific variation requested:
Never
Binary Input Change With Time
Binary Input Change With Relative Time
Configurable (attach explanation)
Sends Unsolicited Responses:
Never
Configurable (Unsolicited data
response mode are switched
on/off via the configuration tool )
Only certain objects
Sometimes (attach explanation)
ENABLE/DISABLE UNSOLICITED
Function codes supported
Sends Static Data in Unsolicited Responses:
Never
When Device Restarts
When Status Flags Change
No other options are permitted.
Default Counter Object/Variation:
No Counters Reported
Configurable (attach explanation)
Default Object ___20_____
Default Variation ___01_____
Point-by-point list attached
Sends 32-Bit counters.
Counters Roll Over at:
No Counters Reported
Configurable (attach explanation)
16 Bits
32 Bits
Other Value _____________
Point-by-point list attached
Sends Multi-Fragment Responses: Yes No
21SIPROTEC DNP 3.0 - Bus mapping / Point lists 7SJ80/7SK80/7RW80
C53000-L2040-A320-2
Point lists 3
3.1 Functional Scope 22
3.2 Binary Input Points 25
3.3 Control Relay Output Blocks/Binary Output Status 31
3.4 Counters 34
3.5 Analog Inputs 35
Point lists
22 SIPROTEC DNP 3.0 - Bus mapping / Point lists 7SJ80/7SK80/7RW80
C53000-L2040-A320-2
3.1 Functional Scope
Depending of the functional scope, some of the following described functions, annun-
ciations, commands, measured and metered values are not available.
7SJ80
Table 3-1 7SJ80 Functional scope
No. Function Ref. to Chapter
103 Setting Group Change Option 3.2.14
104 Oscillographic Fault Records -
112 50/51 (Charac. Phase) Overcurrent Protection 3.2.2
113 50N/51N (Charac. Ground) Overcurrent Protection 3.2.2
115 67, 67-TOC Directional Overcurrent Protection 3.2.4
116 67N, 67N-TOC Directional Overcurrent Protection 3.2.4
117 Cold Load Pickup 3.3.2
122 2nd Harmonic Inrush Restraint 3.2.3
127 50 1Ph Single Phase Overcurrent Protection -
130 (sens.) Ground fault dir. characteristic 3.2.8
131 (sensitive) Ground fault 3.2.8
140 46 Negative Sequence Protection 3.2.5
142 49 Thermal Overload Protection -
150 27, 59 Under/Overvoltage Protection 3.2.7
154 81 Over/Underfrequency Protection 3.2.6
161 25 Function group 1 Synchronism and Voltage Check -
170 50BF Breaker Failure Protection -
171 79 Auto-Reclose Function 3.2.1
172 52 Breaker Wear Monitoring -
180 Fault Locator -
181 Line Sections for Fault Locator -
182 74TC Trip Circuit Supervision 3.2.11
192 Capacitive voltage measurement -
617 Port B usage -
Functional Scope
23
SIPROTEC DNP 3.0 - Bus mapping / Point lists 7SJ80/7SK80/7RW80
C53000-L2040-A320-2
7SK80
Table 3-2 7SK80 Functional scope
No. Function Ref. to Chapter
103 Setting Group Change Option 3.2.14
104 Oscillographic Fault Records -
112 50/51 (Charac. Phase) Overcurrent Protection 3.2.2
113 50N/51N (Charac. Ground) Overcurrent Protection 3.2.2
116 67N, 67N-TOC Directional Overcurrent Protection 3.2.4
117 Cold Load Pickup 3.3.2
122 2nd Harmonic Inrush Restraint 3.2.3
130 (sens.) Ground fault dir. characteristic 3.2.8
131 (sensitive) Ground fault 3.2.8
140 46 Negative Sequence Protection 3.2.5
141 48 Startup Supervision of Motors 3.2.10
142 49 Thermal Overload Protection -
143 66 Startup Counter for Motors 3.2.9
144 Load Jam Protection
150 27, 59 Under/Overvoltage Protection 3.2.7
154 81 Over/Underfrequency Protection 3.2.6
170 50BF Breaker Failure Protection -
172 52 Breaker Wear Monitoring -
182 74TC Trip Circuit Supervision 3.2.11
190 External Temperature Input -
191 Ext. Temperature Input Connection Type -
192 Capacitive voltage measurement -
617 Port B usage -
Point lists
24 SIPROTEC DNP 3.0 - Bus mapping / Point lists 7SJ80/7SK80/7RW80
C53000-L2040-A320-2
7RW80
Table 3-3 7RW80 Functional scope
No. Function Ref. to Chapter
103 Setting Group Change Option 3.2.14
104 Oscillographic Fault Records -
143 24 Overexcitation Protection
146 Jump of Voltage Vector -
150 27, 59 Under/Overvoltage Protection 3.2.7
152 VT Broken wire supervision -
154 81 Over/Underfrequency Protection 3.2.6
155 Load Restoration -
161 25 Function group 1 Synchronism and Voltage Check -
182 74TC Trip Circuit Supervision 3.2.11
617 Port B usage -
Binary Input Points
25
SIPROTEC DNP 3.0 - Bus mapping / Point lists 7SJ80/7SK80/7RW80
C53000-L2040-A320-2
3.2 Binary Input Points
Binary Input Points
Static (Steady-State) Object Number: 1
Change Event Object Number: 2
Request Function Codes supported: 1 (read)
Static Variation reported when variation 0 requested: 1 (Binary Input with status)
Change Event Variation reported when variation 0 requested: 2 (Binary Input Change with Time)
Point
Index Name Description Class
3.2.1 Auto-Reclose Function
0 >79 ON >79 ON; Automatic reclosure ON; ON = 1, OFF = 0 3
1 CB is NOT ready Circuit breaker is NOT ready; ON = 1, OFF = 0 2
2 79 DynBlock 79 – Auto-reclose is dynamically BLOCKED; ON = 1, OFF = 0 3
3 79 in progress 79 – in progress; ON = 1, OFF = 0 2
4 79 Close 79 – Close command; ON = 1 3
5 79 Successful 79 – cycle successful; ON = 1, OFF = 0 3
6 79 Lockout 79 – Lockout; ON = 1, OFF = 0 1
7 79 L_N Sequence 79-A/R single phase reclosing sequence; Program earthfault is running = 1, Pro-
gram is deactivated = 0
3
8 79 L-L Sequence 79-A/R multi-phase reclosing sequence; ON = 1, OFF = 0 3
3.2.2 Overcurrent Protection
9 50/51 PH ACT 50/51 O/C is ACTIVE; ON = 1, OFF = 0 3
10 50N/51N ACT 50N/51N is ACTIVE; ON = 1, OFF = 0 3
11 50 (N) / 51 (N) PU 50(N)/51(N) O/C PICKUP; ON = 1, OFF = 0 2
12 50/51 Ph A PU 50/51 Phase A picked up; ON = 1, OFF = 0 2
13 50/51 Ph B PU 50/51 Phase B picked up; ON = 1, OFF = 0 2
14 50/51 Ph C PU 50/51 Phase C picked up; ON = 1, OFF = 0 2
15 50N/51NPickedup 50N/51N picked up; ON = 1, OFF = 0 2
16 50 (N)/51(N)TRIP 50(N)/51(N) TRIP; ON = 1 2
3.2.3 InRush Function
17 PhA InrushBlk Phase A trip blocked by inrush detection; ON = 1, OFF = 0 3
18 PhB InrushBlk Phase B trip blocked by inrush detection; ON = 1, OFF = 0 3
19 PhC InrushBlk Phase C trip blocked by inrush detection; ON = 1, OFF = 0 3
20 INRUSH X-BLK Cross blk: PhX blocked Phy; ON = 1, OFF = 0 3
3.2.4 Directional Overcurrent Protection
21 67 ACTIVE 67/67-TOC is ACTIVE; activate = 1, deactivate = 0 3
22 67N ACTIVE 67N/67N-TOC is ACTIVE; activate = 1, deactivate = 0 3
23 67/67N pickedup 67/67N picked up; ON = 1, OFF = 0 2
24 67 A picked up 67/67-TOC Phase A picked up; ON = 1, OFF = 0 2
25 67 B picked up 67/67-TOC Phase B picked up; ON = 1, OFF = 0 2
26 67 C picked up 67/67-TOC Phase C picked up; ON = 1, OFF = 0 2
Point lists
26 SIPROTEC DNP 3.0 - Bus mapping / Point lists 7SJ80/7SK80/7RW80
C53000-L2040-A320-2
27 67N picked up 67N/67N-TOC picked up; ON = 1, OFF = 0 2
28 67/67N TRIP 67/67N TRIP; ON = 1, OFF = 0 2
3.2.5 Negative Sequence Protection
29 46 ACTIVE 46 is ACTIVE; ON = 1, OFF = 0 3
30 46-2 picked up 46-2 picked up; ON = 1, OFF = 0 2
31 46-TOC pickedup 46-TOC picked up; ON = 1, OFF = 0 2
32 46 TRIP 46 TRIP picked up; ON = 1, OFF = 0 2
33 46-1 picked up 46-1 picked up; ON = 1, OFF = 0 2
3.2.6 Over/Underfrequency Protection
34 81 ACTIVE 81 ACTIVE; ON = 1, OFF = 0 3
35 81-1 picked up 81-1 picked up; ON = 1, OFF = 0 2
36 81-2 picked up 81-2 picked up; ON = 1, OFF = 0 2
37 81-1 TRIP 81-1 TRIP; ON = 1, OFF = 0 2
38 81-2 TRIP 81-2 TRIP; ON = 1, OFF = 0 2
3.2.7 Under/Overvoltage Protection
39 27 ACTIVE 27 Undervoltage protection is ACTIVE; ON = 1, OFF = 0 3
40 27-1 picked up 27-1 Undervoltage picked up; ON = 1, OFF = 0 2
41 27-1 TRIP 27-1 Undervoltage TRIP; ON = 1, OFF = 0 2
42 59 ACTIVE 59-Overvoltage protection is ACTIVE; ON = 1, OFF = 0 3
43 59-1 picked up 59 picked up; ON = 1, OFF = 0 2
44 59-1 TRIP 59 TRIP; ON = 1, OFF = 0 2
3.2.8 (sensitive) Ground Fault Protection
45 50Ns/67Ns ACT 50Ns/67Ns is ACTIVE; ON = 1, OFF = 0 3
46 64 Pickup 64 displacement voltage pick up; ON = 1, OFF = 0 2
47 64 Trip 64 displacement voltage element TRIP; ON = 1, OFF = 0 2
48 50Ns-2 Pickup 50Ns-2 Pickup; ON = 1, OFF = 0 2
49 50Ns-2 TRIP 50Ns-2 TRIP; ON = 1, OFF = 0 2
50 50Ns-1 Pickup 50Ns-1 Pickup; ON = 1, OFF = 0 2
51 50Ns-1 TRIP 50Ns-1 TRIP; ON = 1, OFF = 0 2
52 Sens. Gnd Ph A Sensitive Ground fault picked up in Ph A; ON = 1, OFF = 0 2
53 Sens. Gnd Ph B Sensitive Ground fault picked up in Ph B; ON = 1, OFF = 0 2
54 Sens. Gnd Ph C Sensitive Ground fault picked up in Ph C; ON = 1, OFF = 0 2
55 SensGnd Forward Sensitive Gnd fault in forward direction; ON = 1, OFF = 0 2
56 SensGnd Reverse Sensitive Gnd fault in reverse direction; ON = 1, OFF = 0 2
Binary Input Points
Static (Steady-State) Object Number: 1
Change Event Object Number: 2
Request Function Codes supported: 1 (read)
Static Variation reported when variation 0 requested: 1 (Binary Inpu t with status)
Change Event Variation reported when variation 0 requested: 2 (Binary Input Change with Time)
Point
Index Name Description Class
Binary Input Points
27
SIPROTEC DNP 3.0 - Bus mapping / Point lists 7SJ80/7SK80/7RW80
C53000-L2040-A320-2
3.2.9 Startup Counter for Motor
57 66 ACTIVE 66 Motor start protection ACTIVE; ON = 1, OFF = 0 3
58 66 TRIP 66 Motor start protection TRIP; ON = 1, OFF = 0 2
3.2.10 Startup Supervision of Motors
59 START-SUP ACT Startup supervision is ACTIVE; ON = 1, OFF = 0 3
60 START-SUP TRIP Startup supervision TRIP; ON = 1, OFF = 0 2
61 START-SUP pu Startup supervision Pickup; ON = 1, OFF = 0 2
3.2.11 Trip Circuit Supervision
62 74TC ACTIVE 74TC Trip circuit supervision is ACTIVE; ON = 1, OFF = 0 3
63 FAIL: Trip cir. 74TCFailure Trip Circuit; ON = 1, OFF = 0 1
3.2.12 Internal Mode Status
64 Cntrl Auth Control Authority; LOCAL=1, REMOTE=0 3
65 ModeLOCAL Control mode LOCAL; UNLOCKED=1, LOCKED=0 3
66 Relay OK Relay OK; ON = 1, OFF = 0 1
67 Running Setting calculation is running; ON = 1, OFF = 0 3
68 ProtActive At least one protection funct. is active; ON=1, OFF=0 2
69 Error Sum Alarm Error with a summary alarm; ON = 1, OFF = 0
(ref. to chap. 1.1.1)
2
70 Alarm Sum Event Alarm Summary Event; ON = 1, OFF = 0
(ref. to chap. 1.1.2)
2
71 Relay Pickup Relay Pickup; ON = 1, OFF = 0 1
72 Relay TRIP General TRIP of the relay; ON = 1 1
73 Test mode Test mode; ON=1, OFF=0 3
3.2.13 Control switches return position indication(double point
commands)
74 52 Breaker input state of switch breaker; 0=open, 1=close 1
75 52 Breaker status switch breaker failure status; 0=switch breaker position is open or close, 1= switch
breaker is in an intermediate position or position state is incorrect.
1
76 Switch 1 input state of switch 1; 0=open, 1=close 1
77 switch 1 status switch 1 failure status; 0= switch 1 position is open or close, 1= switch 1 is in an in-
termediate position or position state is incorrect.
1
78 Switch 2 input state of switch 2; 0=open, 1=close 1
79 switch 2 status switch 2 failure status; 0= switch 1 position is open or close, 1= switch 1 is in an in-
termediate position or position state is incorrect.
1
80 Switch 3 input state of switch 3; 0=open, 1=close 1
81 switch 3 status switch 3 failure status; 0= switch 2 position is open or close, 1= switch 2 is in an in-
termediate position or position state is incorrect.
1
Binary Input Points
Static (Steady-State) Object Number: 1
Change Event Object Number: 2
Request Function Codes supported: 1 (read)
Static Variation reported when variation 0 requested: 1 (Binary Input with status)
Change Event Variation reported when variation 0 requested: 2 (Binary Input Change with Time)
Point
Index Name Description Class
Point lists
28 SIPROTEC DNP 3.0 - Bus mapping / Point lists 7SJ80/7SK80/7RW80
C53000-L2040-A320-2
82 Switch 4 input state of switch 4; 0=open, 1=close 1
83 switch 4 status switch 4 failure status; 0= switch 3 position is open or close, 1= switch 3 is in an in-
termediate position or position state is incorrect.
1
84 Switch 5 input state of switch 5; 0=open, 1=close 1
85 switch 5 status switch 5 failure status; 0= switch 4 position is open or close, 1= switch 4 is in an in-
termediate position or position state is incorrect.
1
86 Switch 6 input state of switch 6; 0=open, 1=close 1
87 switch 6 status switch 6 failure status; 0= switch 5 position is open or close, 1= switch 5 is in an in-
termediate position or position state is incorrect.
1
88 Switch 7 input state of switch 7; 0=open, 1=close 1
89 switch 7 status switch 7 failure status; 0= switch 6 position is open or close, 1= switch 6 is in an in-
termediate position or position state is incorrect.
1
90 Switch 8 input state of switch 8; 0=open, 1=close 1
91 switch 8 status switch 8 failure status; 0= switch 6 position is open or close, 1= switch 6 is in an in-
termediate position or position state is incorrect.
1
3.2.14 Internal controls
92 Group A Protection Parameter Group A; 0 = Group A is deactivated, 1= Group A is activat-
ed and Group B,C,D are deactivated.
1
93 Group B Protection Parameter Group B; 0 = Group B is deactivated, 1= Group B is activat-
ed and Group A,C,D are deactivated.
1
94 Group C Protection Parameter Group C; 0 = Group C is deactivated, 1= Group C is activat-
ed and Group A,B,D are deactivated.
1
95 Group D Protection Parameter Group D; 0 = Group D is deactivated, 1= Group D is activat-
ed and Group A,B,C are deactivated.
1
96 ModeREMOTE Control mode REMOTE; UNLOCKED=1, LOCKED=0 3
3.2.15 Output channels return position indication (Single point
commands)
97 >switch 1 0 = Open (off), 1= Close (on) 1
98 >switch 2 0 = Open (off), 1= Close (on) 1
99 >switch 3 0 = Open (off), 1= Close (on) 1
100 >switch 4 0 = Open (off), 1= Close (on) 1
101 >switch 5 0 = Open (off), 1= Close (on) 1
102 >switch 6 0 = Open (off), 1= Close (on) 1
103 >switch 7 0 = Open (off), 1= Close (on) 1
104 >switch 8 0 = Open (off), 1= Close (on) 1
105 >switch 9 0 = Open (off), 1= Close (on) 1
106 >switch 10 0 = Open (off), 1= Close (on) 1
107 >switch 11 0 = Open (off), 1= Close (on) 1
Binary Input Points
Static (Steady-State) Object Number: 1
Change Event Object Number: 2
Request Function Codes supported: 1 (read)
Static Variation reported when variation 0 requested: 1 (Binary Inpu t with status)
Change Event Variation reported when variation 0 requested: 2 (Binary Input Change with Time)
Point
Index Name Description Class
Binary Input Points
29
SIPROTEC DNP 3.0 - Bus mapping / Point lists 7SJ80/7SK80/7RW80
C53000-L2040-A320-2
108 >switch 12 0 = Open (off), 1= Close (on) 1
109 >switch 13 0 = Open (off), 1= Close (on) 1
110 >switch 14 0 = Open (off), 1= Close (on) 1
111 >switch 15 0 = Open (off), 1= Close (on) 1
112 >switch 16 0 = Open (off), 1= Close (on) 1
113 >switch 17 0 = Open (off), 1= Close (on) 1
114 >switch 18 0 = Open (off), 1= Close (on) 1
115 >switch 19 0 = Open (off), 1= Close (on) 1
116 >switch 20 0 = Open (off), 1= Close (on) 1
117 >switch 21 0 = Open (off), 1= Close (on) 1
118 >switch 22 0 = Open (off), 1= Close (on) 1
119 >switch 23 0 = Open (off), 1= Close (on) 1
120 >switch 24 0 = Open (off), 1= Close (on) 1
121 >switch 25 0 = Open (off), 1= Close (on) 1
3.2.16 Internal controls
122 <unnamed>1User input 1 2
123 <unnamed> User input 2 2
124 <unnamed> User input 3 2
125 <unnamed> User input 4 2
126 <unnamed> User input 5 2
127 <unnamed> User input 6 2
128 <unnamed> User input 7 2
129 <unnamed> User input 8 2
130 <unnamed> User input 9 2
131 <unnamed> User input 10 2
132 <unnamed> User input 11 2
133 <unnamed> User input 12 2
134 <unnamed> User input 13 2
135 <unnamed> User input 14 2
136 <unnamed> User input 15 2
137 <unnamed> User input 16 2
138 <unnamed> User input 17 2
139 <unnamed> User input 18 2
140 <unnamed> User input 19 2
Binary Input Points
Static (Steady-State) Object Number: 1
Change Event Object Number: 2
Request Function Codes supported: 1 (read)
Static Variation reported when variation 0 requested: 1 (Binary Input with status)
Change Event Variation reported when variation 0 requested: 2 (Binary Input Change with Time)
Point
Index Name Description Class
Point lists
30 SIPROTEC DNP 3.0 - Bus mapping / Point lists 7SJ80/7SK80/7RW80
C53000-L2040-A320-2
141 <unnamed> User input 20 2
142 <unnamed> User input 21 2
143 <unnamed> User input 22 2
144 <unnamed> User input 23 2
145 <unnamed> User input 24 2
146 <unnamed> User input 25 2
147 <unnamed> User input 26 2
148 <unnamed> User input 27 2
149 <unnamed> User input 28 2
150 <unnamed> User input 29 2
151 <unnamed> User input 30 2
152 <unnamed> User input 31 2
153 <unnamed> User input 32 2
154 <unnamed> User input 33 2
155 <unnamed> User input 34 2
156 <unnamed> User input 35 2
157 <unnamed> User input 36 2
158 <unnamed> User input 37 2
159 <unnamed> User input 38 2
160 <unnamed> User input 39 2
1The names are defined during indication allocation using parametrization softwareDIGSI 4
Binary Input Points
Static (Steady-State) Object Number: 1
Change Event Object Number: 2
Request Function Codes supported: 1 (read)
Static Variation reported when variation 0 requested: 1 (Binary Inpu t with status)
Change Event Variation reported when variation 0 requested: 2 (Binary Input Change with Time)
Point
Index Name Description Class
Control Relay Output Blocks/Binary Output Status
31
SIPROTEC DNP 3.0 - Bus mapping / Point lists 7SJ80/7SK80/7RW80
C53000-L2040-A320-2
3.3 Control Relay Output Blocks/Binary Output Status
Binary Output Status Points
Object Number: 10
Request Function Codes supported: 1 (Read)
Default Variation reported when variation 0 requested: 2 (Binary Output Status )
Control Relay Output Blocks/Binary Output Status
Object Number: 12
Request Function Codes supported: 3 (select), 4 (operate), 5 (direct operate), 6 (direct operate, no ack)
Point In-
dex Name Description Supported Control
Relay Output Block
Fields
3.3.1 External commands (Double point commands)
0 52Breaker Trip Breaker switch Trip, Pulse On
(On Time Fixed1)
1 52Breaker Close Breaker switch Close, Pulse On
(On Time Fixed)
2 Switch 1 Trip switch 1 Trip, Pulse On
(On Time Fixed)
3 Switch 1 Close switch 1 Close, Pulse On
(On Time Fixed)
4 Switch 2 Trip switch 2 Trip, Pulse On
(On Time Fixed)
5 Switch 2 Close switch 2 Close, Pulse On
(On Time Fixed)
6 Switch 3 Trip switch 3 Trip, Pulse On
(On Time Fixed)
7 Switch 3 Close switch 3 Close, Pulse On
(On Time Fixed)
8 Switch 4 Trip switch 4 Trip, Pulse On
(On Time Fixed)
9 Switch 4 Close switch 4 Close, Pulse On
(On Time Fixed)
10 Switch 5 Trip switch 5 Trip, Pulse On
(On Time Fixed)
11 Switch 5 Close switch 5 Close, Pulse On
(On Time Fixed)
12 Switch 6 Trip switch 6 Trip, Pulse On
(On Time Fixed)
13 Switch 6 Close switch 6 Close, Pulse On
(On Time Fixed)
14 Switch 7 Trip switch 7 Trip, Pulse On
(On Time Fixed)
15 Switch 7 Close switch 7 Close, Pulse On
(On Time Fixed)
16 Switch 8 Trip switch 8 Trip, Pulse On
(On Time Fixed)
17 Switch 8 Close switch 8 Close, Pulse On
(On Time Fixed)
Point lists
32 SIPROTEC DNP 3.0 - Bus mapping / Point lists 7SJ80/7SK80/7RW80
C53000-L2040-A320-2
3.3.2 Internal commands
18 Group A Select parametergroup A and deactivate parametergroup B,C,D ref.
to chap. 1.2.3
Latch On
19 Group B Select parametergroup B and deactivate parametergroup A,C,D Latch On
20 Group C Select parametergroup C and deactivate parametergroup A,B,D Latch On
21 Group D Select parametergroup D and deactivate parametergroup A,B,C Latch On
22 ModeREMOTE Mode remote control; Latch On = UNLOCKED
Lath Off = LOCKED (ref. to chap.1.2.2 )
Latch On; Latch Off
3.3.3 Output channel (user defined single point output
commands)
Please ref to chap. 1.2.1 for additional notes.
23 Output 12Output channel 1 Latch On, Latch Off, Pulse
On
24 Output 2 Output channel 2 Latch On, Latch Off, Pulse
On
25 Output 3 Output channel 3 Latch On, Latch Off, Pulse
On
26 Output 4 Output channel 4 Latch On, Latch Off, Pulse
On
27 Output 5 Output channel 5 Latch On, Latch Off, Pulse
On
28 Output 6 Output channel 6 Latch On, Latch Off, Pulse
On
29 Output 7 Output channel 7 Latch On, Latch Off, Pulse
On
30 Output 8 Output channel 8 Latch On, Latch Off, Pulse
On
31 Output 9 Output channel 9 Latch On, Latch Off, Pulse
On
32 Output 10 Output channel 10 Latch On, Latch Off, Pulse
On
33 Output 11 Output channel 11 Latch On, Latch Off, Pulse
On
34 Output 12 Output channel12 Latch On, Latch Off, Pulse
On
35 Output 13 Output channel 13 Latch On, Latch Off, Pulse
On
Binary Output Status Points
Object Number: 10
Request Function Codes supported: 1 (Read)
Default Variation reported when variation 0 requested: 2 (Binary Output Status)
Control Relay Output Blocks/Binary Output Status
Object Number: 12
Request Function Codes supported: 3 (select), 4 (operate), 5 (direct operate), 6 (direct operate, no ack)
Point In-
dex Name Description Supported Control
Relay Output Block
Fields
Control Relay Output Blocks/Binary Output Status
33
SIPROTEC DNP 3.0 - Bus mapping / Point lists 7SJ80/7SK80/7RW80
C53000-L2040-A320-2
36 Output 14 Output channel 14 Latch On, Latch Off, Pulse
On
37 Output 15 Output channel 15 Latch On, Latch Off, Pulse
On
38 Output 16 Output channel 16 Latch On, Latch Off, Pulse
On
39 Output 17 Output channel 17 Latch On, Latch Off, Pulse
On
40 Output 18 Output channel 18 Latch On, Latch Off, Pulse
On
41 Output 19 Output channel 19 Latch On, Latch Off, Pulse
On
42 Output 20 Output channel 20 Latch On, Latch Off, Pulse
On
43 Output 21 Output channel 21 Latch On, Latch Off, Pulse
On
44 Output 22 Output channel 22 Latch On, Latch Off, Pulse
On
45 Output 23 Output channel 23 Latch On, Latch Off, Pulse
On
46 Output 24 Output channel 24 Latch On, Latch Off, Pulse
On
47 Output 25 Output channel 25 Latch On, Latch Off, Pulse
On
1The On-Time is fixed within theSIPROTEC parameter package for each commond object. The Control Relay Output Block in-
formation on-time will be ignored.
2The names are defined during indication allocation using parametrization softwareDIGSI 4
Binary Output Status Points
Object Number: 10
Request Function Codes supported: 1 (Read)
Default Variation reported when variation 0 requested: 2 (Binary Output Status )
Control Relay Output Blocks/Binary Output Status
Object Number: 12
Request Function Codes supported: 3 (select), 4 (operate), 5 (direct operate), 6 (direct operate, no ack)
Point In-
dex Name Description Supported Control
Relay Output Block
Fields
Point lists
34 SIPROTEC DNP 3.0 - Bus mapping / Point lists 7SJ80/7SK80/7RW80
C53000-L2040-A320-2
3.4 Counters
Counters
Static (Steady-State) Object Number: 20
Change Event Object Number: 22
Request Function Codes supported: 1 (read)
Static Variation reported when variation 0 requested: 1 (32-Bit Counter with Flag)
Change Event Variation reported when variation 0 requested: 1 (32-Bit Counter without Time)
Point In-
dex Name Description Scaling(232-1 of the unsigned long-
value corresponds to...)
0 Wp+= Wp Forward (metered measurand derived from measured value) 232-1 impulses
1 Wq+= Wq Forward (metered measurand derived from measured value) 232-1 impulses
2 Wp-= Wp Reverse (metered measurand derived from measured value) 232-1 impulses
3 Wq-= Wq Reverse (metered measurand derived from measured value) 232-1 impulses
4 Wp(puls) = Pulsed Energy Wp (active)(metering impulses at binary input) 232-1 impulses
5 Wq(puls) = Pulsed Energy Wq (reactive)(metering impulses at binary input) 232-1 impulses
Analog Inputs
35
SIPROTEC DNP 3.0 - Bus mapping / Point lists 7SJ80/7SK80/7RW80
C53000-L2040-A320-2
3.5 Analog Inputs
Analog Inputs
Static (Steady-State) Object Number: 30
Change Event Object Number: 32
Request Function Codes supported: 1 (read)
Static Variation reported when variation 0 requested: 02 (16-Bit Analog Input)
Change Event Variation reported when variation 0 requested:02 (Analog Change Event without Time)
Point In-
dex Name Description Scaling(32767 corre-
sponds to ...) Default Change
Event assigned
Class
3.5.1 Recorded measured values
0 la= Current phase a 3276.7 A 1
1 lb= Current phase b 3276.7 A 1
2 lc= Current phase c 3276.7 A 1
3 I0= Current I0 3276.7 A 1
4 Va= Voltage phase a 32.767 kV 1
5 Vb= Voltage phase b 32.767 kV 1
6 Vc= Voltage phase c 32.767 kV 1
7 Va-b= Voltage phase a to phase b 32.767 kV 1
8 Vb-c= Voltage phase b to phase c 32.767 kV 1
9 Vc-a= Voltage phase c to phase a 32.767 kV 1
10 V= Voltage Ground 32.767 kV 1
11 P= Active power 32767 kW 1
12 Q= Reactive power 32767 kVar 1
13 S= Apparent power 32767 kVar 1
14 Freq= frequency 327.67 Hz 1
15 cos φ= power factor 3.2767 1
16 UsrMv1 user defined measurement 3276.7 1
17 UsrMv2 user defined measurement 3276.7 1
18 UsrMv3 user defined measurement 3276.7 1
19 UsrMv4 user defined measurement 3276.7 1
20 UsrMv5 user defined measurement 3276.7 1
21 UsrMv6 user defined measurement 3276.7 1
22 UsrMv7 user defined measurement 3276.7 1
23 UsrMv8 user defined measurement 3276.7 1
24 UsrMv9 user defined measurement 3276.7 1
25 UsrMv10 user defined measurement 3276.7 1
26 UsrMv11 user defined measurement 3276.7 1
27 UsrMv12 user defined measurement 3276.7 1
3.5.2 Min/Max values
28 la Min= Current phase a minimum 3276.7 A 3
Point lists
36 SIPROTEC DNP 3.0 - Bus mapping / Point lists 7SJ80/7SK80/7RW80
C53000-L2040-A320-2
29 la Max= Current phase a maximum 3276.7 A 3
30 lb Min= Current phase b minimum 3276.7 A 3
31 lb Max= Current phase b maximum 3276.7 A 3
32 lc Min= Current phase c minimum 3276.7 A 3
33 lc Max= Current phase c maximum 3276.7 A 3
34 Va-n Min= Voltage phase a minimum 32.767 kV 3
35 Va-nMax= Voltage phase a maximum 32.767 kV 3
36 Vb-nMin= Voltage phase b minimum 32.767 kV 3
37 Vb-nMax= Voltage phase b maximum 32.767 kV 3
38 Vc-nMin= Voltage phase c minimum 32.767 kV 3
39 Vc-nMax= Voltage phase c maximum 32.767 kV 3
40 Vn Min= Voltage neutral minimum 32.767 kV 3
41 Vn Max= Voltage neutral maximum 32.767 kV 3
42 P Min= Active power minimum 32767 kW 3
43 P Max= Active power maximum 32767 kW 3
44 Q Min= Reactive power minimum 32767 kVar 3
45 Q Max= Reactive power maximum 32767 kVar 3
46 S Min= Apparent power minimum 32767 kVar 3
47 S Max= Apparent power maximum 32767 kVar 3
48 f Min= frequency Minimum 327.67 Hz 3
49 f Max= frequency Maximum 327.67 Hz 3
50 cos φ min= Power factor minimum 3.2767 3
51 cos φ max= Power factor maximum 3.2767 3
If Object 30 Variation 01 (32-Bit Analog Input) requesten, additional:
3.5.3 Statistic values
52 (0)Ia= Trip Current phase a 32767 A 1
53 (0)Ib= Trip Current phase b 32767 A 1
54 (0)Ic= Trip Current phase c 32767 A 1
55 Sum Ia = Accumulation of interrupted current Ph A 327.67 kA 3
56 Sum Ib = Accumulation of interrupted current Ph B 327.67 kA 3
57 Sum Ic = Accumulation of interrupted current Ph C 327.67 kA 3
Analog Inputs
Static (Steady-State) Object Number: 30
Change Event Object Number: 32
Request Function Codes supported: 1 (read)
Static Variation reported when variation 0 requested: 02 (16-Bit Analog Input)
Change Event Variation reported when variation 0 requested:02 (Analog Change Event without Time)
Point In-
dex Name Description Scaling(32767 corre-
sponds to ...) Default Change
Event assigned
Class
Analog Inputs
37
SIPROTEC DNP 3.0 - Bus mapping / Point lists 7SJ80/7SK80/7RW80
C53000-L2040-A320-2
58 Op. Hours= Counter of operating hours 32767 h 1
59 <unnamed> User input 2 3
60 <unnamed> User input 2 3
Analog Inputs
Static (Steady-State) Object Number: 30
Change Event Object Number: 32
Request Function Codes supported: 1 (read)
Static Variation reported when variation 0 requested: 02 (16-Bit Analog Input)
Change Event Variation reported when variation 0 requested:02 (Analog Change Event without Time)
Point In-
dex Name Description Scaling(32767 corre-
sponds to ...) Default Change
Event assigned
Class
Point lists
38 SIPROTEC DNP 3.0 - Bus mapping / Point lists 7SJ80/7SK80/7RW80
C53000-L2040-A320-2
39SIPROTEC DNP 3.0 - Bus mapping / Point lists 7SJ80/7SK80/7RW80
C53000-L2040-A320-2
Glossary
AME Asynchronous interface module with (electrical) isolated RS485 interface for the
SIPROTEC devices from Siemens.
AMO Asynchronous interface module with optical interface for the SIPROTEC devices from
Siemens.
AR Automatic Recloser
CFC Continuous Function Chart
DC Double Command
DIGSI Parameterization system for SIPROTEC devices
DNP Distributed Network Protocol
DP Double-point Indication
Input data/
input direction Data from the DNP slave to th e DNP master.
Mapping Allocation of the SIPROTEC data objects to the DNP point index.
Output data/
output direction Data from the DNP master to the DNP slave.
RTU Remote Terminal Unit
SC Single Command
SP Single-point Indication
40 SIPROTEC DNP 3.0 - Bus mapping / Point lists 7SJ80/7SK80/7RW80
C53000-L2040-A320-2
Index
41
SIPROTEC DNP 3.0 - Bus mapping / Point lists 7SJ80/7SK80/7RW80
C53000-L2040-A320-2
Index
A
Additional support ............................................4
Alarm summary event ....................................10
Analog Inputs .......................................... 12, 35
Applicability of manual .....................................4
B
Binary Input Points .................................. 10, 25
Binary Outputs / Commands ................... 11, 31
C
Caution (definition) ...........................................5
Command output ............................................11
continuous output ...........................................11
Control authority .............................................11
Control mode ..................................................11
Copyright ..........................................................2
Counters .........................................................34
D
Danger (definition) ............................................5
Device Profile Document ...............................18
DNP messages ................................................4
DNP V3.0 specification ....................................4
I
Implementation Table ....................................16
M
Metered measurands .....................................13
N
Note (definition) ................................................5
P
Parameter names .............................................6
Parameter options ............................................6
Pulse output ...................................................11
pulse output ....................................................11
Q
Qualified personnel (definition) ........................5
S
Scaling of the metered measurands ..............13
Scaling values ................................................12
Setting group ..................................................12
Stop data transmission ...................................11
Subset Level 2 ................................................16
Subset Level 3 ................................................16
Summary alarm ..............................................10
Symbol conventions .........................................6
T
Target audience of manual ..............................3
Typographic conventions .................................6
V
Validity ..............................................................4
W
Warning (definition) ..........................................5
Index